Battery Capacity Indicator
During battery mode operation, the battery capacity indicator will show approximate percentage of
battery capacity remaining. The low battery alarm will begin to sound when 25% capacity is remaining.
The battery voltage meter can be used in conjunction with the capacity indicator to verify the remaining
capacity. Use the set / alarm silence button on the front panel to access battery voltage.
Battery
Percentage
Battery
Voltage
100% >211.2VDC
75%
198.4VDC ~ 211.2VDC
50%
176VDC ~ 198.4VDC
25%
168VDC ~ 176VDC
Battery Self-test
Note: When performing battery self-test, a minimum of 500W load should be applied to the UPS
to provide accurate battery capacity.
1. While the UPS is operating in online mode, press the set / alarm silence button three times until
the battery voltage metering is displayed.
2. While the UPS is operating in online mode, press and hold the function / test button for about
one second, then release.
3. If the batteries are in good condition, the UPS will beep 6 times while the test is being
performed. During this time the battery voltage meter and capacity icon will display the current
condition.
4. If a single, long audible tone sounds and the unit does not switch to battery mode, this indicates
the following possible situations: the batteries are dead / defective or installed incorrectly, the
battery pack is not installed, the battery bank interconnect cable is not installed, or the battery
fuse is missing / defective. If the problem cannot be resolved, contact Falcon Service.
Содержание SSG6KRM-2
Страница 2: ...2...
Страница 5: ...5 Double Conversion On line UPS Block Diagram...
Страница 7: ...7 Symbols Important Instruction Special Note Recycle Do not dispose with ordinary trash...
Страница 12: ...12 SSGR SSGR 1 2 Models...
Страница 25: ...25 SSG6KRM 2TXI With Transformer Module Warning Utility sources must be of the same phase...
Страница 27: ...27 Single Output Configuration 120VAC...