9

ENGLISH

N.B.:

1) For installation of electrical cables use suitable rigid

or flexible piping.

2) Always keep the low voltage accessory connection

cables separate from the 230 V power cables. Use
separate sheaths to avoid any interference.

3. INSTALLATION

3.1 PRELIMINARY CHECKS

To ensure correct operation of the automatic unit the structure
of the existing door must meet the following requirements:

- length and weight as specified in Table 3 (section 1.1);
- max. doorpost depth as specified in Table 4;
- robust and rigid structure of the leaf;
- good condition of the existing hinges;
- smooth, uniform movement of the leaf with no abnormal

friction at any point of its travel;

- “neutral” position of the door during its entire travel. If the

door tends to close or open, check the alignment of the
hinges.

- Presence of mechanical end stops.

3.2 MOUNTING THE OPERATOR

1)

Remove the protective casing (fig. 3) and the end covers
(fig. 4) from the operator.

Warning

: Before removing the end cover with the function

switch, remove the connector joining the switch to the 959MP
electronic control unit.

2)

As regards the mounting position of the operator (on the
lintel or on the door) and the type of arm to use (pushing,
pulling or sliding), refer to the relevant mounting table and
drill the holes required to mount the operator and the
pulling arm.

N.B.:

 The two intermediate operator fixing holes are not in a

central position (see mounting tables). The holes are offset in
order to ensure that the operator is mounted with the correct
direction of rotation of the mechanism.

The mounting tables are the following:

Table A: LINTEL MOUNTING (PUSHING ARTICULATED ARM)

Outward opening

Table B: DOOR MOUNTING (PUSHING ARTICULATED ARM)

Inward opening

Table C: LINTEL MOUNTING (SLIDING ARM) 

Inward opening

3)

Mount the operator using the six M6 screws and washers
provided.

Warning

:

- The structure of the lintel (or the door) at the operator

mounting position must not exhibit any significant
deformation.

- The operator must be mounted parallel to the floor.

N.B.:

 If the sliding arm is to be used, the driving arm must be

mounted before the operator is fixed on the lintel (see section
3.3.3.).

 3.3 MOUNTING THE DRIVING ARMS

3.3.1

MOUNTING THE PUSHING ARTICULATED ARM (fig. 5)

1)

Close the door.

2)

Free arms (1) and (2) by pulling apart the coupling (3)
manually as shown in fig. 5.

3)

Fit arm (1) on the operator transmission shaft by means of
the extension and the screw (4) provided (fig. 5). The arm
must be mounted perpendicular to the closed door.

N.B.:

  If a greater distance between the operator and the arm

is required, use the higher extensions available as accessories
(see Table A/B).

4)

Mount plate (5) of arm (2) on the door or the lintel using the
two M6 screws and the washers provided (fig. 5). The

installation distances are given in Table A/B.

5)

Slacken the fixing screw (6) and assemble the two arms by
means of coupling (3) (fig. 5).

6)

Turn arm (1) until arm (2) is perpendicular to the closed
door or the lintel as shown in fig. 5 (a-b), sliding the spacer
(7) along arm (2).

7)

Tighten the fixing screw (6) between the two arms.
The length of arm (2) is given in the relevant mounting
tables. If necessary, cut off the section of the arm extending
beyond the articulation and then cover the ends using the
caps provided (fig. 5).

8)

Check manually that the door is free to open and close
fully and that it comes to rest against the mechanical end
stops. If the door does not close correctly, adjust the return
spring as described in section 10.

3.3.2

MOUNTING THE SLIDING ARM (fig. 6)

1)

Mount arm (1) on the operator transmission shaft by means
of the extension and the screw (2) provided (fig. 6). The
arm must be fitted pointing 45° outwards as shown in fig.
6(a).

N.B.:

 If a larger distance is required between the operator and

the arm use the higher extensions available as accessories (see
Table C).

Warning

: Mount arm (1) on the transmission shaft before fitting

the operator on the lintel (fig. 6).

2)

Insert the roller (3) inside the sliding guide (4) (fig. 6).

3)

Pull arm (1) inwards manually as shown in fig. 6(b) and
secure the sliding guide (4) by means of two M6 screws on
the closed door as shown in Table C.

4)

Check manually that the door is free to open and close
fully and comes to rest against the mechanical end stops.
If the door does not close correctly, adjust the return spring
as described in section 10.

4. START-UP

1)

Make the electrical connections to the 959 MP electronic
control unit as described in section 6.
To gain access to the control unit, pass the cables through
the special conduit (fig. 1 - ref. 1) as shown in fig. 8.

2)

Fit the two end covers and connect up the function switch.
The end cover with the switch may be fitted on the right or
the left. For cable routing refer to fig. 8.

3)

Turn the operating function switch (fig. 1 - ref. 12) to
position I (

AUTOMATIC 

logic).

4)

Check that the programming unit microswitches (fig. 10)
are all in the 

OFF 

position.

