FAAST 8251BPI and 8100
INSTALLATION AND MAINTENANCE INSTRUCTIONS
16
b) Sensor:
(i) Alarm Threshold and Delay:
Enable or Disable Acclimate Mode:
Acclimate Mode:
-
Enable :
enter the
Min
and
Max
Sensitivity Level for each activation level
-
Disable :
enables
Threshold Mode
Threshold Levels (%/m):
- enter the required
Day
,
Night
and
Weekend
Sensitivity Level for each
activation level
Note:
the
Threshold
Levels
may
alternatively be set during Design
– refer to
Design
Delay (sec):
introduces a specified delay
and verifies if the alarm condition still exists
before triggering the Alarm
(ii) Night Mode:
select Start Time and End Time
(iii) Alarm/Fault Relay Latching:
Alarms and Minor Fault can be individually configured to be Latching or Non-Latching
c) Network:
(i) Passwords:
FAAST XM devices have two types of
password
:
-
Web Access Password
:
required to
access remote monitoring available via a
web browser
-
the default
Password
is
1234
-
Administrator Password
- required to
reconfigure FAAST devices using PipeIQ
software
-
the default
Password
is
password
Caution:
if a Default Password is changed
and then lost, there may be a delay before
Pertronic can identify the password so that it
can be accessed or changed
(ii) Device Mail Server Configuration:
-
Sender Account
:
enter the email ID for the
Sender Account
-
SMTP Server Name:
enter the
SMTP Server Name
to use for email communication
-
SMTP Port
: default Port = 25
- contact the site IT department to confirm the correct Port
(iv) Device Connection:
select an IP Address automatically via DHCP or use a Static IP Address:
- Obtain an IP Address automatically via DHCP
- contact the site IT department to obtain the information required to connect to the site
’s ethernet
- Use a Static IP Address:
- IP Address:
Default = 192.168.1.10
- Subnet Mask:
Default = 255.255.255.0
- Default Gateway:
Default = 192.168.1.1
- DNS Server: Primary and Secondary - contact the site IT department to obtain the information required
(v) Email Notification:
- enter the Email addresses of the Users to whom to send the Alarm notifications. Email addresses may be
a Group of addresses
- select the notifications each user should receive using the check boxes
8100 Only