Changed function after a power cut
Modes 1–5 and 8 keep the light off after power returns. Modes
6–7 and 9–10 set the light to full. This can be changed with IRT
9090 as follows:
1. Press the POWER UP button once.
2. Select a new start function with the ON and OFF buttons.
3. Send the new information with a press of the green button.
NOTE!
Modes 1–5 switch off after a power cut. The system
requires at least a 15 second reset period before the light can
be switched on using the proximity sensor.
Mode
Range of use
Function after
power cut
1
Office room
Switched off
2
Open-plan offices
Switched off
3
School/classroom min.
Switched off
4
Office landscape according to EN 12464
Switched off
5
Office room according to EN 12464
Switched off
6
Corridor
On
7
Toilet
On
8
Meeting room/conference room with light
scenarios
Switched off
9
Office landscape
(requires switching off centrally with 230 V)
On
10
Office landscape according to EN 12464
(requires switching off centrally with 230 V)
On
Change level before switching off
The low level (background) before switching off, available in mo-
des 2, 6 and 9, is preprogrammed to 20 %. In modes 4, 7 and 10,
the level only applies to DALI 2 and is selected to 100 %. The level
can be changed as follows for all these modes.
1. Press the BACKGROUND button once.
2. Select a new light level for 10, 20, 30, 40, 50, 60 or 70%. The
minimum level is selected with the 0 button.
3. Send the new information with a press of the green button.
Mode
Range of use
Low level %
1
Office room
-
2
Open-plan offices
20 %
3
School/classroom min.
-
4
Office landscape according to EN 12464
100 %
5
Office room according to EN 12464
0
6
Corridor
20 %
7
Toilet
100 %
8
Meeting room/conference room with light
scenarios
-
9
Office landscape
(requires switching off centrally with 230 V)
20 %
10
Office landscape according to EN 12464
(requires switching off centrally with 230 V)
100 %