Fagerhult e-Sense Actilume Скачать руководство пользователя страница 2

Dokumentet kan ändras utan föregående meddelande. Subject to change without notice.

1a. The light is switched on when the proximity sensor is trig-
gered if the light level is too low. Daylight adjustment active. 
1b. The light is switched off when the proximity sensor is 
triggered if the light level is sufficient. The light is switched on 
when daylight adjustment is active if the level drops below the 
set value.
2. Proximity.
3. Last proximity detection, 15 minute timer begins counting 
down. If the sensor is triggered within the period, the timer is 
reset. 
4. The light is adjusted downwards and is switched off after 15 
minutes. 

NOTE!

 If the system is affected by bright sunlight for more than 

15 minutes, the adjustment may go from the minimum level 
to completely off. When the effect of sunlight decreases, the 
light is switched on again to the minimum level and adjusts to 
daylight.

Mode 1 (one flash) – Office room

Mode 2 (two flashes) – Open plan office solution

1a. The light is switched on when the proximity sensor is trig-
gered if the light level is too low. Daylight adjustment active. 
1b. The light is switched off when the proximity sensor is 
triggered if the light level is sufficient. The light is switched on 
when daylight adjustment is active if the level drops below the 
set value. 
2. Proximity.
3. Last proximity detection, 15 minute timer begins counting 
down. If the sensor is triggered within the period, the timer is 
reset. 
4. The light is adjusted down to 20 % after 15 minutes.
5. After two hours the light is switched off completely. If the 
sensor is triggered within the period, the timer is reset and the 
light returns to daylight adjustment. 

NOTE!

 If the system is affected by bright sunlight for more than 

15 minutes, the adjustment may go from the minimum level 
to completely off. When the effect of sunlight decreases, the 
light is switched on again to the minimum level and adjusts to 
daylight.

Närvaro
Precense

2

Närvaro
Precense

Содержание e-Sense Actilume

Страница 1: ...ing installation directive EN 12464 These additional modes are easily programmable with a push of the IRT 9090 00 IR transmitter The Actilume system always switches to the maximum light level before daylight adjustment begins Deployment with service button on the sensor Startup Requirement Fixture correctly positioned e g over the work space Power up the fixture The light will switch on after appr...

Страница 2: ...ts to daylight Mode 1 one flash Office room Mode 2 two flashes Open plan office solution 1a The light is switched on when the proximity sensor is trig gered if the light level is too low Daylight adjustment active 1b The light is switched off when the proximity sensor is triggered if the light level is sufficient The light is switched on when daylight adjustment is active if the level drops below ...

Страница 3: ...ex or the light level is wrong relative to the amount of daylight See illustration below Example Classroom A normal classroom has a large window area along one of the long walls The lighting closest to the window is connected to DALI 1 Window and is adjusted from 3 100 The fixtures in the centre and further inside the space are adjusted with an offset of 30 which compensates for the lower level of...

Страница 4: ...measure ment The desired setpoint must be set with no interference from daylight Small sharp reflections from glass objects for example may affect the total value The sensor should be pla ced so that it reads the work surface in a workspace An ideal position would be directly above the centre of the desk but if the sensor is integrated into the end of a fixture it should be directed away from the ...

Страница 5: ...0 0 Switched off Daylight adjustment workspace light only 6 Corridor Corridor Auto on off 15 60 min 20 On 7 Toilet Washbasin Toilet Auto till från 15 15 min toilets only 100 On Daylight adjustment washbasin only 8 Meeting room conference room with light scenarios Channel 1 Channel 2 Manual on Auto off 15 0 Switched off No daylight adjustment 9 Office landscape requires switching off centrally with...

Страница 6: ...th 230 V Programming a preset mode 1 Press button MODE 2 Select a MODE from 1 to 10 3 Send the new information with a press of the green button Aim carefully at the IR receiver the sender has a very narrow beam to prevent accidental transmission to nearby systems The light will flash once to confirm the new setting Setting daylight level With the IRT 8099 IR transmitter Fagerhult order no 86155 it...

Страница 7: ...mall movements 1 Press the TEST button once The light will adjust downwards First check that there are no people under the sensor Walk slowly towards the zone until the light flashes Reset the fun ction by pressing the TEST button again To check the mode that has been programmed e Sense Acti lume can indicate the mode that is selected 1 Press the MODE button once The light is first adjusted downwa...

Страница 8: ... room with light scenarios Switched off 9 Office landscape requires switching off centrally with 230 V On 10 Office landscape according to EN 12464 requires switching off centrally with 230 V On Change level before switching off The low level background before switching off available in mo des 2 6 and 9 is preprogrammed to 20 In modes 4 7 and 10 the level only applies to DALI 2 and is selected to ...

Страница 9: ...o install deploy and use NOTE Important Philips has updated the Actilume system and has added functions for Philips OccuSwitch DALI also This means that the programming tool IRT 8099 00 has been replaced with IRT 9090 00 with effect from 2014 All the original program ming functions are the same but the new functions cannot be programmed into Actilume generation 1 which Fagerhult uses in all its fi...

Отзывы: