MODEL SELECTION GUIDE
4
Model Number
ED-1000-1
ED-1500-1
ED-2000-1
ED-2400-1
(ED-2500-1)
Nominal VA
1000
1500
2000
2400
(2500)
Electrical Input
AC Voltage, +10% -20%
120Vac
Current-Amps
10.4
15.6
20.8
22 (24)
Frequency Range
47-450 Hz
Electrical Output
AC Voltage,
±
3%
120Vac
Watts @ 50 or 60 Hz
700
1050
1400
1680 (1750)
Watts @ 400 Hz
595
892
1190
1487 (1550)
Current-Amps @ 50/60 Hz
8.3
12.5
16.7
20 (20.8)
Current-Amps @ 400 Hz
7.1
10.6
14.2
17 (18.0)
50/60 Hz Non – Linear
Repetitive Peak (Amps)
20
30
40
48
400 Hz Non – Linear
Repetitive Peak (Amps)
14.2
21.3
28.3
33
Total Harmonic Distortion
< 3% @ 100% Linear Load, < 5% @ 100% Non – Linear Load
Overload
200% for 0.5 Seconds, 120% for 30 Seconds
Dynamic Response
±
5% RMS for 100% Step Load Chang e, 1ms Recovery Time
Output Protection
Short Circuit and Overload
Battery
Type
Sealed Lead Acid Maintenance -Free
Back Up Time @ Full Load
@ 1/2 Load
8 Minutes
20 Minutes
5 Minutes
14 Minutes
3 Minutes
9 minutes
Battery times are approximate.
Electrical Connections
Input
6’ Cord with 5 -15P
8’ Cord with 5 -20P
8’ Cord with
L5-30P
Output
(4) 5-15R
Environmental
Operating Temperature
UL Listed - 0º C to 35º C (32º F to 9 5º F)
Non-UL Listed - 0º C to 50º C (32º F to 122 º F)
With Hawker High Temperature batteries - 0º C to 60º C (32º F to 140 º F)
Humidity
10% to 95% Non – Condensing
Altitude
7,000 Feet
Cooling
Low Velocity Forced Air Fans
Audible Noise @ 1.5 Meters
54dBA
Controls and Indicators
Sequenced LED s
Load Level
Single LED
Utility Present, Low Battery, Summary Alarm, Inverter On
Audible Alarms
Utility Interrupt, Inverter Failure, Overload, Low Battery
Communications
Dry Contact Closures on Utility L oss & Low Battery via 9 Pin “D” Connector
Mechanical
Dimensions H x W x D i nches (mm)
13.5 x 6.25 x 19.4 (342.9 x 158.8 x 492.8)
Weight lb . (kg)
41 (18.6)
64 (29)
(ED-2500-1 65 lbs, 29.4 kg)
Agency Listing
UL Listed 1778, FCC Class A