ENGLISH

 

5.2   2

nd  

LEVEL PROGRAMMING

 

To access 2ND LEVEL PROGRAMMING, press push-button 

and  hold down while pressing push-button 

+

:

 

   if you also release push-button 

F

, the display shows the value of the function  that can  be modified  with keys 

and 

-

.

 

• 

  if you press  key 

(and  hold  down), the display shows the  name  of  the next function.  If you release it, the  value 

that can  be  modified  with keys 

and 

is displayed.

 

• 

  when you reach  the last function,  press 

to exit programming, and  the display resumes showing the automated 

system status.

 

 

 

2

nd 

LEVEL  PROGRAMMING

 

Display

 

Function

 

Default 

1

 

bo

 

MAXIMUM TAKE-OFF  POWER:

 

The motor  works at  maximum  power  (ignoring the selected  power  level) during the  move- 
ment  take-off.

 

 

= active

 

no 

= excluded

 

no

 

PF

 

PREFLASHING:

 

Allows 5 types of preflashing to be  selected,  with a duration  equal  to 3 secs.

 

 

no 

= no  preflashing

.

 

OC  

=preflashing before  each movement.

 

CL 

= preflashing  before  a  closing  movement.

 

OP 

= preflashing  before  an  opening movement.

 

PA 

= preflashing  only at  end  of  pause.

 

no

 

tP

 

PREFLASHING TIME (visible  only if preflashing   is selected in the previous menu):

 

Adjusts preflashing time  from   

1  

to 

10 

sec. in 1 second  steps.

 

 

01  

= minimum  preflashing

 

10  

= maximum  preflashing

 

03

 

Ph

 

CLOSING  PHOTOCELLS:

 

Activate  the function  if you want the closing photocells  to lock movement  and  reverse it on 
disengagement.  Normally,  operation  of  the  closing  photocells  immediately   puts the  gate 
into reverse when this function  is off.

 

Y   

= reversal on disengagement

 

no 

= immediate reversal to opening

 

no

 

oP

 

OPENING  PHOTOCELLS:

 

Activate  the  function  if you want  the  opening  photocells  to  lock  movement   and  reverse it 
during closing. Normally, with this function  off, operation  of the opening  photocells  determines 
the resumption of movement  on their disengagement.

 

n o 

= immediate reversal to closing

 

no 

= resumption of motion  on disengagement

 

no

 

Ad

 

ADMAP FUNCTION

 

Permits activation  of operation  in accordance with French standard  NFP 25/362.

 

Y   

= active

 

no 

= excluded

 

no

 

EC

 

ENCODER:

 

The "virtual"  encoder  on  the  board  operates  as an  anti-crushing device  and  manages  the 
slowing and  partial opening  start points.

 

If the gate  strikes an obstacle  during the opening  or closing stage, the "virtual" encoder  causes 
reversal of the motion.  The second  obstacle  detected in the same direction causes the motor 
to stop. An alarm is signalled in both  cases (see section on alarms).

 

It is  necessary to  adjust  the  sensitivity  of  the  "virtual"  encoder  by  varying the  time  that  the 
board  waits for before  controlling reversal of motion  from a minimum  of 

sec to a maximum 

of 

10 

sec in one-second  steps.

 

00 

= maximum  sensitivity

 

10 

= minimum  sensitivity

 

02

 

Содержание Estate Swing E-SL 1800

Страница 1: ...E SL 1800...

Страница 2: ...N 12453 and EN 12445 For non EU countries to obtain an adequate level of safety the Standards mentioned above must be observed in addition to nation al legal regulations 11 Before attempting any job o...

Страница 3: ...ATION 6 5 4 INSTALLING THE RACK 7 5 4 1 STEEL RACK TO WELD Fig 11 7 5 4 3 NYLON RACK TO SCREW Fig 13 7 5 4 2 STEEL RACK TO SCREW Fig 12 7 6 OPERATIONAL START UP 8 6 1 ELECTRONIC BOARD CONNECTION 8 6 1...

Страница 4: ...ergency batteries are not installed or if the operator is not in service These operators in addition to having different features and technical specifications also differ as to the following compo nen...

Страница 5: ...to be automated an upper guide must be provided plus mechanical limit switches to pre vent the gate derailing The gate slide track must be linear and horizontal Manual movement of the gate must be eas...

Страница 6: ...h as shown in Fig 7 and wall in the founda tion plate supplying one or more sheaths for routing electric cables through the hole in the foundation plate Using a spirit level check if the plate is perf...

Страница 7: ...hough openings in the motor casing see Fig 9 re 1 Fig 8 and Fig 9 refer to operator C720 E SL1800 3 Adjust the height of the gearmotor and the distance from the gate with reference to the dimensions i...

Страница 8: ...e slot In this way the slot play will enable any adjustments to be made 3 Mark the drilling point on the gate Drill a 1 4 in hole and apply thread with a 3 8 in male tap Screw the bolt 4 Move the gate...

Страница 9: ...on the control board connections programming mainte nance always turn off power Observe points 10 11 12 13 14 of the GENERAL SAFETY OBLIGATIONS Follow the instructions in Fig 3 to arrange the cables i...

Страница 10: ...t be left from the mechanical limit switches 7 TESTING THE AUTOMATED SYSTEM Once the operator has been installed carry out a thorough oper ational check of all accessories and connected safety devices...

Страница 11: ...e which must comply with current standards and of the release devices 10 REPAIR Contact an authorized Repair Centre for repairs 11 ACCESSORIES 11 1 BATTERY KIT Install the battery kit as shown in Fig...

Страница 12: ...the gate re closes by itself after the selected pause time If semi automatic operating mode has been selected a second pulse must be sent to re close the gate An opening pulse issued during the re cl...

Страница 13: ...RELEASE BATTERY E E7 72 20 BUS 2EASY F OPEN A GND OPEN B CLOSE SAFE STOP SAFE FSW OP GND FSW CL 24 RADIO XF SETUP USB OUT...

Страница 14: ...RORS 15 10 FUNCTION LOGICS 16 EC DECLARATION OF CONFORMITY Manufacturer FAAC S p A Address Via Calari 10 40069 Zola Predosa BOLOGNA ITALY Declares that Electronic device E720 conforms to the essential...

Страница 15: ...differential thermal breaker with adequate tripping threshold Connect the earth lead to the appropriate terminal Always separate power cables from control and safety cables push button receiver photoc...

Страница 16: ...DESCRIPTION 1 OPEN A Device with N O contact that causes total opening of the gate 2 6 GND Accessory power supply negative 3 OPEN B CLOSE SAFE Device with N O contact that causes partial opening of t...

Страница 17: ...hotocells it is advisable to select the type of operation on the basis of the area of move ment that they need to protect Safety devices during closing operate only during the automated system closing...

Страница 18: ...ient Tab 2 Description of BUS 2EASY led Ensure that there are not two or more pho tocell pairs with the same address If no BUS 2EASY accessory is used leave the BUS 2EASY connector J12 fig 1 free Tab...

Страница 19: ...E SAFE SAFE Fig 6 Connection of a pair of closing photocells and a pair of opening photocells Fig 9 SAFE SAFE Connection of a pair of closing photocells a pair of open ing photocells and a pair of ope...

Страница 20: ...e name of the next function etc When you reach the last function press push button F to exit the program and store the parameters The display shows again the status of the automated system 1st LEVEL P...

Страница 21: ...e total gate travel Adjustable from 5 with speed 5 10 with speed between 5 and 8 15 with speed 8 to 99 in 1 steps 5 10 15 minimum slowing 99 maximum slowing 20 rc SLOWING DURING CLOSING Adjusts the sl...

Страница 22: ...ELLS Activate the function if you want the closing photocells to lock movement and reverse it on disengagement Normally operation of the closing photocells immediately puts the gate into reverse when...

Страница 23: ...OSED 07 gate in MOTION 08 gate OPENING 09 gate CLOSING 10 ACTIVE safety 11 timed output that can be activated by second radio channel see next function 12 output that can be activated by second radio...

Страница 24: ...return to gate status display 00 CLOSED 07 FAIL SAFE in progress 01 OPEN 08 BUS 2EASY device check in progress 02 Stop then OPEN 09 Preflashing then OPEN 03 Stop then CLOSE 10 Preflashing then CLOSE...

Страница 25: ...utton twice in quick 1 succession The automated system will carry out an 2 opening control Ensure the automated device is free of any obstacle by people 3 or things To enable other radiocontrols with...

Страница 26: ...Normally Closed contact and the corresponding leds must therefore be ON where the automated system is in stand by they will go off when the connected device is engaged The inputs OPEN A OPEN B CLOSE...

Страница 27: ...oon as the led for the FCA limit switch on the board goes off secure with the appropriate screws 4 Move the gate to closing position manually leaving 1 5 8 in from the limit switch me chanical stop 5...

Страница 28: ...when it reaches the limit switch If the limit switch reached is the opening switch with the SQUARE the device stores that point as the opening stop conversely if the limit switch is the closing switc...

Страница 29: ...se inputs are shown in brackets The CLOSE can be activated at the OPEN B input from the 2nd programming level LOGIC E PULSES STATUS OF AUTOMATED SYSTEM OPEN A OPEN B CLOSE STOP FSW OP FSW CL FSW CL OP...

Страница 30: ...e opens the gate partially time B no effect no effect OPEN inhibited no effect OPEN inhibited no effect no effect OPEN inhibited DURING OPENING reverses to closing 1 reverses to closing 1 recloses the...

Страница 31: ...hibited no effect OPEN inhibited no effect CLOSE inhibited no effect OPEN CLOSE inhibited LOGIC C COMMANDS MAINTAINED PULSES STATUS OFAUTOMATED SYSTEM OPEN A CLOSE STOP FSW OP FSW CL FSW CL OP CLOSED...

Страница 32: ...liegendem Handbuch sind unverbindlich FAAC beh lt sich das Recht vor ohne die wesentlichen Eigenschaften dieses Ger tes zu ver ndern und ohne Verbindlichkeiten in Bezug auf die Neufassung der vorliege...

Отзывы: