LE-03MB - User manual
40
9.14. Set up the output mode of pulse 1
Start L field L field Start C field A field C field
Data
Check
sum
Stop
68
08
08
68
11
addr
11
01/02/04/05/06/08
CS
16
Example: (Meter address is 01)
Master to Slave: 68 04 04 68 11 01 11
01
24 16
Slave to Master: E5
The red-lighted 01 represents the output mode of Pulse1:
01: Import active energy
02: export active energy
04: Export active energy (default)
05: Import reactive energy
06: export reactive energy
08: Export reactive energy
9.15. Read the constant of pulse 1
Start L field L field Start C field A field C field
Check
sum
Stop
68
03
03
68
11
addr
12
CS
16
Example: (Meter address is 01)
Master to Slave: 68 03 03 68 11 01 12 24 16
Slave to Master: 68 04 04 68 11 01 10
00
22 16
The red-lighted
00
represents the constant of pulse 1:
00: 0.0025 kwh (kvarh)/pulse (default)
01: 0.01 kWh (kvarh)/pulse
02: 0.1 kWh (kvarh)/pulse
03: 1 kWh (kvarh)/pulse
04: 10 kWh (kvarh)/pulse
05: 100 kWh (kvarh)/pulse
9.16. Set up the constant of pulse 1
Start L field L field Start C field A field C field
Data
Check
sum
Stop
68
08
08
68
11
addr
11
00/01/02/03/04/05
CS
16
Example:
(Meter address is 01)
Master to Slave:
68 04 04 68 11 01 13
00
25 16
Slave to Master:
E5