MODEL SELECTION GUIDE

4

Model Number  

ED-1000-1 

ED-1500-1 

ED-2000-1 

ED-2400-1 

(ED-2500-1) 

Nominal VA  

1000 

1500 

2000 

2400 

(2500) 

    

Electrical Input  

AC Voltage,  +10%  -20% 

120Vac 

Current-Amps  

10.4 

15.6 

20.8 

22 (24) 

Frequency Range  

47-450 Hz 

    

Electrical Output  

AC Voltage,  

±

 3% 

120Vac 

Watts @ 50 or 60 Hz  

700 

1050 

1400 

1680 (1750) 

Watts @ 400 Hz  

595 

892 

1190 

1487 (1550) 

Current-Amps @ 50/60 Hz  

8.3 

12.5 

16.7 

20 (20.8) 

Current-Amps @ 400 Hz 

7.1 

10.6 

14.2 

17 (18.0) 

50/60 Hz Non  – Linear  
Repetitive Peak (Amps)  

20 

30 

40 

48 

400 Hz Non  – Linear   
Repetitive Peak  (Amps) 

14.2 

21.3 

28.3 

33 

Total Harmonic Distortion

 

< 3% @ 100% Linear Load, < 5% @ 100% Non  – Linear Load

 

Overload

 

200% for 0.5 Seconds, 120% for 30 Seconds

 

Dynamic Response

 

±

 5% RMS for 100% Step Load Chang e, 1ms Recovery Time

 

Output Protection

 

 Short Circuit and Overload

 

    

Battery 

Type 

Sealed Lead Acid Maintenance -Free 

Back Up Time                @ Full Load  
                                     @ 1/2  Load  

8 Minutes  

20 Minutes  

5 Minutes  

14 Minutes  

3 Minutes 
9 minutes  

    Battery times are approximate.  

    

Electrical Connections  

Input 

6’ Cord with 5 -15P 

8’ Cord with 5 -20P 

8’ Cord with  

 L5-30P 

Output 

(4) 5-15R 

    

Environmental  

Operating Temperature  

UL Listed  - 0º C to 35º C (32º F to 9 5º F) 

Non-UL Listed  - 0º C to 50º C (32º F to 122 º F) 

With Hawker High Temperature batteries  - 0º C to  60º C (32º F to 140 º F) 

Humidity 

10% to 95% Non  – Condensing  

Altitude 

7,000 Feet   

Cooling 

Low Velocity Forced Air Fans  

Audible Noise @  1.5 Meters 

54dBA 

    

Controls and Indicators  

Sequenced LED s 

Load Level  

Single LED  

Utility Present, Low Battery, Summary Alarm, Inverter On  

Audible Alarms  

Utility Interrupt, Inverter Failure, Overload, Low Battery  

Communications  

Dry Contact Closures on Utility L oss & Low Battery via 9 Pin “D” Connector  

     

Mechanical  

Dimensions H x W x D i nches (mm)

 

13.5 x 6.25 x 19.4         (342.9 x 158.8 x 492.8)  

Weight                                  lb .  (kg) 

41   (18.6) 

64   (29) 

(ED-2500-1 65 lbs, 29.4 kg)  

Agency Listing 

UL Listed  1778,   FCC Class A  

Содержание ED-1000-1

Страница 1: ...1 FALCON ELECTRIC INC 5106 Azusa Canyon Road Irwindale CA 91706 Tel 626 962 7770 Fax 626 962 7720 The information contained herein is the property of FALCON ELECTRIC This information is proprietary co...

Страница 2: ...n 6 Front Panel LED Functions 6 Rear Panel Diagram Description 7 Chapter 4 Communications Interface 8 Signals Interfacing 8 Chapter 5 Operation 9 Step By Step Operating Procedure 9 Operational Mode Ta...

Страница 3: ...detergent on the UPS Never attempt to service batteries High voltage exists within the unit which could cause electrical shock Servicing of batteries should be performed or supervised by personnel kno...

Страница 4: ...Also your understanding of the product is essential in providing you years of service for your back up power requirements Refer to the cross reference table below to understand which unit with its pow...

Страница 5: ...is considered a non linear load which can be very abusive to most power protection equipment and could decrease its life expectancy The FALCON ED unit is specially devised to accept these loads and p...

Страница 6: ...Maintenance Free Back Up Time Full Load 1 2 Load 8 Minutes 20 Minutes 5 Minutes 14 Minutes 3 Minutes 9 minutes Battery times are approximate Electrical Connections Input 6 Cord with 5 15P 8 Cord with...

Страница 7: ...te label located on the rear panel of the unit 3 This UPS has been shipped with the battery connection fuse removed to meet new transportation regulations THE BATTERY CONNECTION FUSE MUST BE INSTALLED...

Страница 8: ...d LED turns on and a continuous audible alarm is sounded when the UPS is overloaded or has failed Should this occur check the load level and correct any overload condition if present During this condi...

Страница 9: ...access to the UPS contact closure status interface Please reference page 9 of this manual for details 9 UPS Model Identification Label 10 Inlet for Input Line Cord on ED1000 1 only Line cord permenen...

Страница 10: ...CHAPTER CHAPTER 4 4 DB 9 COMMUNICATIONS INTERFACE 8...

Страница 11: ...actual battery back up time and the low battery condition varies depending on the amount of load charge on the battery and condition of the battery See SPECIFICATIONS on page 4 for approximate backu...

Страница 12: ...ower switch ON at all times and switch your devices OFF individually This will insure that your batteries are always at a maximum charged state The power switch acts as a system ON OFF switch When thi...

Страница 13: ...years Never attempt to service batteries High voltage exists within the unit which could cause electrical shock Servicing of batteries should be performed or supervised by personnel knowledgeable of...

Страница 14: ...urer s instructions may cause interference to radio and television reception All models covered in this manual have been tested and found to comply with the limits for a Class A computing device in ac...

Страница 15: ...r unit s historical records The RMA number issued must appear on the outside of the shipping carton The original shipping container must be used when returning any ED Series product Falcon Electric wi...

Страница 16: ...the nature of the trouble experienced and the disposition of the equipment after repair The equipment will be returned freight collect by FALCON to the location specified via the best and least expen...

Отзывы: