background image

 

FAAST 8251BPI and 8100  
INSTALLATION AND MAINTENANCE INSTRUCTIONS

  

19 

 

(iv)  identify cells which do not meet the system constraints 

– highlighted in 

red

 

 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 

(v)  select 

Settings \ Constraints

, then 

CUSTOM

 

-  first review the 

Sensitivity

 settings used by 

VEWFD

EWFD

 or 

SFD

 to identify appropriate settings 

for the system being configured, then apply settings suitable to the 

CUSTOM

 constraints 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

(vi)  accept any advisory notices, then verify all Settings meet the Constraints 

- verify 

Flow Balance

: should be =>0.70 

- select Auto Balance to maximise 

Flow Balance

 and manually adjust 

Hole Diameters

 if required to 

achieve 

Flow Balance

 =>0.70 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание 8251BPI

Страница 1: ...ximum single pipe length 80m External pipe diameter 25mm Internal pipe diameter 15 21mm Specifications 1 Introduction 2 Scope of this Manual 2 Description 2 Features 2 Items Included with Unit 2 Insta...

Страница 2: ...all be discerned by monitoring the user interface at either the local or remote display Features Clip intelligent protocol 8251BPI only Advanced detection using blue LED and IR laser technology Monit...

Страница 3: ...xhaust pipe into the output port ensuring a snug fit DO NOT glue these pipes Wiring Before working on the FAAST system notify all required authorities that the system will be temporarily out of servic...

Страница 4: ...N C T7 22 Fire 2 COM 21 Fire 2 N O 20 Fire 1 N C T6 19 Fire 1 COM 18 Fire 1 N O 17 Action 2 N C T5 16 Action 2 COM 15 Action 2 N O 14 Action 1 N C T4 13 Action 1 COM 12 Action 1 N O 11 Alert N C T3 10...

Страница 5: ...he unit Table 1b FAAST 8100 Terminal Designations Notes a the Terminal Blocks are numbered with T11 to the top and T1 at the bottom b Terminal Block T2 is unused SLC Number Name Terminal Block 35 Ext...

Страница 6: ...ard must be installed on the front panel of the FAAST aspirating smoke detection system For installation first slide the card into the bottom pocket then beneath each of the mounting tabs If necessary...

Страница 7: ...segment is lit in amber Labels Detector faults are labelled adjacent to the indicators on the Air Flow Fault graph User Interface Buttons The User Interface has three buttons shown in Figures 9a 8251B...

Страница 8: ...a configuration fault occurs during the initial configuration or the device is unable to operate due to the configuration the Urgent Fault relay will be set The device must be re configured using Pipe...

Страница 9: ...the FAAST system resets the Fault and Alarm relays It then sets the Isolate relay and the ISOLATE Fault indicator illuminates on the user interface In this mode the fan switches off and the device do...

Страница 10: ...ice returns to its previous state Once the passcode is accepted the locked out button s become active After 45 seconds of inactivity the Fault indicator begins to blink green After an additional 15 se...

Страница 11: ...ice loses power for more than 72 hours the device sets the TIME fault indicating the time needs to be updated Logs Event Log The FAAST system is equipped with internal memory that can be configured to...

Страница 12: ...of its peripherals and cannot function correctly Urgent Fault 7 Aspirator The Fan has stopped operating and requires immediate attention Urgent Fault 8 Filter 8251BPI Device Filter is clogged and requ...

Страница 13: ...nt log viewer Email Notification The FAAST system has the ability to send e mail notifications to an individual or organization Up to 6 different email addresses may be stored for notification Each em...

Страница 14: ...est and fans speed test retrieve and view logs in graph and tabular form control test and monitor FAAST aspirating detectors A comprehensive Help Menu is available from the Menu Bar to guide the user...

Страница 15: ...ing updated ii b ii above Right click the device and select Get Configuration for an existing detector being maintained Section C CONFIGURING FAAST XM 8000 Series in PipeIQ A Configuration the followi...

Страница 16: ...ces using PipeIQ software the default Password is password Caution if a Default Password is changed and then lost there may be a delay before Pertronic can identify the password so that it can be acce...

Страница 17: ...Lock Out Test initiates the self test mode and simulates a Fire 2 Alarm condition The Alarm relays are also latched after the programmed delay Reset to Reset latched Alarms and Defects Isolate initiat...

Страница 18: ...Target Sensitivity for each of the activation levels Alert Action 1 Action 2 Fire 1 and Fire2 the Target Sensitivity represents the sensitivity at the Sampling Point and equates to the sensitivity of...

Страница 19: ...he Sensitivity settings used by VEWFD EWFD or SFD to identify appropriate settings for the system being configured then apply settings suitable to the CUSTOM constraints vi accept any advisory notices...

Страница 20: ...e Day values simply by pressing the arrow viii Select the device from the tree right click and select Device Information record the following details in Section H FAAST XM System Validation Form a Fan...

Страница 21: ...Configuration Sensor the Threshold Levels are converted to five Activations Levels in the panel ALERT ACTION 1 ACTION 2 FIRE 1 and FIRE2 Set the Sensitivity for each Activation Level per the Table bel...

Страница 22: ...activate as a Smoke Alarm or ACTION2 FIRE 1 and one of the pre Alarm thresholds ALERT ACTION 1 or ACTION 2 may be combined on a single circuit on the F16e provided the circuit is configured for Reside...

Страница 23: ...onitor Live Events as they occur Search for Live Events Produce Reports in pdf doc or xls format Clear Live Events Stored Events Retrieve Stored Events Search for Stored Events produce Reports in pdf...

Страница 24: ...ual holes meets the minimum performance requirements for individual points Note that this may require reference to the approval compliance notes for the particular ASD system and should also take into...

Страница 25: ...cating smoke has been detected this is the Transport Time for this Sample Point the Maximum Transport Time shall be less than the maximum time specified within the design documentation engineering spe...

Страница 26: ...erify the settings are suitable for the site refer to Section C Device Details F2g System Handover During the commissioning all results shall be recorded These along with all configuration data shall...

Страница 27: ...34 1 64 1 65 34 3 35 1 68 1 70 35 3 36 1 73 1 75 36 4 37 1 78 1 80 37 4 38 1 83 1 85 38 4 39 1 88 1 90 39 5 40 1 92 1 95 40 5 41 1 97 2 00 41 6 42 2 02 2 05 42 6 43 2 07 2 10 43 6 44 2 12 2 15 44 7 4...

Страница 28: ...lterations occurring after the date of manufacture In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other warranty expressed or implied what...

Страница 29: ...umber Loop Address Contact Person Customer Name Facility Name Facility Location Device Location Site Address Night Mode Start Time End Time Daylight Saving Starts On Ends On Time Format 12 Hour 24 Hou...

Страница 30: ...Action 1 Action 2 Fire 1 Fire 2 Urgent Isolate Minor AirFlow Flow Boundary Flow Delay Sec User Interface Button Activation Passcode Button Lock Out Test Reset Isolate ModBus Passcode Address System T...

Отзывы: