Operating instructions 

 

Trip wire switch - XY2W series

 

 
 
 
 

XY2004A12-07A    01/12/2017

 

 

 14/16 

ENG 

  Position the cam by rotating it 

 

  Reposition the index by tensioning the 

cable according to the cam selected 

  Set the device 

 

  Trip the switch, reset and repeat the 

operation 

  Check the position of the index and 

reposition, if necessary 

  Replace the cover 

  Device's electrical connection on the 

screw clamp terminals: min. 1 x 0.5 mm², 
max. 1 x 2.5 mm² or 2 x 1.5 mm² 

  The viewing port allows you to check at 

any time that cable tension is correct 

 

Particular case :  

Where the device is installed when the ambient temperature is extreme 

(a) OBJECTIVE: this setting makes it possible to anticipate a 
drop in temperature during operation 

(b) OBJECTIVE: this setting makes it possible to anticipate a rise in 
temperature during operation (the diagrams show the device with an 
RH cable anchor point. Reverse the pushbutton's position for 
devices with an LH cable anchor point). 

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание XY2W Series

Страница 1: ...Volute BP 20708 16430 Champniers France Tel 33 0 5 45 93 01 10 Fax 33 0 5 45 93 01 15 E mail sales solution ex tech no www ex tech no MODE D EMPLOI OPERATING INSTRUCTIONS INTERRUPTEUR C BLE MOD LES X...

Страница 2: ...signal tique du produit 2 Fabricant Ex tech Solution Formerly Technor Atex 22 impasse de la Volute Z A les Montagnes B P 20708 16430 Champniers France Tel 33 5 45 93 01 10 Fax 33 5 45 93 01 15 E mail...

Страница 3: ...Dur e de vie m canique 1 millions de man uvre 6 2 Donn es techniques R f rence produit Gaz Dust Fonctionnement Contact R armement XY2WCE1A250 Actionnement droite 1 NO 1 NF Par Bouton Poussoir XY2WCE1...

Страница 4: ...du personnel qualifi comp tent et habilit Une utilisation d fectueuse ou anormale ainsi que le non respect des consignes du pr sent document excluent toute clause de garantie et ne sauraient engager n...

Страница 5: ...ons ont t s effectu s correctement V rifiez que l quipement ne comporte aucun corps tranger et qu aucune pi ce ne soit endommag e Serrez les presse toupes et le bouchons obturateurs 10 Entretien et ma...

Страница 6: ...es supports guident le c ble 3 Monter le ressort d extr mit recommand fixer le c ble dans le ressort 4 D poser le couvercle 5 Tendre le c ble jusqu l index en utilisant le ridoir ou le tendeur incorpo...

Страница 7: ...pareil sur bornes vis triers mini 1 x 0 5 mm maxi 1 x 2 5 mm ou 2 x 1 5 mm La fen tre de visualisation permet tout moment de v rifier la tension correcte du c ble Cas particulier L appareil est instal...

Страница 8: ...Mode d emploi Interrupteur c ble XY2W XY2004A12 07A 01 12 2017 8 16 FR...

Страница 9: ...plate of the product 2 Manufacturer Ex tech Solution Formerly Technor Atex 22 impasse de la Volute Z A les Montagnes B P 20708 16430 Champniers France Tel 33 5 45 93 01 10 Fax 33 5 45 93 01 15 E mail...

Страница 10: ...x 1 5 mm2 Mechanical endurance 1 millions operations 6 2 Additional technical data Reference Gaz Dust product Operation Contact Reset XY2WCE1A250 Actuation on the right 1 NO 1 NF By pushbutton XY2WCE...

Страница 11: ...non observance of the instructions of this document exclude any clause of guarantee and do not engage our responsibility According to the standard IEC 60079 31 it is prohibited to operate the control...

Страница 12: ...nections have been performed properly The device may include any foreign body and no part is damaged The cable gland must be tightened 10 Maintenance The maintenance and repairs works on devices must...

Страница 13: ...the cable supports to rigid components thesupports guide the cable 3 Fit the recommended end spring and fix the cable in the spring 4 Remove the cover 5 Tension the cable up to the index using the tu...

Страница 14: ...on the screw clamp terminals min 1 x 0 5 mm max 1 x 2 5 mm or 2 x 1 5 mm The viewing port allows you to check at any time that cable tension is correct Particular case Where the device is installed wh...

Страница 15: ...Operating instructions Trip wire switch XY2W series XY2004A12 07A 01 12 2017 15 16 ENG...

Страница 16: ...O Box 256 forus 4066 Stavanger Norway Tel 47 51 63 00 70 Fax 47 51 63 00 72 E mail post ex tech no www ex tech no Ex tech Signalling 355 rue de la G noise Z A les Montagnes 16430 Champniers France Tel...

Отзывы: