background image

26

ENGLISH

settInGs

• 

date-tIme

• 

lanGuaGe

• 

deGrees

 

See chapter: firSt ignition SettingS

DISPLAY

This menu allows you to adjust the brightness of the display. The values range from OFF, 1 to 20. if set to OFF, the display backlighting is set 

to maximum brightness and turns off after a 60 second delay.

The backlighting can be turned on again by pressing any key or if the stove is in alarm status.

CONTrOLs PrOCeDUre

 

Š

Press key 6.

 

Š

Press key 3 until 

SETTINgS

 appears and confirm by pressing key 6.

 

Š

Keep pressing key 3 until 

DISPLAY

 appears and confirm by pressing key 6.

 

Š

Use keys 4-5 to set the desired intensity.

 

Š

Press key 6 to confirm and key 1 to scroll back through the menus until the initial page.

STAND BY

The 

STAND BY

 function, if enabled, is used when stove switch-off is to be controlled by means of an additional thermostat

CONTrOLs PrOCeDUre

 

Š

Press key 6.

 

Š

Press key 3 until 

SETTINgS

 appears and confirm by pressing key 6.

 

Š

Keep pressing key 3 until 

STAND BY

 appears and confirm by pressing key 6.

 

Š

Use keys 4-5 to enable (

ON

) / disable (

OFF

).

 

Š

Press key 6 to confirm and key 1 to scroll back through the menus until the initial page.

J

FOR CORRECT OPERATION, THE SET THERMOSTAT MuST BE SET TO LOW-TA.

> SEE CHAPTER ON ADDITIONAL THERMOSTAT SETTINgS

stand By funCtIon on

if the sTaND-BY function is active (ON), if the room temperature exceeds the value of the 

SET THERMOSTAT

 + 

DELTA T OFF

, then the stove 

will switch off after a preset delay, displaying 

STAND BY

.

when the room temperature is lower than the 

SET THERMOSTAT

 - 

DELTA T ON

 and after a possible cooling time, the stove switches back on.

stand By funCtIon off (faCtory settInG)

if the sTaND-BY function is not active (OFF ), if the stove exceeds the set room temperature it will switch to the minimum value, modulating 

and displaying 

MODuLATION

. when the room temperature is lower than the 

SET THERMOSTAT

 the stove goes back to operating at the set 

power, displaying 

WORk

.

operatIon wIth addItIonal thermostat (optIonal) 

stand By funCtIon off

 (FaCTOrY seTTiNg)

if the sTaND-BY function is not active (OFF ), if the stove exceeds the room temperature set on the additional thermostat (contact open) it will 

switch to the minimum value, displaying mODULaTiON. when the room temperature is lower than the value set on the additional thermostat 

(contact closed), the stove goes back to operating at the set power, displaying wOrK.

stand By funCtIon on

when the sTaND-BY function is active (ON), when the room temperature set on the additional thermostat has been reached (contact open), 

the stove will switch off after a preset delay, displaying 

STAND BY

.

when the room temperature is lower than the value set on the additional thermostat (contact closed) and after a possible cooling time, the 

stove switches back on.

Содержание 001284000

Страница 1: ...MADE IN ITALY design production DAHIANA DAHIANA plus TEOREMA 004280386 Rev 000 UK pellet stoves USER MANUAL...

Страница 2: ...2 ENGLISH...

Страница 3: ...the chrono 24 Settings 26 Display 26 stand by 26 OPERATION with additional thermostat optional 26 Additional thermostat 27 Additional thermostat installation 27 delta t 27 First Load 27 reset 27 Addit...

Страница 4: ...OIRE Avant de bouger le po le faire attention lever les c ramiques indiqu es pour viter des d g ts OBVEZNA POZORNOST Prije pomicanja pe i uklonite ozna ene plo ice kako biste izbjegli o te enja VORSIC...

Страница 5: ...TEOREMA 5 ENGLISH...

Страница 6: ...well as the instructions contained in this manual The Manufacturer cannot be held responsible for the failure to comply with such precautions After removing the packaging ensure that the content is in...

Страница 7: ...ply cable so that it does not come into contact with hot parts ofthe appliance The power supply plug must be accessible after installation Do not close or reducethe dimensions ofthe airingvents in the...

Страница 8: ...uid is used the latter could penetrate inside the crackles highlighting them SINCE THE PRODUCT CAN TURN ON AUTOMATICALLY THANKS TO THE TIMER OR REMOTELY USING THE DEDICATED APPLICATIONS IT IS STRICTLY...

Страница 9: ...mestichotwaterproductionandinadjacentandcommunicating rooms 3 where the depression measured in situ between the external and internal environment is greater than 4 Pa N B Watertight appliances can als...

Страница 10: ...tion If the exhaust is not inserted in an existing flue a vertical section with a windproof end piece is required UNI 10683 The vertical duct can be inside or outside the building If the smoke duct is...

Страница 11: ...mbient air outlet D Pellet hopper H Bulb thermostat reactivation B Access to combustion chamber and ash drawer E Combustion air inlet I On Off fuse 230V power supply C Upper fumes exhaust F Rear fumes...

Страница 12: ...etails A Access to combustion chamber and ash drawer D Bulb thermostat reactivation G On Off fuse 230V power supply B Pellet hopper E Combustion air inlet H Ambient probe C Ambient air outlet F Rear f...

Страница 13: ...ustion chamber and ash drawer D Combustion air inlet H Ambient probe B Pellet hopper E Rear fumes exhaust I Additional thermostat input Ducting additional thermostat input F Bulb thermostat reactivati...

Страница 14: ...e operation At this point simply set the desired temperature on the thermostat the thermostat will command the operation of the second motor when the temperature has not been reached contact closed th...

Страница 15: ...ration will cause the display to show the following CLOSE HOPPER STOVE DOOR This indication means that you have 60 seconds to close the hatch door and the pellet lid After the 60 seconds during igniti...

Страница 16: ...be cured to obtain a sufficient heat yield THE USE OF POOR QUALITY PELLETS OR ANY OTHER MATERIAL WILL COMPROMISE STOVE FUNCTIONS VOIDING THE WARRANTY AND RELEASING THE MANUFACTURER OF LIABILITY Do no...

Страница 17: ...On off stove hold for 3 seconds 9 Degrees Celsius Fahrenheit 4 Set power 10 Press the button once to enable or disable the chrono 5 Set switch off delay The button allows to set the switch off delay F...

Страница 18: ...gnal receiver Handle the remote control with care When it is not being used place it on the special base supplied The remote control must not be left in a place where it is exposed to direct sunlight...

Страница 19: ...t the contact of the external additional thermostat is closed Open contact the contact of the external additional thermostat is open Icon visible only if SET THERMOSTAT is set to LOW TA WI FI BT STBY...

Страница 20: ...recommended to Ventilate the room well If present remove any majolica or natural stone parts from the top of the product Activate the product at the maximum power and temperature Avoid remaining in t...

Страница 21: ...key 6 Select the language using keys 4 or 5 Press key 6 to confirm and key 1 to scroll back through the menus until the initial page Degrees This menu allows you to set the unit of measure for the te...

Страница 22: ...tion LOW TA hot If the Set Thermostat is LOW TA set under the 7 threshold temperature checking is entrusted to the additional thermostat contact thus bypassing the on board temperature probe If the co...

Страница 23: ...RANGE IF THE FIRST TWO ARE INSUFFICIENT Controls procedure Press key 6 Press key 3 until easy setup appears and confirm by pressing key 6 Use keys 4 5 to set the range Press key 6 to confirm and key...

Страница 24: ...T Set thermostat PRG3 Power prg3 1 5 Set power PRG3 prg4 Start prg4 OFF 00 00 Ignition time PRG4 Stop prg4 OFF 00 00 Switch off time PRG4 Monday Sunday On off Enable disable days PRG4 Set prg4 LOW TA...

Страница 25: ...0 23 00 08 00 16 30 t 22 18 2 1 25 ENGLISH Time slot 1 start 02 00 stop 23 00 power 3 set thermostat 22 C Time slot 2 start 08 00 stop 16 30 power 1 set thermostat 18 C stove operation Time slot Set p...

Страница 26: ...STAND BY function is active ON if the room temperature exceeds the value of the Set Thermostat DELTA T OFF then the stove will switch off after a preset delay displaying STAND BY When the room temper...

Страница 27: ...ground equal to 1 50 m Stove operation with the external thermostat connected in the TA clamp may differ depending on whether or not the STAND BY function is enabled Additional thermostat installation...

Страница 28: ...function allows you to lock the display keys similar to mobile phones With the function active each time a key is pressed the message keys locked will appear To lock the keypad press keys 1 and 5 simu...

Страница 29: ...eaning the ceramic glass Never use abrasive or chemically aggressive detergents for cleaning The ceramic glass must be cleaned when the glass is completely cold To clean the ceramic glass simply use a...

Страница 30: ...rom the burn pot slot ignition plug pipe holder and combustion chamber Clear clean all the holes in the burn pot Re position the burn pot in its slot and push it towards the fire wall NOTE Use a suita...

Страница 31: ...y require subsequent technical assistance Requests for routine maintenance are not covered by the warranty GASKETS pellet hopper lid DOOR ASH DRAWER AND BURN POT INSPECTION OF SMOKE DUCTS The gaskets...

Страница 32: ...r inspections ash drawer and door replace and apply silicone where indicated C Combustion chamber and heat exchanger full cleaning including ignition plug pipe D Hopper complete emptying and cleaning...

Страница 33: ...licone where indicated C Combustion chamber and heat exchanger full cleaning including ignition plug pipe D Hopper complete emptying and cleaning E Check the air intake pipe and check clean the mechan...

Страница 34: ...On indicates the presence of an alarm The alarm can only be reset if the fumes motor has stopped and 15 minutes have passed since the alarm was displayed by pressing key 1 for 3 seconds Fumes motor f...

Страница 35: ...bility to use the product and wrong maintenance by the consumer with respect to what is reported and recommended by the instructions manual of the product which is part of the sales contract this guar...

Страница 36: ...aults in the electrical insulation This can cause electric shocks Installations not complying with the regulations in force as well as incorrect use and failure to comply with the maintenance schedule...

Страница 37: ...37 ENGLISH...

Страница 38: ...38 ENGLISH...

Страница 39: ...39 ENGLISH...

Страница 40: ...o extraflame it www lanordica extraflame com TO FIND THE SERVICE CENTRE NEAREST TO YOU CONTACT YOUR DEALER OR CONSULT THE SITE WWW LANORDICA EXTRAFLAME COM The manufacturer reserves the right to vary...

Отзывы: