![Express SERIES](http://html.mh-extra.com/html/express/series-h/series-h_installation-operation-and-maintenance-manual_2452458047.webp)
47
REMOVING THE CYLINDER:
Unit Serial #: _____________________ No. of Humidi
fi
ers: ______________________________________________
Model #: _________________________________ Voltage: _______ V/ ___ Ph.
Steam Output: _______ lb./hr.
Customer/Job: ___________________________ Address: ______________________________________________
1. Completely drain the existing cylinder (flip On/Off rocker switch to “Drain).
2. Turn off water supply at the shut-off valve.
3. Turn the humidifier off (flip On/Off rocker switch to “OFF”).
4. Turn main power “Off” at the external shut-off.
5. Remove all terminal plugs from the cylinder.
6. Loosen the steam hose clamp and remove the steam hose from the cylinder.
7. (Using a flat head screwdriver) Remove the cylinder strap, keeping the cylinder in place.
8. A and B sized cylinders are threaded. Unscrew the cylinder (counter clockwise) and lift up and out.
9. C sized cylinders are seated into the brass plumbing with an O-ring. Just lift up and out.
• Disconnect power (external shut-off) before servicing.
• CAUTION: cylinder may be
hot
.
• Compartments contain high voltage wiring.
WARNING
!
Fill Cup
Steam Hose
Electrode Connector
On-Off-Drain Switch
LCD
Door Interlock Switch
Circuit Breakers
Cylinder
Cylinder Fitting
Drain Valve
Lock