background image

9

Before making any connections, study the enclosed electrical diagrams carefully (Pic. 11, Pic. 12, Pic. 13).

IMPORTANT

: The whole electrical system must be earthed (Pic. 13).

Power supply, electric motor and flashing light 

connections are made with electric cables with a section of 1.5 mm

2

 for a maximum

distance of 50 m. For distances of over 50 metres, we recommend using electric cables with a section of 2 mm

2

.

- For 

limit switches, photocells, pushbuttons and accessories

 use cables with a 1 mm

2

 section (Pic. 11 - Drwg. 3499).

- The 

pneumatic safety rib

 attached to the gate is connected via cable, a cable winder is to be provided to take up the slack, or by 

radio

link

, in series with the 

limit switches

 or with the

 receiving photocell

, connection diagram Drwg. 3499.

- The ELPRO 10 PLUS three-phase electronic programmer is installed in its own panel, inside the Fibo 300 protection cover; it is prepared

for all programmed automatic and semiautomatic logic services, line relays and incorporated indication lights (Pic. 11 - Drwg. 3499).

ELECTRICAL CONNECTIONS TO ELPRO 10 PLUS PROGRAMMER

PIC. 13

1 - Magnetothermal differential

mains switch, 0.03A type

2 - Cruastro radio link receiver
3 - Rubber pneumatic rib
4 - Cruastro radio link transmitter
5 - Miri 4 flashing light
6 - Polo 44 receiving photocell
7 - Polo 44 projecting photocell
8 - Prit 19 keyswitch
9 - Birio A8 aerial
10 -Astro 43 external radio receiver
11 -Pulin 3 wall-mounted push

button panel

12 -Internal photocell Receiver

Polo 44 on post

13 -Gate stop required
14 -Radio transmitter Astro 43 Small
15 -Fibo 300
16 -Electric cable containment
17 -Internal photocell Projector

Polo 44 on post

PLUS

10

n

°

2x1,5

n

°

4x1

n

°

4x1,5

400V
50Hz

n

°

4x1

n

°

2x1

n

°

4x1

n

°

2x1

n

°

4x1

n

°

4x1

n

°

4x1

1

2

3

4

5

6

3

4

7

8

9

11

12

13

13

17

10

15

16

14

PIC. 12

Hold on switched (Deadman) control:

Pedestrian Opening:

Trimmer T3

-

+

OPERATING MODES

from 3 to 30s. It can be activated by

any pulse (eg. by remote control)

superior to 2s

3

DIP-SWITCH 3

ON= Automatic Closing

OFF= No Automatic. Semi-automatic
          closing by pulse

Automatic / Semiautomatic:

Automatic Operation:

 any pulse opens the gate, the gate stays

open as long as the Dwell time expires as set by T2 trimmer, then
it closes automatically, no pulsing is required.

Semi-automatic Operation:

 any pulse opens the gate that stays

open. A second pulse to Close is required for the gate to close.

Open and Close operations are achieved "by holding a
switch on" (no relay self-holding in involved) therefore a
phisical attendance is required to keep the gate opening or
closing until either the button or key is released.

Remote Controlled Operations Excluded during

Dwell Time on Automatic Mode:

3

ON= Automatic Closing

OFF= Closing by Pulse

5

ON: Step by step. Stop in between

OFF: Standard Operations

With this setting it is not possible to operate the gate by remote control during the dwell time on automatic
mode. DIP-SWITCH 2=ON, 3=ON and 5=ON

DIP-SWITCH 6

6

ON= Deadman Control. Dip-switch 4=OFF
         and Dip-switch 3=OFF

OFF= Standard Operations

DIP-SWITCH No.3=ON Automatic Closing

Time clock
installation:

3

ON= Automatic Closing

OFF= No Automatic. Semi-automatic
          closing by pulse

4

3

COMMON

COMMON

OPEN

NO

-

+

Pedestrian Trimmer T3

set on to zero

2

ON: No reversing on opening

OFF: Travel reversing on any pulsing

Dwell Time

from 5 to 128s

T2

-

+

COMMON

OPEN

4

3

How it works: Set the clock to the required times. On the pre-set time the gate is automatically opened and
held open. Any further pulsing (even by remote control) is not accepted by the system until the time pre-
set by the clock has expired. On expiring and after the pre-set dwell time the gate is closed automatically.
T3 trimmer on to zero, Dip-Switch 3=ON.

External time clock

Содержание FIBO 300

Страница 1: ...G B INSTALLATION MANUAL...

Страница 2: ...ion for intense opening closing cycles The drive shaft is in direct contact with a mechanical torque control device worm and gear are made of bronze and steel and are supported by bearings in an oil b...

Страница 3: ...THE PLUGS ONCE THE PLUG PROTRUSION HAS BEEN ESTABLISHED TIGHTEN THE NUT TO THE FLOOR IN ORDER TO FIRMLY FIX THE PLUG IN THE HOLE THEN UNSCREW AND REMOVE THE NUT INSERT THE PLUGS IN THE HOLES LEAVING A...

Страница 4: ...te Pic 6 Temporarily clamp the rack to the gate levelling it using a spirit level for the entire length of the gate the rack must mesh the idle Fibo 300 driving gear I smoothly and without friction Th...

Страница 5: ...located on the front beneath the electric power panel E P P tighten in order to increase the torque and loosen in order to reduce the torque Pic 10 PIC 8 PIC 9 RACK SPARE RACK AS A PITCH GAGE IMPORTA...

Страница 6: ...ING ON AUTOMATIC CLOSING ON PREFLASHING ACTIVATED ON RADIO STEP BY STEP STOP IN BETWEEN ON DEAD MAN CONTROL Dip 4 OFF and Dip 3 OFF ON NO LAMP ON DURING DWELL TIME OFF NO FUNCTION EXT TIME PEDESTRIAN...

Страница 7: ...21 A 1 2 4 6 22 A 2 1 2 3 4 5 M 16 17 18 19 20 21 22 23 R S T THREE PHASE ELECTRIC MOTOR 230 V 25 W max FLASHING LAMP SUPPLY VOLTAGE 230 400 V 10 THREE PHASE HIGH VOLTAGE 10 A 380 V FUSES POWER CONTAC...

Страница 8: ...d Bridge terminals 3 and 6 if no key or push button switches are required N W To fit extra accessories such as lights CCTV etc use only solid state relays to prevent damages to the microprocessor DIP...

Страница 9: ...13 13 17 10 15 16 14 PIC 12 Holdonswitched Deadman control Pedestrian Opening Trimmer T3 OPERATING MODES from 3 to 30s It can be activated by any pulse eg by remote control superior to 2s 3 DIP SWITCH...

Страница 10: ...provided Pic 11 and Pic 15 following the Elpro 10 PLUS function logic description Drwg 3499 p 6 E P P ELECTRIC POWER PANEL WITH THE ELPRO 10 PLUS PROGRAMMER INCORPORATED SUPPORT PREPARED FOR ATTACHING...

Страница 11: ...cles a year 8 hours a day 131 000 FIBO 300 GEAR MOTOR Output revolutions 40 7 rpm Drive gear Z 24 Module 4 0 Ratio 1 32 Maximum nominal torque 128 Nm Transfer speed 12 m min Hydraulic oil type AGIP RO...

Страница 12: ...isconnect the mains switch before opening the electrical wire junction box cover The whole automation should be earthed with the yellow green wire We recommend reading the Safety Norms suggestions and...

Отзывы: