RME2-AI-IA3 Analog Variables Acquisition Module – User’s Manual
Exemys
www.exemys.com
Rev. 1
14
1.3.2.
Alarms
In this sub-menu, user has available the alarms configuration for inputs, RME2-AI-IA3 has
two alarm thresholds for each input, one for a low value and one for a high value.
The alarm values are used to change the status text on the monitoring screen and to send
SNMP traps if configured.
The configured values are compared with the scaled value of each input.
If we need an alarm when the value of input number 4 is out of the range of 10°C to 400 °C
(decimals=0), we must set the parameters "
Low Value
" to 10 and "
High Value
" to 400.