10
MANUGENESMARTxx - Version 2.01
© 2018 EXOR International S.p.A. - Subject to change without notice
3 Technical Specifications
Immunity to conducted disturbances
inducted by radiofrequency field
0.15 ÷ 80 MHz, 10V
EN 61000-4-6
Voltage dips, short interruptions and
voltage variations immunity test
Port: AC mains; Level:
100% duration: 1 cycle and 250 cycles (50Hz);
40% duration: 10 cycles (50Hz);
70% duration: 25 cycles (50Hz);
Phase: 0°-180°
Test executed on the 230Vac side of the EXOR International S.p.A. Power Supply
EN 61000-4-11
Durability information
Backlight service life
20000 Hrs. or more
(LED type)
(Time of continuos operation until the brightness of the
backlight reaches 50% of the rated value when the
sorrounding air temperature is 25°C) - see Note 1
Front foil
10 years if the surrounding air temperature is 25°C
(without direct exposure to
sunlight or UV)
UV Resistance
Indoor applications: After 300 hours cycled humidity in
QUV accelerated weathering, some yellowing and
brittleness may be present.
Solvent resistance
Contact for 1/2 hour at 21°C, No visible effect: Acetone, Butyl Cellosolve, Cyclohexanone, Ethyl Acetate,
Hexane, Isopropyl Alcohol, MEK, Methylene Chloride, Toluene, Xylene
Contact for 24 hours at 49°C, No visible effect: Coffee, Ketchup, Lemon Juice, Mustard (slight yellow
stain), Tea, Tomato juice.
Touchscreen reliability
> 1 milion operations
Note 1: Extended use in environments where the surrounding air temperature is 40°C or higher may
degrade backlight quality/reliability/durability.
Electromagnetic Compatibility (EMC)
Radiated disturbance test
Class A
EN 55011
Electrostatic discharge immunity test
8 kV (air electrostatic discharge)
EN 61000-4-2
4 kV (contact electrostatic discharge)
Radiated, radio-frequency,
80 MHz ÷ 1 GHz, 10V/m
EN 61000-4-3
electromagnetic field immunity test
1,4 GHz ÷ 2 GHz, 3 V/m
2 GHz ÷ 2.7 GHz, 1 V/m
Burst immunity test
± 2 KV dc power port
EN 61000-4-4
± 1 KV signal line
Surge immunity test
± 0,5 KV dc power port (line to earth)
EN 61000-4-5
± 0,5 KV dc power port (line to line)
± 1 KV signal line (line to earth)