RME1-TC User’s Manual - Thermocouple Acquisition Module
Exemys
Table 5 - ModBus Registers
MODBUS TCP Register
Descrition
40.001 up to 40.008
Temperature value (Inputs value in centigrade degrees multiplied by 10).
40.009 up to 40.016
Status (shows the alarm status of each input)
0: Normal
m
1: Low alar
2: High alarm
40.101
on
Firmware
versi
40.102 Hardware
version
40.103 up to 40.105
Serial number
40.201 up to 40.208
Type of Thermocouple
1= Thermocouple E
2= Thermocouple J
3= Thermocouple K
4= Thermocouple N
5= Thermocouple R
6= Thermocouple S
7= Thermocouple T
40.249 up to 40.256
Alarms enable of each one of the inputs
0: Both alarms disabled
1: Low alarm enabled
2: High alarm enabled
3: Both alarms enabled
40.257 up to 40.264
Low alarm set point variable (value between 32.767 and 32.767)
40.265 up to 40.272
High alarm set point (value between 32.767 and 32.767)
The registers with gray background can be modified with Modbus TCP. All the other are only for
4.2 CVS/XML mode operation
reading.
4.2.1 CSV
to make an automatic data acquisition through other query method under HTTP, the
he available information in these pages is as follows:
•
temp.csv: Temperature value in centigrade multiplied by 10.
If you want
RME1-TC has 3 web pages where you can get, in plain text format delimited by commas, its
analog inputs status.
T
www.exemys.com Rev.
1
Page
24