ELECTRONIC CONTROL PANEL FOR NUPI 66
WITH PROGRAMMABLE RADIO TECHNOLOGY
Elpro 7 RP
GB
General description:
Elpro 7 RP is an electronic control panel developed for Nupi 66. The main feature of this unit is the capability to learn the required working times
during operation (gate delay in open and close cycles, dwell time). 230 V - 50 Hz single-phase power supplied. The manufacturer is not liable for incorrect use of the
controller; and reserves also the right to change and update it to the latest standards of the art at any time.
11
M1
M2
12 13 14 15 16 17 18 19 20
6
WORKING LOGIC:
Elpro 7 RP is supplied with pre-set working times so that to allow the rst installation: working time (about 20 s), gate delay times (opening = 2 s,
closing = 6 s, dwell on automatic mode = 15 s). Once satis ed that the system is working all right, new working times can be programmed to meet the user's needs or
the installation requirements. Elpro 7 RP functions can be set by dip-switches, both before and after the times have been stored by the unit.
LEARNING THE TIMES:
Elpro 7 RP learning operation is quite easy and can be achieved either by the P button on the PBC or by the remote control after entering setting.
mode, see point 1).
Starting the unit to learn the required times: with the gate in closed position pulse the equipment to one complete cycle, ie. open-stop/dwell-close
Important:
1) In order to avoid setting times which are not suitable with the correct gate functioning, some time limits were pre-set. Beyond these values the automation will start
with the maximum pre-set time: M1 and M2 motor run time (max 55 s), dwell time on automatic mode (maximum 90 s).
2) During the learning operation, no other functions can be activated, the photocells and the stop button are out of service.
3) If the new setting operation is interrupted (for example: mains cut off), the times in the previous setting are memorized.
4) Normally, not on programming mode, the P button has the same function as a remote control button and it is possible to test the system by pulsing it; the Led 7
becomes a simple indicator, the same as the indicator to terminal 8.
IMPORTANT:
- The control panel must be installed in a sheltered, dry place.
- Make sure that the power supply to the electronic programmer is 230 V ±10%.
- Make sure that the power supply to the electric motor is 230 V ±10%.
- For distances of over 50 metres we recommend using electric cables with bigger sections.
- Fit the mains to the control panel with a 0,03 A high performance circuit breaker.
- Use 1,5 mm² section wires for voltage supply, electric motor and ashing lamp. Maximum recommended distance 50 m.
- Use 1 mm² section wires for limit switches, photocells, push-buttons/key-switch and accessories.
- Bridge terminals 1 and 2 if no photocells are required.
- Bridge terminals 3 and 6 if no key- or push-button switches are required.
N.W.: to t extra accessories such as lights, CCTV etc. use only solid state relays to prevent damages to the microprocessor.
DIP-SWITCH
ON
OFF
1
4 5 6 7 8
2 3
2 A fuse
24 V low voltage
PLUG-IN RADIO
CARD SUPPORT
TRANSFORMER
L7
L1
L3
L4
L5
L6
L2
PROGRAMMING
P BUTTON
SINGLE-PHASE
MOTOR
M1
(actuator and
electric lock if
required)
SINGLE-PHASE
MOTOR
M2
ELECTRONIC TORQUE
CONTROL
ELECTRONIC
TORQUE CONTROL
+ more power
- less power
1 2
4 5
3
1 2
4 5
3
1 2 3 4 5 6 7 8 9 10
Torque control setting:
adjust torque from lower level (step 1) up to the
required amount of power step by step to achieve
a correct performance of the system so that the
gates are operated as required and any injuring
hazard is prevented.
Please note, torque is to be adjusted by a
technician.
!
24 V - 3 W Indicator:
Led
on
= the gate is open
Led
off
= the gate is closed
Fast
ash = closing movement
Slow
ash = opening movement
3
8
8
ON: gate leaf for
pedestrian opening
OFF: standard operation
Pedestrian opening (M1 motor by open pulse):
Partial opening for pedestrians is only allowed in closed gate position
by pulsing to open (the gate closes after the dwell time if set to
automatic dip-switch 3 = ON):
- the rst pulse operates 1 gate leaf (M1)
- the second pulse operates the second gate leaf
Led status indication:
L1 = 230 V - 50 Hz power supply. Alight
L2 = photocells, if obstructed light goes off
L3 = open. Alight whenever an open pulse is given
L4 = close. Alight whenever a close pulse is given
L5 = stop. It goes off on pulsing stop
L6 = radio. It goes on by pressing a transmitter button
L7 = gate status and programming led
Dip-switch:
1= ON Photocells, stop during opening
2= ON Radio no reversing during opening
3= ON Automatic closing
4= ON Pre- ashing in service
5= ON Radio step by step
6= ON No delay on opening
7= ON No additional pushing on the gate leaf after closing
8= ON Pedestrian opening by open button
DIP-SWITCH
ON
OFF
1
4 5 6 7 8
2 3