background image

 

 

 

 

 

 

 

 

UPS2000-G-(1 kVA-3 kVA)

 

 

User Manual

 

 

 

Issue 

08

 

Date 

2017-08-04

 

HUAWEI TECHNOLOGIES CO., LTD. 

Summary of Contents for UPS2000-G-1KRTL

Page 1: ...UPS2000 G 1 kVA 3 kVA User Manual Issue 08 Date 2017 08 04 HUAWEI TECHNOLOGIES CO LTD ...

Page 2: ... Huawei and the customer All or part of the products services and features described in this document may not be within the purchase scope or the usage scope Unless otherwise specified in the contract all statements information and recommendations in this document are provided AS IS without warranties guarantees or representations of any kind either express or implied The information in this docum...

Page 3: ...nly to commercial and industrial use rather than medical facilities and life support equipment The UPS is of C2 class A If a C2 class A UPS is used in residential areas additional measures must be taken to prevent radio frequency interferences Intended Audience This document is intended for Sales engineers Technical support engineers System engineers Hardware installation engineers Commissioning e...

Page 4: ...t information best practices and tips NOTE is used to address information not related to personal injury equipment damage and environment deterioration Change History Changes between document issues are cumulative The latest document issue contains all the changes made in previous issues Issue 08 2017 08 04 Updated the section Alarm Handling Issue 07 2017 01 19 Added the DHCP feature Added an exte...

Page 5: ...hnologies Co Ltd iv Issue 04 2015 11 23 Updated settings of the voltage range in ECO mode Added button functions for exiting parameter setting screens and alarm screen Issue 03 2015 10 20 Updated the button description Issue 02 2015 08 29 Updated the routine maintenance Issue 01 2015 06 25 This issue is the first official release ...

Page 6: ...rview 4 2 1 Model Description 4 2 2 Working Principle 5 2 3 Product Structure 6 2 4 Optional Components 9 3 Installing the UPS 12 3 1 Installation Preparations 12 3 2 Tools 13 3 3 Installing UPS 14 3 4 Installing Cables 16 3 5 Installation Verification 21 4 Setting Control Panel 23 4 1 LCD Panel 23 4 2 Buzzer Alarm Tones 25 4 3 Character Display 26 4 4 Buttons 27 4 5 Setting Parameters 28 4 6 Oper...

Page 7: ... 5 9 Entering Alarm Cause ID Screen 52 6 Maintenance and Storage 53 6 1 Maintenance 53 6 2 Storage 53 7 Routine Maintenance 54 7 1 UPS Maintenance 54 7 2 Battery Maintenance 55 8 Troubleshooting 60 9 Specifications 62 9 1 Physical Specifications 62 9 2 Environmental Specifications 62 9 3 Mains Input Electrical Specifications 63 9 4 Bypass Input Electrical Specifications 64 9 5 Output Electrical Sp...

Page 8: ... nearby Never install the UPS in a place exposed to sunlight or with a heater nearby Never block or shield the air vents on the UPS shell 1 3 Operating Environment A UPS can be used to serve resistive capacitive loads resistive loads and micro inductive loads It does not apply to pure capacitive loads pure inductive loads and half wave rectification loads It does not apply to energy feedback loads...

Page 9: ...ll overload the UPS such as a laser printer to the output socket of the UPS When routing cables keep them away from the place where they are easily to be stepped on or make someone stumble Never connect household appliances such as a hair drier to the output socket of the UPS The power to the UPS must come from a near grounded cushion socket Use only power cables that comply with Verband Deutscher...

Page 10: ...UPS2000 G 1 kVA 3 kVA User Manual 1 Precautions Issue 08 2017 08 04 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 3 1 6 Servicing Maintenance and Troubleshooting ...

Page 11: ... kVA in the description of their common features and parameters UPS2000 G 1KRTL 1 K long backup time model rack mounted IEC UPS2000 G 2KRTS 2 K standard model rack mounted IEC The two models are represented by 2 kVA in the description of their common features and parameters UPS2000 G 2KRTL 2 K long backup time model rack mounted IEC UPS2000 G 3KRTS 3 K standard model rack mounted IEC The two model...

Page 12: ...duct category UPS 2 Product family 2000 P capacity 20 kVA 3 Product series A tower series G rack series 4 Output capacity Unit VA 1K 1 kVA 2K 2 kVA 3K 3 kVA 5 UPS type RT rack or tower mounted UPS TT tower mounted UPS 6 Built in battery pack optional S standard backup time model which provides only a standard battery pack L long backup time model You need to use an external large capacity battery ...

Page 13: ...ure 2 2 UPS conceptual diagram 2 3 Product Structure Figure 2 3 to Figure 2 8 show the rear view of the 1 kVA 2 kVA and 3 kVA UPSs Figure 2 3 Rear view of UPS2000 G 1KRTS 1 Mains input socket C14 2 Input circuit breaker 3 Universal serial bus USB port security protection mechanism supported 4 RS232 port 5 Optional card slot 6 Output socket C13 ...

Page 14: ...socket C14 2 Input circuit breaker 3 USB port security protection mechanism supported 4 RS232 port 5 Optional card slot 6 Output socket C13 7 External battery connector only for long backup time models Figure 2 5 Rear view of UPS2000 G 2KRTS 1 Mains input socket C14 2 Input circuit breaker 3 USB port security protection mechanism supported 4 RS232 port 5 Optional card slot 6 Output socket C13 ...

Page 15: ... 2 Input circuit breaker 3 USB port security protection mechanism supported 4 RS232 port 5 Optional card slot 6 Output socket C13 7 External battery connector only for long backup time models Figure 2 7 Rear view of UPS2000 G 3KRTS 1 Mains input socket C20 2 Input circuit breaker 3 USB port security protection mechanism supported 4 RS232 port 5 Optional card slot 6 Output socket C13 7 Output socke...

Page 16: ...humidity sensor ENR1DETA MODULE Measures the UPS ambient temperature 0 50 C and humidity 0 100 RH Used together with an SNMP card Battery pack ESS 36V12 9 2AHBPV BB01 Contains two battery strings Each string contains three 9 Ah 12 V DC batteries The output voltage of the battery pack is 36 V DC Applicable to the 1 kVA UPS with long backup time ESS 72V12 9AHBPVBB 01 Contains one battery string with...

Page 17: ...rd RMS RELAY02B Provides dry contact signals and monitors the UPS remotely Used together with an SNMP card External charger CHG 36V15A 01B Connects the battery pack or rack to the mains and charges the batteries or battery pack Applicable to the 1 kVA UPS with long backup time CHG 72V12A 01B Applicable to the 2 kVA UPS with long backup time CHG 96V10A 01B Applicable to the 3 kVA UPS with long back...

Page 18: ...08 04 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 11 Optional Component Model Function Remarks capability and input filtering capability Guide rail component None Secures the UPS or battery pack Configured in rack mounted scenarios ...

Page 19: ...y from water sources heat sources and inflammable materials The UPS is free from direct sunlight dust volatile gases corrosive materials and salty air Do not install the UPS in environments with conductive metal scraps in the air The optimal operating temperatures for batteries are 20 30 C Operating temperatures higher than 30 C shorten the battery lifespan and operating temperatures lower than 20...

Page 20: ... 3 1 Reserved clearances 3 2 Tools Get tools insulated to prevent electric shocks Table 3 1 lists the tools that may be used during installation Table 3 1 Tools Appearance Specifications and Name Clamp meter Multimeter Labels Phillips screwdriver PH2 x 150 mm or PH3 x 250 mm Flat head screwdriver 2 mm x 80 mm Torque screwdriver Crimping tool Diagonal pliers ...

Page 21: ...UPS can be installed on a desk or in a 19 inch rack 1 kVA UPS 2 kVA UPS and 3 kVA UPS need 2 U space separately The installation method for 1 kVA UPS 2 kVA UPS and 3 kVA UPS are the same The figures in this chapter based on the 3 kVA UPS Install the UPS in appropriate mode by performing the following steps Rack mounting a UPS Step 1 Take out mounting brackets from the fitting bag and install mount...

Page 22: ...S front panel Step 2 Rotate the control panel 90 degrees clockwise Step 3 Rotate the logo 90 degrees clockwise on the front panel Reinstall the front panel Step 4 Assemble support bases The minimum distance between two support bases should be 150 mm Step 5 Place UPS on the support bases in sequence Step 6 Adjust the UPS and the support bases to be horizontally Figure 3 3 Tower mounting the UPS Fig...