Important

: When mounting the “pulling articulated” or “sliding”

arms or for opening angles greater than 90°, turn 

microswitch

no. 2 to ON 

before connecting power to the system.

5)

Close the door.

6)

Power up the operator. Powering is signalled by an acoustic
signal from a buzzer.

7)

Check that the 5V LED on the programming unit (fig. 9)
lights up.

8)

At the end of the initialisation procedure, check the status
of the signalling LEDs on the programming unit as shown in
Table 5.

Содержание 959 B-E

Страница 1: ...tfreundlich 100 Altpapier pour la nature papier recycl 100 for nature recycled paper 100 per la natura carta riciclata 100 para la naturaleza 100 papel reciclado C ERME T A Z I E N D A C E R TIF I C A...

Страница 2: ...bsequent amendments 91 368 EEC 93 44 EEC and 93 68 EEC complieswiththeessentialsafetyrequirementsinthefollowingEECDirectives 73 23 EEC and subsequent amendment 93 68 EEC 89 336 EEC and subsequent amen...

Страница 3: ...with an opening distance of the contacts of 3 mm or more Alternatively use a 6A thermomagnetic breaker with multi pole switching 12 Ensure that there is a differential switch up line of the electrical...

Страница 4: ...3 ITALIANO Fig 2a Fig 3 Fig 2b Fig 4 Fig 8 2x0 5 mm2 2x0 5 mm 2 2x0 5 mm 2 3x1 5 mm 2 230 V 2 x 0 5 mm 2 6 5 4 3 7 1 8 2 2 2x0 5 mm 2 schermato screened blind abgeschimt apantallado...

Страница 5: ...4 ITALIANO Fig 5 90 90 2 1 2 1 3 7 6 5 4 2 1 a b 45 45 1 3 2 1 4 4 1 a b Fig 6...

Страница 6: ...eje est ndar por una de lasopcionales prolongaci n de 20 mm prolongaci n de 50 mm En tal caso sumar a las cotas interesadas la altura correspondiente 20 50 mm Quote in mm Dimensions in mm Cotes en mm...

Страница 7: ...e der beiden optionalen Verl ngerungen ersetzen Wellenverl ngerung 20 mm Wellenverl ngerung 50 mm In diesem Fall ebenfalls die betreffenden H henma evergr ern 20bzw 50mm Cota con prolongaci n del eje...

Страница 8: ...prolongaci n de 20 mm prolongaci n de 50 mm En tal caso sumar a las cotas interesadas la altura correspondiente 20 50 mm 0 160 Quota con prolunga albero standard Nel caso sia necessario aumentare la d...

Страница 9: ...nal 24 Vdc electric lock power supply N O N C 24 Vdc accessories power supply Terminalstripinputs Functionswitch CODIS optional Internal external emergency STOP safety device CLOSURE safety device 1 1...

Страница 10: ...d use the higher extensions available as accessories see Table A B 4 Mount plate 5 of arm 2 on the door or the lintel using the two M6 screws and the washers provided fig 5 The installation distances...

Страница 11: ...s of the settings Turn the trimmers anticlockwise to reduce the values of the settings 5 3 PROGRAMMING THE MICROSWITCHES fig 10 The programming unit has a series of microswitches which allow the funct...

Страница 12: ...12 STOP safety control fig 19 a any device safety sensor photocell etc which by opening a contact has a safety effect on the operating cycle In particular this safety device interrupts the opening cl...

Страница 13: ...LOCK N O EL LOCK COM L screened cable 2 x 0 5 mm2 50 m max 2 NIGHT ONE WAY CODIS L L 1 2 3 2 1 4 3 0 Vdc 1 1 230 V 6 10 50 60 Hz N F N O C INTERNAL SENSOR N F N O C EXTERNAL CONNECTOR BROWN WHITE GREE...

Страница 14: ...mum opening by 60 to 100 The standard setting is 100 LED 2 o PAUSE TIME adjust to 0 30 seconds Theopeningiscontrolledbymeans Fig 21 g Programming unit connector 14 pole 7 FUNCTION SWITCH The 959 B E o...

Страница 15: ...of lit LEDs indicated in Table 7 5 Pressthe and pushbuttonssimultaneouslytoactivate or deactivate the function and check the status of LED 6 according to the indications of Table 7 Note the standard...

Страница 16: ...onsecutive operating cycles The control devices in any case take priority over the operation of the system The programme can be cancelled by performing a RESET function 18 Level II RESET active inacti...

Страница 17: ...or allow children or adults to stand within range of the door especially during operation and do not leave objects near it Do not allow children to play with the door Do not deliberately obstruct move...

Страница 18: ...ner al d a la presente publicaci n todas las modificaciones que considere oportunas para el perfeccionamiento t cnico o para cualquier otro tipo de exigencia de car cter constructivo o comercial FAAC...

Отзывы: