FAAST 8251BPI and 8100
INSTALLATION AND MAINTENANCE INSTRUCTIONS
20
(vii) the amended Sensitivity settings will be reflected in the Sensor settings in Configuration
– refer to
Threshold Levels (%/m)
under
Alarm Threshold and Delay
in
Configuration \ Sensor
- in the screenshot below, the
Day Threshold Levels
reflect the fact the
Day
Sensitivity has been
amended, while
Night
and
Weekend
are default values
-
Night
and
Weekend
Threshold Levels can be sequentially updated to match the
Day
values
simply by pressing the arrow
(viii) Select the device from the tree, right click and select
Device Information.
- record the following details in Section H : FAAST
XM System Validation
Form:
a. Fan Speed RPM
b. Flow Velocity Inlet 1
c. Flow Velocity Inlet 2
d. Flow Velocity Inlet 3
e. Flow Velocity Inlet 4
f. Flow Base Inlet 1
g. Flow Base Inlet 2
h. Flow Base Inlet 3
i. Flow Base Inlet 4
- Flow Velocity values represent the current flow
rate through each Inlet
- Flow Base values represent the flow rates as
measured during the BaseLining process
Flows are measured in m/s, while PipeIQ calculates
flow rates in l/min - a Flow Rate Conversion Table is
available at Section G