FAAST 8251BPI and 8100
INSTALLATION AND MAINTENANCE INSTRUCTIONS
5
FAAST 8100 to FACP Wiring Diagram
Figure 4b: 8100 to FACP Wiring Diagram
Figure 3: Power and Alarm Connector Block
FAAST 8100 System Powering
The following procedure describes how to initially
power up the FAAST system.
1.
Unplug the unit’s power connector to the unit
before turning ON the power.
2. Turn on the power.
3. Check the voltage at the connector. Make sure it is
within the required voltage range.
4. If the voltage is within the proper range, reconnect
the power connector to the unit.
5. Verify the system fan starts up and air begins to
flow out of the exhaust port.
6. Connect a computer, with the PipeIQ software
installed, to the unit using the Ethernet connection
on the bottom of the unit.
7. Use the PipeIQ software to set up the unit
configuration required for the particular application.
8. When the configuration is complete, remove the
Ethernet connection to the unit.
Table 1b: FAAST 8100 Terminal Designations
Notes:
a) the Terminal Blocks are numbered with T11 to the top
and T1 at the bottom
b) Terminal Block T2 is unused (SLC)
Number
Name
Terminal Block
35
Ext Monitor/Reset
+
T11
34
Ext Monitor/Reset
-
33
Ext Monitor/Reset
-
32
Isolate N/C
T10
31
Isolate COM
30
Isolate N/O
29
Urgent Fault N/C
T9
28
Urgent Fault COM
27
Urgent Fault N/O
26
Minor Fault N/C
T8
25
Minor Fault COM
24
Minor Fault N/O
23
Fire 2 N/C
T7
22
Fire 2 COM
21
Fire 2 N/O
20
Fire 1 N/C
T6
19
Fire 1 COM
18
Fire 1 N/O
17
Action 2 N/C
T5
16
Action 2 COM
15
Action 2 N/O
14
Action 1 N/C
T4
13
Action 1 COM
12
Action 1 N/O
11
Alert N/C
T3
10
Alert COM
9
Alert N/O
8
N/A
T2
7
N/A
6
N/A
5
N/A
4
External Power
+
T1
3
External Power
+
2
External Power
-
1
External Power
-
FAAST 8100 Cabling Requirements
The FAAST 8100 provides a series of Euro style
pluggable terminals, located behind the left side door of
the unit.
Refer to Table 1 for the proper electrical connections to
the unit and Figure 4 for typical connection for monitoring
a Stand-Alone FAAST system at a Fire Alarm Control
Panel (FACP).