9
MANUGENESMARTxx - Version 2.01
© 2018 EXOR International S.p.A. - Subject to change without notice
3 Technical Specifications
Touchscreen technology
Resistive
RTC backup
Supercapacitor
Fuse
Automatic
Serial Port
RS-232, RS-485, RS-422 software configurable
Recipe memory
Flash
Hardware clock
Clock/Calendar with supercapacitor back-up
Accuracy RTC (at 25°C)
<100ppm
Environmental conditions
Operating temperature (surrounding
0 ÷ +50°C
EN 60068-2-14
air temperature)
Storage temperature
-20 ÷ +70°C
EN 60068-2-14
Operating and storage humidity
5 ÷ 85 % RH not-condensing
EN 60068-2-30
Vibrations
5 ÷ 9 Hz, 7 mm p-p
EN 60068-2-6
9 ÷ 150 Hz, 1 g
Shock
± 50 g, 11 ms, 3 pulses per axis
EN 60068-2-27
Protection class
IP66 front panel *
EN60529
Pollution degree environment
2
* The front face of the EXOR unit, installed in a solid panel, has been tested using conditions equivalent to the standards
shown in the “Environmental conditions”. Even though the level of resistance EXOR unit is equivalent to these stan
-
dards, oils that should have no effect on the eSMART can possibly harm the unit. This can occur in areas where either
vaporized oils are present, or where low viscosity cutting oil are allowed to adhere to the unit for long periods of time. If
the front face protection sheet on the eSMART becomes peeled off, these conditions can lead to the ingress of oil into
the unit and separate protection measures are suggested.
If the installation gasket is used for a long period of time, or if the unit and its gasket are removed from the panel, the
original level of the protection cannot be guaranteed.