Page 23: ... Installing Cables Step 1 Connect the UPS output power cable For socket type output connect loads to the UPS output sockets When a power failure occurs the UPS automatically supplies power to the loads Figure 3 5 Connecting cables to the 1KRTS UPS output Figure 3 6 Connecting cables to the 1KRTL UPS output Figure 3 7 Connecting cables to the 2KRTS UPS output ...

Page 24: ...10 Connecting cables to the 3KRTL UPS output Step 2 Connecting battery power cables to a long backup time model The step is optional for long backup time model the standard model with built in batteries cannot support external batteries For details about battery pack installation see the UPS2000 G 1 kVA 3 kVA Battery Pack Quick Installation Guide The installation method for 1 kVA UPS 2 kVA UPS and...

Page 25: ...connected exceeds 40 Ah it is recommended that an external charger be purchased to increase the charge current If an external charger is not purchased the charge time will be long The battery pack ESS 36V12 9 2AHBPVBB01 for 1 kVA UPS with long backup time contain two group battery strings The battery pack ESS 72V12 9AHBPVBB01 for 2 kVA UPS with long backup time only contain one group battery strin...

Page 26: ...ep 5 Connect the UPS to a PC Connect the UPS to the RS232 or USB port on a PC Then you can monitor the UPS status using the PC as long as you have installed the monitoring software The installation method for 1 kVA UPS 2 kVA UPS and 3 kVA UPS are the same The figures below based on the 3 kVA UPS Figure 3 14 Connecting communications cables to the 3KRTS UPS Figure 3 15 Connecting communications cab...

Page 27: ... For details about how to install and use the iManager NetEco 1000U see the iManager NetEco 1000U User Manual The software and the user manual are available at http support huawei com enterprise or http support huawei com Step 6 Take out input power cables from the fitting bag and connect mains input power cables to the UPS Figure 3 16 Connecting cables to the 1KRTS UPS input Figure 3 17 Connectin...

Page 28: ...3KRTS UPS input Figure 3 21 Connecting cables to the 3KRTL UPS input End 3 5 Installation Verification Table 3 2 gives the installation verification checklist Table 3 2 Installation verification checklist No Item Acceptance Criterion 1 Cable routing Cable routing meets engineering requirements 2 Cable connections Power cables and battery cables are tightened to specified torques using a torque wre...

Page 29: ... 4 Cable labels Labels are neatly attached to both ends of each cable and the information on the labels is concise and understandable 5 Ground cable connection The ground cable is securely connected to the equipment room ground bar Measure the resistance between the UPS ground cable and the equipment room ground bar which must be less than 1 ohm 6 Distances between cable ties Distances between cab...

Page 30: ... Panel 4 1 LCD Panel The control panel is on the UPS front panel The control panel allows you to control and operate the UPS view the running status set parameters and view alarms Figure 4 1 LCD panel Table 4 1 Icon description Icon Function Backup time information Alternately displays the remaining power backup time alarm ID and CF only displays in frequency conversion ...

Page 31: ...e UPS Output information Displays the output voltage frequency or battery voltage Vac output voltage Hz output frequency output load ratio A output current Load information Displays the current load percentage by level 0 25 Indicator 1 is steady on 25 50 Indicators 1 and 2 are steady on 50 75 Indicators 1 2 and 3 are steady on 75 100 Indicators 1 2 3 and 4 are steady on 100 Indicators 1 2 3 and 4 ...

Page 32: ...Indicators 1 2 and 3 are steady on 75 100 Indicators 1 2 3 and 4 are steady on 100 Indicators 1 2 3 and 4 are blink Input voltage information Displays the input voltage frequency battery voltage or input current percentage Vac input voltage Vdc battery voltage Hz input frequency A battery capacity percentage 4 2 Buzzer Alarm Tones Table 4 2 describes the buzzer alarm tones Table 4 2 Buzzer alarm t...

Page 33: ...n ENA Enable DIS Disable ESC Escape CF Frequency conversion TP Temperature CH Charging FU Bypass frequency unstable EE EEPROM error VOT Voltage FRE Frequency BVU Bypass overvoltage BVL Bypass undervoltage CAP Capacity DT Discharge time ECO ECO mode VU High voltage VL Low voltage AUT Constant frequency mode BUZ Buzzer off AST Automatic startup DHP Dynamic Host Configuration Protocol DHCP IP ADS IP ...

Page 34: ...E Starting the UPS Hold down ON MUTE for over 5 seconds to connect the UPS power supply Enabling or disabling the buzzer Hold down ON MUTE for 2 5 seconds to enable or disable the buzzer However when the UPS sends a new alarm the mute function is unavailable you need to disable the buzzer again Selecting the previous option During the setting of UPS parameters press ON MUTE for more than 3 seconds...

Page 35: ...mode hold down SELECT for 5 seconds to start setting only for 11 UPS buzzer parameters Selecting the next option During the setting of UPS parameters press SELECT for more than 3 seconds Release the button when you hear a beep sound to select the next option ON MUTE SELECT Transferring to bypass mode When the input power supply is normal and the UPS is started in normal mode hold down ON MUTE and ...

Page 36: ...igure 4 3 Setting parameters on the LCD When the UPS is in standby mode or bypass mode hold down SELECT for 5 seconds to start setting UPS parameters When the UPS is in normal mode or battery mode hold down SELECT for 5 seconds to enable or disable the buzzer off BUZ function set the DHCP DHP function or view the IP address IP subnet mask SUB and gateway GAT During the setting of UPS parameters pr...

Page 37: ...lay Setting Enable or disable the frequency conversion mode 50 The output frequency is always 50 Hz and the frequency conversion mode is enabled 60 The output frequency is always 60 Hz and the frequency conversion mode is enabled AUT The frequency conversion mode is disabled default value The CF frequency conversion mode takes priority over the ECO mode If the CF frequency conversion mode is enabl...

Page 38: ...he lowest input voltage in bypass mode Display Setting Press or to adjust and set the lowest input voltage in bypass mode 170 220 The value range is 170 V AC to 220 V AC and the default value is 170 V AC The lowest input voltage in bypass mode should be lower than the lowest input voltage in ECO mode Set the battery capacity Display Setting Press or to adjust and set the UPS battery capacity 18 99...

Page 39: ... or disable the ECO function ENA Enables the ECO mode DIS Disables the ECO mode default value Set the highest allowable voltage in ECO mode Display Setting Press or to adjust and set the highest input voltage in ECO mode 13 24 Set the parameter based on the preset output voltage The value range is 13 V AC to 24 V AC The default value is 22 V AC Set the lowest allowable voltage in ECO mode Display ...

Page 40: ...e the automatic startup function ENA Enables the automatic startup function DIS Disables the automatic startup function default value The DHCP function setting IP address display subnet mask display and gateway display are available only when an SNMP card is configured If no SNMP card is connected default values are displayed for the IP address subnet mask and gateway If an SNMP card is connected ...

Page 41: ...OFF ENTER to exit The default value is 192 168 0 10 Subnet mask display Display Remarks Subnet mask can only be displayed but not configurable Press or to switch between different screens On the ESC screen press OFF ENTER to exit The default value is 255 255 255 0 Gateway display Display Remarks Gateway can only be displayed but not configurable Press or to switch between different screens On the ...

Page 42: ... function for reporting the no battery alarm default value Exit setting Display Remarks Exit from the parameter settings screen 4 6 Operating Modes Table 4 5 Operating mode description Operating Mode Description Display Normal mode When the input voltage is in the acceptable range the UPS works in normal mode supplies stable sine wave AC output current while charging batteries ECO mode When the in...

Page 43: ...and is overloaded it will enter the bypass mode if the input voltage is in an acceptable range If the UPS is set to be enables the bypass mode the UPS automatically transfers to bypass mode after connecting to the mains When the UPS works in bypass mode the buzzer beeps once every 10 seconds Standby mode When the UPS connects to the mains but is not started in normal mode or not enables the bypass...

Page 44: ...eque ncy abnor mal Minor This alarm is automatically cleared The bypass frequency is outside the bypass frequency range The UPS remains in the current state If the UPS works in bypass mode it transfers to standby mode and has no output Possible cause The bypass input frequency is abnormal Measure Check whether the bypass input frequency exceeds the configured range If yes change the range or wait ...

Page 45: ...n nected Minor This alarm is automatically cleared Batteries are not connected connected improperly or damaged The power supply from the UPS is not affected Possible cause No batteries are connected Measure Connect batteries Possible cause The batteries are in poor contact Measure Check the battery cable connection If battery cables are loose connect them securely 25 1 Batter y overvo ltage Critic...

Page 46: ...voltage of each battery exceeds 14 7 V The UPS automaticall y transfers to battery mode When the battery undervoltage alarm is generated the UPS automaticall y transfers to normal mode and starts the charger for charging 26 1 Batter y underv oltage Critical This alarm must be manually cleared The voltage of each battery is lower than 5 V when the UPS is started This alarm is generated because ther...

Page 47: ...kup time model the voltage of each battery is lower than 10 9 V The power supply from the UPS is not affected 29 1 Batter y requiri ng mainte nance Minor This alarm is automatically cleared The battery voltage is lower than the battery replacement voltage 11 V when batteries are in self check mode The power supply from the UPS is not affected Possible cause The actual number of batteries does not ...

Page 48: ... UPS works 42 15 Interna l fault Critical This alarm must be manually cleared The bus voltage is lower than 320 V This alarm is generated during the startup of the UPS If this alarm is generated the UPS fails to start Possible cause The soft start resistor is damaged Measure Contact the dealer or Huawei technical support for repair 42 17 Interna l fault Critical This alarm must be manually cleared...

Page 49: ...nical support Possible cause An overload occurred when the input voltage was low Measure Rectify the fault and restart the UPS 42 24 Interna l fault Minor This alarm is automatically cleared An error occurs in the EEPROM All UPS parameters are restored to the factory settings If this alarm is generated the customer needs to replace the UPS Possible cause The EEPROM is faulty Measure Contact the de...

Page 50: ... lower than 100 V If this alarm is generated during the running of the UPS the UPS transfers to no output After 10 minutes the UPS automaticall y starts the inverter If this alarm persists the UPS then transfers to no output again After the UPS transfers to no output three times the alarm needs to be manually cleared Possible cause The output load types are not supported or the load exceeds the sp...

Page 51: ...Interna l fault Critical This alarm must be manually cleared The ambient temperature exceeds 50º C The UPS transfers to bypass mode When the temperature decreases the UPS automaticall y starts and clears this alarm If this alarm is generated three times within 3 hours the UPS does not start or clear the fault Possible cause The ambient temperature exceeds 50º C Measure Lower the ambient temperatur...

Page 52: ...automatically cleared The inverter output load is more than 105 of the rated load The power supply from the UPS is not affected Possible cause The load exceeds the rated loading capacity of the inverter Measure Lower the load or replace the UPS with a UPS with a larger capacity 66 2 Output overlo ad Minor This alarm is automatically cleared The bypass output load is more than 110 of the rated load...

Page 53: ...inutes after the UPS transfers from normal mode to bypass mode In normal mode when the bypass input is abnormal this alarm is generated when the UPS transfers to no output mode transfers from normal mode to bypass mode three times within 20 minutes the UPS is locked in bypass mode For normal mode the UPS transfers to no output mode 66 4 Output overlo ad Critical This alarm must be manually cleared...

Page 54: ...ar m Cause ID Alar m Name Alarm Severity Alarm Clear Mode Trigger Condition Impact on the System Repair Proposal capacity 4 8 Alarm Indication Table 4 7 Alarm indication Alarm Display Blinking Buzzer Insufficient battery capacity Beeps once every second Overload Beeps twice every second Battery disconnection Beeps once every second Overcharge Beeps once every second ...

Page 55: ...s the requirements Cables are properly connected between the UPS and batteries Power cables and signal cables are correctly identified Cables are neatly routed and securely bound Devices are installed and cables are routed in ways that facilitate modification capacity expansion and maintenance The UPS is properly grounded The voltage between the neutral wire and the ground cable is less than 5 V A...

Page 56: ... batteries If the 1 kVA UPS with long backup time needs to connect to external battery strings each battery string must consist of three 12 V batteries connected in series If the 2 kVA UPS with long backup time needs to connect to external battery strings each battery string must consist of six 12 V batteries connected in series If the 3 kVA UPS with long backup time needs to connect to external b...

Page 57: ...5 2 Setting the output voltage Step 3 Set the system output frequency based on the rated frequency The values include 50 Hz 60 Hz and AUT default Figure 5 3 Setting the system output frequency Step 4 This step is required only for the UPS with long backup time Set the battery capacity to the total capacity of all batteries actually connected The default value is 18 Ah for the UPS with long backup ...

Page 58: ...e the UPS to enter the standby mode or bypass mode if set or enabled before Battery Mode Hold down OFF ENTER for over 2 seconds to turn off the UPS in battery mode 5 4 Transferring to Bypass Mode When the input power supply is normal and the UPS is started in normal mode hold down ON MUTE and SELECT both for 5 seconds to enable the UPS enter the bypass mode If the input voltage exceeds the accepta...

Page 59: ...r disable the buzzer off function During the setting of UPS parameters press ON MUTE for more than 3 seconds Release the button when you hear a beep sound to select the previous option During the setting of UPS parameters press SELECT for more than 3 seconds Release the button when you hear a beep sound to select the next option Press OFF ENTER for more than 3 seconds to confirm the setting Button...

Page 60: ...e replaced contact the dealer Hand over used batteries to recyclers or pack them with the package for new batteries and send them to the dealer 6 2 Storage Before storing the UPS charge it for 5 hours The correct way of storing the UPS is standing the UPS without unpacking in a dry place During the storage period maintain the UPS by charging its batteries as follows Table 6 1 UPS charging during s...

Page 61: ...nel are allowed to perform maintenance Maintain UPSs regularly based on the following requirements Otherwise the UPSs may fail to operate properly and the lifespan may be shortened 1 Routine maintenance items for UPSs Check Item Expected Result Troubleshooting Maintenance Interval Operating environment Ambient temperature 0 40 C Humidity 0 95 RH non condensing If the humidity and temperature are a...

Page 62: ...yers of cables are intact and terminals are free from noticeable sparks Replace the cables Secure the output terminals Quarterly Battery self check No battery alarm is generated If an alarm is present rectify the fault Yearly 7 2 Battery Maintenance Before installing batteries read through the battery user manuals and pay attention to safety precautions and connection methods provided by battery m...

Page 63: ...at least 4 hours In high temperature areas discharge and charge batteries once every two months Each charge should last at least 4 hours Do not overdischarge batteries After discharging batteries fully charge them within 24 hours Ensure that the battery discharge duration is 999 minutes at most and 0 minute by default If you set the value to 0 minute the discharge time is not limited Routine maint...

Page 64: ... Float voltage 13 68 V x Number of batteries tolerance 1 1 If the voltage drop between the battery string output terminals and the battery input terminals at the UPS side is greater than 1 of the battery string voltage check whether the cable between the battery string and the UPS is excessively long or the cable diameter is excessively small 2 Check whether the equalized charging voltage and floa...

Page 65: ... support Quarterly Cables between batteries No cable deteriorates and the insulation layer does not crack Replace the faulty cable Quarterly Battery voltage Equalized charging voltage 14 16 V 0 1 V Float charging voltage 13 68 V 0 1 V 1 Check whether the equalized charging voltage and float charging voltage of a battery are normal 2 If the charging voltage of a battery exceeds the specifications r...

Page 66: ...ion is identified 2 If the fault persists contact Huawei technical support Yearly Battery connection reliability 1 Each battery terminal is connected reliably When battery strings are powered off check the reliability of each terminal in the order from positive terminals to negative terminals 2 The tightening torque of each battery screw meets the requirements of the battery manufacturer A torque ...

Page 67: ...nce every second The external or internal batteries are incorrectly connected Check that all batteries are connected correctly and blink on the LCD and the buzzer beeps twice every second The UPS is overloaded Remove surplus load from the UPS output end The UPS is overloaded and supplying power to devices in bypass mode Remove surplus load from the UPS output end The UPS is overloaded server times...

Page 68: ... 8 Troubleshooting Issue 08 2017 08 04 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 61 Symptom Possible Cause Measures Batteries are faulty Contact the dealer or Huawei technical support to replace batteries ...

Page 69: ...mm x 310mm 10 7 kg UPS2000 G 1KRTL 88mm x 438mm x 310mm 5 9 kg UPS2000 G 2KRTS 88mm x 438mm x 410mm 18 5 kg UPS2000 G 2KRTL 88mm x 438mm x 410mm 8 6 kg UPS2000 G 3KRTS 88mm x 438mm x 630mm 27 9 kg UPS2000 G 3KRTL 88mm x 438mm x 410mm 9 2 kg 9 2 Environmental Specifications Table 9 2 Environment specifications Item 1 kVA 2 kVA 3 kVA Operating temperature 0 C 40 C Humidity 0 95 RH non condensing Alt...

Page 70: ...tio of actual load to rated load 100 80 80 70 70 60 60 0 When the ambient temperature is 35 40 C 175 155 135 125 V AC tolerance 5 Ratio of actual load to rated load 100 80 80 70 70 60 60 0 Lo wes t reco very volt age When the ambient temperature is 0 35 C 175 155 135 125 V AC tolerance 5 Ratio of actual load to rated load 100 80 80 70 70 60 60 0 When the ambient temperature is 35 40 C 190 170 150 ...

Page 71: ...ations Table 9 4 Bypass Input Electrical Specifications Item 1 kVA 2 kVA 3 kVA Bypass voltage tolerance 170V 264 V AC Bypass frequency tolerance 47 53 Hz or 57 63 Hz Bypass overload capability 110 120 30 minutes 120 130 10 minutes 130 150 1 minute Input mode One mains input The upper and lower thresholds of bypass voltage toleranceare are configurable on the LCD 9 5 Output Electrical Specification...

Page 72: ...es 110 130 The UPS automatically shuts down in battery mode or transfers to bypass mode in line mode after 1 minutes 130 150 The UPS automatically shuts down in battery mode or transfers to bypass mode in line mode after 3 seconds 150 The UPS automatically shuts down in battery mode or transfers to bypass mode in line mode after 0 5 seconds max When the ambient temperature is 35 40 C 105 110 The U...

Page 73: ... 80 9 6 Battery Specifications Table 9 6 Battery specifications Item 1 kVA 2 kVA 3 kVA Rated battery voltag e Standard model 24 V DC 48 V DC 72 V DC Long backup time model 36 V DC 72 V DC 96 V DC Numb er of batteri es Standard model 2 4 6 Long backup time model 3 6 8 Batter y leakag e current Standard model 17 µ A 25 7 µA 27 4 µA Long backup time model 25 4 µA 28 5 µA 32 8 µA Battery type 12 V DC ...

Page 74: ...d chargi ng voltag e Standard model 28 3 V DC 1 56 6 V DC 1 84 9 V DC 1 Long backup time model 42 5 V DC 1 84 9 V DC 1 113 3 V DC 1 Table 9 7 Power backup specifications of the battery pack Battery Pack Load UPS2000 G 1KR TL min UPS2000 G 2KR TL min UPS2000 G 3KR TL min 1 Battery group 100 15 0 6 5 7 0 75 21 0 10 0 11 0 50 39 0 18 0 17 0 25 77 0 37 0 45 0 2 Battery groups 100 36 0 17 0 16 0 75 47 ...

Page 75: ...backup time only contain one group battery strings The 1 kVA UPS with long backup time is allowed a maximum of two battery packs ESS 36V12 9 2AHBPVBB01 in parallel The 2 kVA UPS with long backup time is allowed a maximum of four battery packs ESS 72V12 9AHBPVBB01 in parallel The 3 kVA UPS with long backup time is allowed a maximum of four battery packs ESS 96V12 9AHBPVBB02 in parallel 9 7 ECO Feat...

Page 76: ...2 Radiated emission RE IEC 62040 2 Category C2 Low frequency signal IEC61000 2 2 Anti electromagnetic interference IEC 61000 4 2 Conducted emission IEC 61000 4 6 Radiated susceptibility RS IEC 61000 4 3 Electrical fast transient burst EFT B IEC 61000 4 4 Surge IEC 61000 4 5 Power magnetic susceptibility PMS IEC 61000 4 8 Harmonic current IEC61000 3 12 Flashing IEC61000 3 11 input current 16 A Impa...

Page 77: ...A Acronyms and Abbreviations C CE ConformitéEuropé enne E ECO economy control operation EEPROM electrically erasable programmable read only memory H HTTP HTTP Hypertext Transfer Protocol L LCD liquid crystal display P PFC power factor correction R RS232 Recommend Standard 232 S SNMP Simple Network Management Protocol T THDv total harmonic distortion voltage ...

Page 78: ...UPS2000 G 1 kVA 3 kVA User Manual AAcronyms and Abbreviations Issue 08 2017 08 04 Huawei Proprietary and Confidential Copyright Huawei Technologies Co Ltd 71 U UPS uninterruptible power system ...