Operating instructions 

 

Trip wire switch - XY2W series

 

 
 
 
 

XY2004A12-07A    01/12/2017

 

 

 10/16 

ENG 

6.  Technical data 

 
The trip wire switch XY2W described in this manual are certified II 2 GD and can operate into the classified 
zones 1 and 2 for gases or 21 and 22 for dusts. 

 

6.1. Features 
 

Certificate Europe (ATEX) 

INERIS 04ATEX0040 

Normes appliquées  

 

EN / IEC 60079-0 
EN / IEC 60079-1 
EN / IEC 60079-7 
EN / IEC 60079-31 

Ex-codes 

  0080 

 

II 2 G D

 

Ex d e IIC T6 Gb 
Ex tb IIIC T85°C Db 

Temperature range 

Ambient : -

20°C … +60°C 

Storage : -

40°C … +70°C 

IP rating 

IP 65  according to IEC 60529 

Material 

Zinc alloy 

Rated operational 
specification of the contact 
for DUST (XY2W…EX) 

Ue = 240V, Ie = 6A, Ui = 400V 
AC-15, A300 

– Ue = 240V,  Ie = 3A 

DC-13, Q300 

– Ue = 250V, Ie = 0,27A 

Rated operational 
specification of the contact 
for GAZ (XY2W…) 

Ue = 250V, Ie = 3A, P = 1W 
 

Type of contacts 

Snap-action 

– See table below 

Short-circuit protection 

By fuse 6 A gG outside Atex area 

Cable entry 

1 cable entry M20 for cable 7 to 12 mm, 1 cable entry with 2 blind plug 

Electrical connection 

Screw terminal, conductor of 1 x 2,5 mm

2

 or 2 x 1,5 mm

2

 

Mechanical endurance 

1 millions operations 

 

6.2. Additional technical data 
 

Reference 

Gaz & Dust 

product  Operation 

Contact 

Reset 

XY2WCE1A250 

Actuation on the right 

1 NO + 1 NF 

By pushbutton 

XY2WCE1A270 

Actuation on the right 

1 NO + 1 NO 

By pushbutton 

XY2WCE1A450 

Actuation on the right 

1 NO + 1 NF 

By pushbutton with key 421 

XY2WCE1A470 

Actuation on the right 

1 NO + 1 NO 

By pushbutton with key 421 

XY2WCE2A250 

Actuation on the left 

1 NO + 1 NF 

By pushbutton 

XY2WCE2A270 

Actuation on the left

 

1 NO + 1 NO 

By pushbutton 

XY2WCE2A450 

Actuation on the left

 

1 NO + 1 NF 

By pushbutton with key 421 

XY2WCE2A470 

Actuation on the left

 

1 NO + 1 NO 

By pushbutton with key 421 

 

Reference 

Dust 

product 

Operation 

Contact 

Reset 

XY2WCE1A250EX 

Actuation on the right 

1 NO + 1 NF 

By pushbutton 

XY2WCE1A270EX 

Actuation on the right 

1 NO + 1 NO 

By pushbutton 

XY2WCE1A450EX 

Actuation on the right 

1 NO + 1 NF 

By pushbutton with key 421 

XY2WCE1A470EX 

Actuation on the right 

1 NO + 1 NO 

By pushbutton with key 421 

XY2WCE2A250EX 

Actuation on the left 

1 NO + 1 NF 

By pushbutton 

XY2WCE2A270EX 

Actuation on the left

 

1 NO + 1 NO 

By pushbutton 

XY2WCE2A450EX 

Actuation on the left

 

1 NO + 1 NF 

By pushbutton with key 421 

XY2WCE2A470EX 

Actuation on the left

 

1 NO + 1 NO 

By pushbutton with key 421 

 
 

 

Содержание XY2W Series

Страница 1: ...Volute BP 20708 16430 Champniers France Tel 33 0 5 45 93 01 10 Fax 33 0 5 45 93 01 15 E mail sales solution ex tech no www ex tech no MODE D EMPLOI OPERATING INSTRUCTIONS INTERRUPTEUR C BLE MOD LES X...

Страница 2: ...signal tique du produit 2 Fabricant Ex tech Solution Formerly Technor Atex 22 impasse de la Volute Z A les Montagnes B P 20708 16430 Champniers France Tel 33 5 45 93 01 10 Fax 33 5 45 93 01 15 E mail...

Страница 3: ...Dur e de vie m canique 1 millions de man uvre 6 2 Donn es techniques R f rence produit Gaz Dust Fonctionnement Contact R armement XY2WCE1A250 Actionnement droite 1 NO 1 NF Par Bouton Poussoir XY2WCE1...

Страница 4: ...du personnel qualifi comp tent et habilit Une utilisation d fectueuse ou anormale ainsi que le non respect des consignes du pr sent document excluent toute clause de garantie et ne sauraient engager n...

Страница 5: ...ons ont t s effectu s correctement V rifiez que l quipement ne comporte aucun corps tranger et qu aucune pi ce ne soit endommag e Serrez les presse toupes et le bouchons obturateurs 10 Entretien et ma...

Страница 6: ...es supports guident le c ble 3 Monter le ressort d extr mit recommand fixer le c ble dans le ressort 4 D poser le couvercle 5 Tendre le c ble jusqu l index en utilisant le ridoir ou le tendeur incorpo...

Страница 7: ...pareil sur bornes vis triers mini 1 x 0 5 mm maxi 1 x 2 5 mm ou 2 x 1 5 mm La fen tre de visualisation permet tout moment de v rifier la tension correcte du c ble Cas particulier L appareil est instal...

Страница 8: ...Mode d emploi Interrupteur c ble XY2W XY2004A12 07A 01 12 2017 8 16 FR...

Страница 9: ...plate of the product 2 Manufacturer Ex tech Solution Formerly Technor Atex 22 impasse de la Volute Z A les Montagnes B P 20708 16430 Champniers France Tel 33 5 45 93 01 10 Fax 33 5 45 93 01 15 E mail...

Страница 10: ...x 1 5 mm2 Mechanical endurance 1 millions operations 6 2 Additional technical data Reference Gaz Dust product Operation Contact Reset XY2WCE1A250 Actuation on the right 1 NO 1 NF By pushbutton XY2WCE...

Страница 11: ...non observance of the instructions of this document exclude any clause of guarantee and do not engage our responsibility According to the standard IEC 60079 31 it is prohibited to operate the control...

Страница 12: ...nections have been performed properly The device may include any foreign body and no part is damaged The cable gland must be tightened 10 Maintenance The maintenance and repairs works on devices must...

Страница 13: ...the cable supports to rigid components thesupports guide the cable 3 Fit the recommended end spring and fix the cable in the spring 4 Remove the cover 5 Tension the cable up to the index using the tu...

Страница 14: ...on the screw clamp terminals min 1 x 0 5 mm max 1 x 2 5 mm or 2 x 1 5 mm The viewing port allows you to check at any time that cable tension is correct Particular case Where the device is installed wh...

Страница 15: ...Operating instructions Trip wire switch XY2W series XY2004A12 07A 01 12 2017 15 16 ENG...

Страница 16: ...O Box 256 forus 4066 Stavanger Norway Tel 47 51 63 00 70 Fax 47 51 63 00 72 E mail post ex tech no www ex tech no Ex tech Signalling 355 rue de la G noise Z A les Montagnes 16430 Champniers France Tel...

Отзывы: