3 - 5%

Max 3 mt

10

ENGLISH

ExAMPlEs of coRREcT connEcTion To ThE chiMnEy

In the presence of type B gas appliances with intermittent operation not intended for heating, they must have their own aeration and/or 

ventilation opening. 

The air inlets must meet the following requirements:

 

Š

they must be protected with grids, metal mesh, etc., but without reducing the net useful section;

 

Š

they must be made so as to make the maintenance operations possible;

 

Š

positioned so that they cannot be obstructed;

The clean and non-contaminated air flow can also be obtained from a room adjacent to that of installation (indirect aeration and 

ventilation), as long as the flow takes place freely through permanent openings communicating with the outside.

The adjacent room cannot be used as a garage, or to store combustible material or for any other activity with a fire hazard, bathroom, 

bedroom or common room of the building.

Flue gas eXhaust

The heat generator works in depression and is equipped with an outlet fan for flue gas extraction. There must be a single exhaust system for 

the generator. Using a flue that is shared with other devices is not allowed.

The components of the flue gas exhaust system must be chosen in relation to the type of appliance to be installed in compliance with:

 

Š

UNI/ TS 11278 in the event of metal chimneys, with particular attention to that stated in the specification; 

 

Š

UNI EN 13063-1 and UNI EN 13063-2, UNI EN 1457, UNI EN 1806 in the event of non-metallic chimneys.

 

Š

The length of the horizontal section must be minimal and, in any case, no longer than 3 metres, with a minimum upward slope of 3%

 

Š

There must not be more than 4 direction changes including the one due to the use of the "T" element.

 

Š

A “T” fitting with a condensation collection cap must be provided at the base of the vertical section.

 

Š

If the exhaust is not inserted in an existing flue, a vertical section with a windproof end piece is required (UNI 10683).

 

Š

The vertical duct can be inside or outside the building. If the smoke duct is inserted in an existing flue, it must be certified for solid fuel.

 

Š

If the smoke duct is outside the building, it must always be insulated.

 

Š

The smoke ducts must have at least one airtight inlet for flue gas sampling.

 

Š

All the sections of the flue gas duct must be accessible to inspection.

 

Š

Inspection openings must be provided for cleaning.

 

Š

If the generator has a fume temperature lower than  160°C+ ambient temperature caused by the high yield (contact technicians) it 

MUST be resistant to humidity.

 

Š

A flue system that does not respect the previous points or, in general, that does not comply with the regulations, may cause condensation 

phenomena inside it.

ChIMneY CaP

The chimney caps must meet the following requirements:

 

Š

they must have a useful outlet section no less than double that of the chimney/ducted system on which it is installed;

 

Š

they must be adapted in order to prevent the penetration of rain and snow in the chimney/ducted system;

 

Š

they must be built so that, in the event of winds coming from all directions and from any angle, the expulsion of combustion products 

is in any case ensured;

Protection from rain 

and wind

Condensation-proof 

"T" fitting with 

inspection plug 

Insulated flue

Insulated "T" 

fitting with 

inspection plug

Protection from rain and wind

"T" fitting with 

i n s p e c t i o n 

plug

COnneCtIOn tO the MaIns eleCtrIC suPPlY

The generator is supplied with an electric power cable to be plugged into a 230V 50 Hz socket, possibly with a circuit breaker switch. The 

socket must be easily accessible.

The electrical system must be compliant with standards. The efficiency of the earthing circuit must be checked. Unsuitable earthing of the 

system can cause malfunctioning for which the manufacturer will not be held liable. 

Power supply variations beyond 10% can cause faulty operation of the product.

Содержание 001284000

Страница 1: ...MADE IN ITALY design production DAHIANA DAHIANA plus TEOREMA 004280386 Rev 000 UK pellet stoves USER MANUAL...

Страница 2: ...2 ENGLISH...

Страница 3: ...the chrono 24 Settings 26 Display 26 stand by 26 OPERATION with additional thermostat optional 26 Additional thermostat 27 Additional thermostat installation 27 delta t 27 First Load 27 reset 27 Addit...

Страница 4: ...OIRE Avant de bouger le po le faire attention lever les c ramiques indiqu es pour viter des d g ts OBVEZNA POZORNOST Prije pomicanja pe i uklonite ozna ene plo ice kako biste izbjegli o te enja VORSIC...

Страница 5: ...TEOREMA 5 ENGLISH...

Страница 6: ...well as the instructions contained in this manual The Manufacturer cannot be held responsible for the failure to comply with such precautions After removing the packaging ensure that the content is in...

Страница 7: ...ply cable so that it does not come into contact with hot parts ofthe appliance The power supply plug must be accessible after installation Do not close or reducethe dimensions ofthe airingvents in the...

Страница 8: ...uid is used the latter could penetrate inside the crackles highlighting them SINCE THE PRODUCT CAN TURN ON AUTOMATICALLY THANKS TO THE TIMER OR REMOTELY USING THE DEDICATED APPLICATIONS IT IS STRICTLY...

Страница 9: ...mestichotwaterproductionandinadjacentandcommunicating rooms 3 where the depression measured in situ between the external and internal environment is greater than 4 Pa N B Watertight appliances can als...

Страница 10: ...tion If the exhaust is not inserted in an existing flue a vertical section with a windproof end piece is required UNI 10683 The vertical duct can be inside or outside the building If the smoke duct is...

Страница 11: ...mbient air outlet D Pellet hopper H Bulb thermostat reactivation B Access to combustion chamber and ash drawer E Combustion air inlet I On Off fuse 230V power supply C Upper fumes exhaust F Rear fumes...

Страница 12: ...etails A Access to combustion chamber and ash drawer D Bulb thermostat reactivation G On Off fuse 230V power supply B Pellet hopper E Combustion air inlet H Ambient probe C Ambient air outlet F Rear f...

Страница 13: ...ustion chamber and ash drawer D Combustion air inlet H Ambient probe B Pellet hopper E Rear fumes exhaust I Additional thermostat input Ducting additional thermostat input F Bulb thermostat reactivati...

Страница 14: ...e operation At this point simply set the desired temperature on the thermostat the thermostat will command the operation of the second motor when the temperature has not been reached contact closed th...

Страница 15: ...ration will cause the display to show the following CLOSE HOPPER STOVE DOOR This indication means that you have 60 seconds to close the hatch door and the pellet lid After the 60 seconds during igniti...

Страница 16: ...be cured to obtain a sufficient heat yield THE USE OF POOR QUALITY PELLETS OR ANY OTHER MATERIAL WILL COMPROMISE STOVE FUNCTIONS VOIDING THE WARRANTY AND RELEASING THE MANUFACTURER OF LIABILITY Do no...

Страница 17: ...On off stove hold for 3 seconds 9 Degrees Celsius Fahrenheit 4 Set power 10 Press the button once to enable or disable the chrono 5 Set switch off delay The button allows to set the switch off delay F...

Страница 18: ...gnal receiver Handle the remote control with care When it is not being used place it on the special base supplied The remote control must not be left in a place where it is exposed to direct sunlight...

Страница 19: ...t the contact of the external additional thermostat is closed Open contact the contact of the external additional thermostat is open Icon visible only if SET THERMOSTAT is set to LOW TA WI FI BT STBY...

Страница 20: ...recommended to Ventilate the room well If present remove any majolica or natural stone parts from the top of the product Activate the product at the maximum power and temperature Avoid remaining in t...

Страница 21: ...key 6 Select the language using keys 4 or 5 Press key 6 to confirm and key 1 to scroll back through the menus until the initial page Degrees This menu allows you to set the unit of measure for the te...

Страница 22: ...tion LOW TA hot If the Set Thermostat is LOW TA set under the 7 threshold temperature checking is entrusted to the additional thermostat contact thus bypassing the on board temperature probe If the co...

Страница 23: ...RANGE IF THE FIRST TWO ARE INSUFFICIENT Controls procedure Press key 6 Press key 3 until easy setup appears and confirm by pressing key 6 Use keys 4 5 to set the range Press key 6 to confirm and key...

Страница 24: ...T Set thermostat PRG3 Power prg3 1 5 Set power PRG3 prg4 Start prg4 OFF 00 00 Ignition time PRG4 Stop prg4 OFF 00 00 Switch off time PRG4 Monday Sunday On off Enable disable days PRG4 Set prg4 LOW TA...

Страница 25: ...0 23 00 08 00 16 30 t 22 18 2 1 25 ENGLISH Time slot 1 start 02 00 stop 23 00 power 3 set thermostat 22 C Time slot 2 start 08 00 stop 16 30 power 1 set thermostat 18 C stove operation Time slot Set p...

Страница 26: ...STAND BY function is active ON if the room temperature exceeds the value of the Set Thermostat DELTA T OFF then the stove will switch off after a preset delay displaying STAND BY When the room temper...

Страница 27: ...ground equal to 1 50 m Stove operation with the external thermostat connected in the TA clamp may differ depending on whether or not the STAND BY function is enabled Additional thermostat installation...

Страница 28: ...function allows you to lock the display keys similar to mobile phones With the function active each time a key is pressed the message keys locked will appear To lock the keypad press keys 1 and 5 simu...

Страница 29: ...eaning the ceramic glass Never use abrasive or chemically aggressive detergents for cleaning The ceramic glass must be cleaned when the glass is completely cold To clean the ceramic glass simply use a...

Страница 30: ...rom the burn pot slot ignition plug pipe holder and combustion chamber Clear clean all the holes in the burn pot Re position the burn pot in its slot and push it towards the fire wall NOTE Use a suita...

Страница 31: ...y require subsequent technical assistance Requests for routine maintenance are not covered by the warranty GASKETS pellet hopper lid DOOR ASH DRAWER AND BURN POT INSPECTION OF SMOKE DUCTS The gaskets...

Страница 32: ...r inspections ash drawer and door replace and apply silicone where indicated C Combustion chamber and heat exchanger full cleaning including ignition plug pipe D Hopper complete emptying and cleaning...

Страница 33: ...licone where indicated C Combustion chamber and heat exchanger full cleaning including ignition plug pipe D Hopper complete emptying and cleaning E Check the air intake pipe and check clean the mechan...

Страница 34: ...On indicates the presence of an alarm The alarm can only be reset if the fumes motor has stopped and 15 minutes have passed since the alarm was displayed by pressing key 1 for 3 seconds Fumes motor f...

Страница 35: ...bility to use the product and wrong maintenance by the consumer with respect to what is reported and recommended by the instructions manual of the product which is part of the sales contract this guar...

Страница 36: ...aults in the electrical insulation This can cause electric shocks Installations not complying with the regulations in force as well as incorrect use and failure to comply with the maintenance schedule...

Страница 37: ...37 ENGLISH...

Страница 38: ...38 ENGLISH...

Страница 39: ...39 ENGLISH...

Страница 40: ...o extraflame it www lanordica extraflame com TO FIND THE SERVICE CENTRE NEAREST TO YOU CONTACT YOUR DEALER OR CONSULT THE SITE WWW LANORDICA EXTRAFLAME COM The manufacturer reserves the right to vary...

Отзывы: