LE-03MB - User manual
39
9.11. Read the measurement mode
Start L field
L field
Start C field
A field
CI field
Data
Check sum
Stop
68
03
03
68
11
addr
09
01/02/03
CS
16
Example:
(Meter address is 01)
Master to Slave:
68 03 03 68 11
01
09 1B 16
Slave to Master:
68 04 04 68 11 01 09
01
1C 16
The red-lighted 01 represents the measurement mode:
01: means active energy
02: means active reactive energy
03: means active energy - reactive energy
9.12. Set up the measurement mode
Start L field L field
Start C field
A field
C field
Data
Check sum
Stop
68
04
04
68
11
addr
0A
01/02/03
CS
16
Example:
(Meter address is 01)
Master to Slave:
68 04 04 68 11 01 0A
01
1C 16
Slave to Master:
E5
The red-lighted
01
represents the measurement mode:
01: means active energy
02: means active reactive energy
03: means active energy - reactive energy
9.13. Read the output mode of pulse 1
Start
L field
L field
Start
C field
A field
C field
Check sum
Stop
68
03
03
68
11
addr
10
CS
16
Example:
(Meter address is 01)
Master to Slave:
68 03 03 68 11 01 10 22 16
Slave to Master:
68 04 04 68 11 01 10
01
23 16
The red-lighted
01
represents the output mode of pulse 1:
01: Import active energy
02: export active energy
04: Export active energy (default)
05: Import reactive energy
06: export reactive energy
08: Export reactive energy