Input impedance
2
KΩ
Count frequency
0
1
Khz
We now show two examples of how to connect an input, directly from the same source feeding the
equipment and from an external source where we can clearly see that they must share the common
Terminal.
Digital outputs
Digital outputs are of the open collector type. The load to be connected must be fed with an external
power supply and they have to share the GND Terminal with the equipment power supply. If necessary,
the same power supply used to feed the equipment can be used.
The output type is NPN Sourcing type (Open collector).
GRD3621-XF-3G / GRD3625-XF-3G and GRD3621-MQ-3G / GRD3625-MQ-3G
Parameter
Maximum
Units
Withstand voltage
50
Vdc
Current
200
mA
GRD3534-XF-3G and GRD3534-MQ-3G
Parameter
Maximum
Units
Withstand voltage
45
Vdc
Current
50
mA
GRD-MQ User Manual
Features of power supply and inputs/outputs
29 / 84