background image

CHAPTER

CHAPTER

5

5

OPERATION

The FALCON

®

ED unit is very simple to use.

1.

Be sure the power cord is plugged into the nearest 
available, appropriately rated wall outlet.

2.

Activate the power switch to the "ON" position.

3.

The green AC LED illuminates.

4.

The green INV LED illuminates.

5.

Leave the power switch "ON" and unplug the power cord from the 
wall. This will simulate a power loss to test battery operation.

6.

The green AC LED will shut off.

7.

An intermittent audible alarm will sound.

The system will continue to operate.  If this were to continue for a long 
while, the red LOW BATTERY light would illuminate, indicating that 
battery back-up time is ending and system shutdown is imminent.  The 
intermittent alarm will become continuous at this point.  The ED unit will 
automatically shut itself off to avoid excessive battery discharge.  When 
power returns, normal operation of the UPS resumes without any 
operator adjustment.

The duration of actual battery back-up time and the low battery condition 
varies depending on the amount of load, charge on the battery, and 
condition of the battery.  See SPECIFICATIONS on page 4 for 
approximate backu[ times.

8.

Plug the system power cord in again and turn the power switch 
"OFF".

9.

Turn off the devices you wish to plug into the UPS.  Plug them into
the outlets labeled UPS OUTPUT at the rear of the UPS.

10.

Activate the ED unit power switch to the "ON" position.

11.

Turn "ON" each of your devices.

12.

Some of the LOAD indicators may illuminate.  The amount of load 
determines the actual number of indicators lit.
The bottom green L.E.D. signifies approximately 50% of load 
capacity.  The second green L.E.D. represents approximately 75% 
of load capacity.  If the yellow L.E.D. illuminates, full load has been
achieved. If the red light illuminates, an OVERLOAD condition is 
present. If this situation continues for about 15 seconds, the unit 
will automatically shut off.
If the system overheats or the Inverter should fail, the unit 
automatically transfers the load to a filtered bypass line, sounds a 
continuous alarm and the red ALM light will illuminate.

9

Содержание ED-1000-1

Страница 1: ...1 FALCON ELECTRIC INC 5106 Azusa Canyon Road Irwindale CA 91706 Tel 626 962 7770 Fax 626 962 7720 The information contained herein is the property of FALCON ELECTRIC This information is proprietary co...

Страница 2: ...n 6 Front Panel LED Functions 6 Rear Panel Diagram Description 7 Chapter 4 Communications Interface 8 Signals Interfacing 8 Chapter 5 Operation 9 Step By Step Operating Procedure 9 Operational Mode Ta...

Страница 3: ...detergent on the UPS Never attempt to service batteries High voltage exists within the unit which could cause electrical shock Servicing of batteries should be performed or supervised by personnel kno...

Страница 4: ...Also your understanding of the product is essential in providing you years of service for your back up power requirements Refer to the cross reference table below to understand which unit with its pow...

Страница 5: ...is considered a non linear load which can be very abusive to most power protection equipment and could decrease its life expectancy The FALCON ED unit is specially devised to accept these loads and p...

Страница 6: ...Maintenance Free Back Up Time Full Load 1 2 Load 8 Minutes 20 Minutes 5 Minutes 14 Minutes 3 Minutes 9 minutes Battery times are approximate Electrical Connections Input 6 Cord with 5 15P 8 Cord with...

Страница 7: ...te label located on the rear panel of the unit 3 This UPS has been shipped with the battery connection fuse removed to meet new transportation regulations THE BATTERY CONNECTION FUSE MUST BE INSTALLED...

Страница 8: ...d LED turns on and a continuous audible alarm is sounded when the UPS is overloaded or has failed Should this occur check the load level and correct any overload condition if present During this condi...

Страница 9: ...access to the UPS contact closure status interface Please reference page 9 of this manual for details 9 UPS Model Identification Label 10 Inlet for Input Line Cord on ED1000 1 only Line cord permenen...

Страница 10: ...CHAPTER CHAPTER 4 4 DB 9 COMMUNICATIONS INTERFACE 8...

Страница 11: ...actual battery back up time and the low battery condition varies depending on the amount of load charge on the battery and condition of the battery See SPECIFICATIONS on page 4 for approximate backu...

Страница 12: ...ower switch ON at all times and switch your devices OFF individually This will insure that your batteries are always at a maximum charged state The power switch acts as a system ON OFF switch When thi...

Страница 13: ...years Never attempt to service batteries High voltage exists within the unit which could cause electrical shock Servicing of batteries should be performed or supervised by personnel knowledgeable of...

Страница 14: ...urer s instructions may cause interference to radio and television reception All models covered in this manual have been tested and found to comply with the limits for a Class A computing device in ac...

Страница 15: ...r unit s historical records The RMA number issued must appear on the outside of the shipping carton The original shipping container must be used when returning any ED Series product Falcon Electric wi...

Страница 16: ...the nature of the trouble experienced and the disposition of the equipment after repair The equipment will be returned freight collect by FALCON to the location specified via the best and least expen...

Отзывы: