manualshive.com logo in svg
background image

Fig. 9

A maximum of 16 BUS photocell pairs can be connected to 
the board.
The photocells are split into groups:

Opening 

photocells: 

  max 

6

Closing 

photocells: 

  max 

7

Opening /Closing photocells: 

 

max 2

Photocell used as an OPEN pulse: 

max 1

Fig. 9 shows a 2-swing leaf automated system indicating the 
coverage beams of the photocells:

A:  Photocells with OPENING and CLOSING action

B:  Photocells with OPENING action

C:  Photocells with OPENING action

D:  Photocells with CLOSING action

Dip1

Dip2

Dip3

Dip4

Ref.

Type

OFF

OFF

OFF

OFF

B -C

OPENING

OFF

OFF

OFF

ON

OFF

OFF

ON

OFF

OFF

OFF

ON

ON

OFF

ON

ON

OFF

OFF

ON

ON

ON

ON

OFF

OFF

OFF

D

CLOSING

ON

OFF

OFF

ON

ON

OFF

ON

OFF

ON

OFF

ON

ON

ON

ON

OFF

OFF

ON

ON

OFF

ON

ON

ON

ON

OFF

OFF

ON

OFF

OFF

A

OPENING and 

CLOSING

OFF

ON

OFF

ON

ON

ON

ON

ON

/

OPEN PULSE

Tab. 4 - Addressing of BUS Photocells

Table 4 shows the programming operations of the dip-switch 
inside the transmitter and of the BUS Photocells receiver.

8.3  MEMORY STORAGE OF BUS ACCESSORIES

You can add the BUS photocells to the system at any time, 
simply by memory-storing them on the board, observing the 
following procedure:

Install and program the accessories using the required 
address (see paragraph 

8.2

)

Cut power to the board.
Connect the two accessories cables to the red 
terminal-board J10 (any polarity will do).
Power up the board, taking care to first connect the 
main power supply (transformer output) and then any 
batteries.
Quickly press once only the SW1 (SET-UP) push-button, to 
execute learning. The BUS LED flashes.
Give an OPEN impulse, leaves will move and the BUS 
learning procedure is over.

The board has memory stored the BUS accessories. Follow the 
instructions in the table below to check if the BUS connection 
is correct.

Tab. 5 - Description of BUS LED

Steady light

Normal operation (LED ON even in the 
absence of photocells)

Slow flashing 
lamp

(flash

every 0.5 sec)

At least one input engaged: photocell 
engaged or not aligned, Open A or Open 
B or Stop input engaged

Light OFF

(flash every 2.5 
sec)

BUS line short circuited

Fast flashing 
lamp

(flash

every 0.2 sec)

If you have detected a BUS connection 
error, repeat the acquisition procedure. If 
the error is repeated, make sure that there 
is not more than one accessory with the 
same address in the system (also see the 
accessories instructions)

1.

2.
3.

4.

5.

6.

 9  MEMORY STORING THE RADIO CODE

The control board has an integrated 2-channel decoding 
system (DS, SLH, LC) named OMNIDEC. This system makes it 
possible to memory-store both total opening (OPEN A) and 
partial opening (OPEN B) of the automated system - this is 
made possible by an additional receiver module (Fig.10 ref. 

) and radio controls on the same frequency. 

  The 3 types of radio codes (DS, LSH, LC) cannot 

coexist.

 

Only one radio code can be used at a time.
To change over from one code to another, you 
must delete the existing one (see paragraph 
on deletion), and repeat the memory-storage 
procedure.

ENGLISH

7

Содержание E700

Страница 1: ...E 700 E 700...

Страница 2: ...tion This product underwent a test in a typical uniform configuration all products made by FAAC S p A Bologna 01 Mars 2008 The Managing Director A Bassi 1 BOX LAYOUT 2 2 WARNINGS 3 3 LAYOUT AND CONNEC...

Страница 3: ...lid hinges can be moved upward to allow opening the box housing Fig 3 they can also be removed and re positioned in order to enable the lid to open to the right or left When you have secured the box i...

Страница 4: ...g any work on the control unit connections maintenance always turn off power Install upstream of the system a differential thermal breaker with adequate tripping threshold Always separate power cables...

Страница 5: ...C Device with NC contact which causes contact which causes the automated the automated system to shut down system to shut down 4 OPEN B Device with N O contact see chap FUNCTION LOGICS 5 OPEN A J10 RE...

Страница 6: ...est automated system condition is shown in bold Check the status of the signalling LEDs as per table below Tab 1 Operation of inputs status LEDs If you connect an electric lock to terminal J4 position...

Страница 7: ...LEDs of both encoders show the FLASHING status In this situation refer to the configuration in TAB 3 to define which encoder connection to rotate DL 3 indicates on a steady flashing beam the reading o...

Страница 8: ...ect the main power supply transformer output and then any batteries Quickly press once only the SW1 SET UP push button to execute learning The BUS LED flashes Give an OPEN impulse leaves will move and...

Страница 9: ...e automated system performs one opening operation Make sure that the automated system is free of any obstacle created by persons or things To add other radio controls transfer the code of the memory s...

Страница 10: ...EDURE To delete ALL the input radio control codes press push button LOGIC SW3 or SPEED SW2 and while holding it down also press push button SETUP SW1 for 10 sec The LED relating to the pressed push bu...

Страница 11: ...OPEN CLOSED opens leaves opens leaf 1 no effect opening inhibited no effect opening inhibited no effect no effect opening inhibited opens leaves OPENING stops operation 1 stops operation stops operat...

Страница 12: ...rliegendem Handbuch sind unverbindlich FAAC beh lt sich das Recht vor ohne die wesentlichen Eigenschaften dieses Ger tes zu ver ndern und ohne Verbindlichkeiten in Bezug auf die Neufassung der vorlieg...

Отзывы: