General settings
From the standby mode screen, pr
ess the “OK”
key to access the first line of menus.
Use the “▲” and “▼” keys to position the cursor
over the “SETTINGS” screen. Press the “◄” key
to access the general settings from the
"SETTINGS" screen.
The general setting "Identification" can be
viewed from the HMI, but it can only be modified
by using the SICom program.
The value of the "CT Phase ratio” and “CT
Neutral ratio” general settings, is the result given
by dividing the number of turns on the primary
winding by the number on the secondary
winding. For example: With TI 500/5, the setting
would be 100.
(*) Depending on model
How to set CT Ratio
Pressing “OK” key from the standby screen it is displayed
MEASUREMENT menu.
Use “▼” key till SETTINGS menu appears. Pressing “◄” key it is
accessed to GENERAL settings.
Use “▼” key to overview the options and press “OK” when “CT
Phase Ratio
” option appears.
After inserting the password 5555 it will be possible to adjust the
wanted value