Extreme Networks Consolidated "i" and "e" Series Hardware Installation Guide
Alpine 3800 Series Chassis Installation
•
AWG, high-strand-count copper wire cable, appropriate for your chassis
—
8 AWG for the Alpine 3808
—
10 AWG for the Alpine 3804
—
14 AWG for the Alpine 3802
•
Flathead screwdriver
To ground the chassis:
1
Strip 0.5 inch (1.2 cm) of insulation from the appropriate AWG, high-strand-count copper wire cable.
2
Insert the cable into the cable lug.
CAUTION
Be sure that no copper is visible between the lug and the cable insulation.
3
Using a
1
/
4
-inch or
5
/
16
-inch flathead screwdriver, tighten the cable retention screw, to 20 inch-pounds
of torque.
4
Attach the ground lug, lock washers, and nuts (in that order) to the grounding studs on the rear of
the chassis. Tighten the nuts to 125 inch-pounds of torque.
After the chassis is installed, install power supplies and connect power as described in Chapter 8. Then
install required modules as described in Chapter 9 and Chapter 10.
Removing the Chassis
This section describes how to remove the Alpine 3800 series chassis from a rack.
To remove the Alpine 3800 series chassis from a rack, you need the following tools, equipment, and
resources:
•
Helper bracket (provided)
•
A minimum of four appropriate screws to secure the helper bracket (not provided)
•
# 1 Phillips screwdriver
•
A minimum of two people to help remove the chassis from the rack
To remove the Alpine 3800 series chassis from a standard 19-inch (48.26 cm) rack:
1
Unplug the power cable from the outlet and then from the switch before you attempt to remove the
chassis components and the chassis from the rack.
2
Mount the helper bracket in the rack directly beneath the chassis using four screws that are
appropriate for your rack.
3
To reduce weight and prevent possible equipment damage, use a # 1 Phillips screwdriver to remove
the:
•
Power supply, SMMi, and I/O modules from the Alpine 3808 and Alpine 3804
•
I/O modules from the Alpine 3802
For information about removing power supplies, see Chapter 8.
For information about removing the SMMi, see Chapter 9.
For information about removing I/O modules, see Chapter 10.
Содержание Alpine 3802
Страница 18: ...18 Extreme Networks Consolidated i and e Series Hardware Installation Guide Preface ...
Страница 19: ...Part 1 Common Features ...
Страница 20: ......
Страница 24: ...24 Extreme Networks Consolidated i and e Series Hardware Installation Guide Common Switch Features ...
Страница 25: ...Part 2 Site Planning ...
Страница 26: ......
Страница 56: ...56 Extreme Networks Consolidated i and e Series Hardware Installation Guide Site Preparation ...
Страница 57: ...Part 3 Summit Switch ...
Страница 58: ......
Страница 106: ...106 Extreme Networks Consolidated i and e Series Hardware Installation Guide Summit Switch Models ...
Страница 116: ...116 Extreme Networks Consolidated i and e Series Hardware Installation Guide Summit Switch Installation ...
Страница 137: ...Part 4 Alpine Switch ...
Страница 138: ......
Страница 158: ...158 Extreme Networks Consolidated i and e Series Hardware Installation Guide Alpine 3800 Series Chassis Installation ...
Страница 208: ...208 Extreme Networks Consolidated i and e Series Hardware Installation Guide Alpine 3800 Series I O Modules ...
Страница 213: ...Part 5 BlackDiamond Switch ...
Страница 214: ......
Страница 303: ...Part 6 Switch Operation ...
Страница 304: ......
Страница 307: ...Part 7 Appendixes ...
Страница 308: ......
Страница 314: ...314 Extreme Networks Consolidated i and e Series Hardware Installation Guide Safety Information ...
Страница 368: ...368 Extreme Networks Consolidated i and e Series Hardware Installation Guide Module Technical Specifications ...
Страница 376: ...376 Extreme Networks Consolidated i and e Series Hardware Installation Guide Installing GBICs and Mini GBICs ...