50-200 EVAPORATOR FOR CHLORINE
WT.050.200.001.UA.IM.0814
7
EVOQUA
W3T98237
h. Unbolt the evaporator from the wooden base. Lift and lower the evapora-
tor onto a concrete mounting pad prepared according to the mounting
details in Dwg. 50.200.100.010. Bolt the evaporator to the pad.
f. Replace top cover and pipe trim.
WARNING: TO AVOID SEVERE PERSONAL INJURY OR EQUIPMENT
DAMAGE, BOLT THE EVAPORATOR SECURELY TO THE CONCRETE PAD.
2.3
Piping
2.3.1
Chlorine Gas and Liquid Piping
WARNING: ALL TWO-BOLT AMMONIA AND RUPTURE DISC UNIONS ARE
ONLY LIGHTLY TIGHTENED FOR SHIPPING. TO AVOID SEVERE PERSONAL
INJURY FROM A CHLORINE LEAK, FIRMLY TIGHTEN ALL UNIONS AFTER
PIPING IS INSTALLED.
NOTE: Piping for chlorine should conform to Chlorine Institute recommenda-
tions.
An ammonia-type union is furnished to accommodate the one-inch chlorine
gas outlet (discharge) pipe. The chlorine gas outlet pipe and union extends
upward from the gray insulation ring at the top of the evaporator. The gas
pressure relief system and a vacuum regulator-check unit (or gas pressure
reducing valve) must be installed in this line. Refer to Dwg. 50.200.110.010 for
proper installation. The vacuum regulator-check unit is electrically operated.
The gas pressure reducing valve can be pilot-operated by air or water or can
be electrically operated. Separate instructions are furnished with either valve.
WARNING: TO AVOID POSSIBLE SEVERE PERSONAL INJURY OR EQUIPMENT
DAMAGE, THE GAS LINE TO THE REGULATING VALVE MUST BE SHORT,
WITH A SLIGHT DOWN-GRADE TOWARDS THE EVAPORATOR, ALLOW-
ING ANY RELIQUIFIED CHLORINE TO DRAIN BACK TO THE EVAPORATOR.
THIS WILL PREVENT ANY RELIQUIFIED CHLORINE FROM REACHING AND
DAMAGING EQUIPMENT DOWNSTREAM OF THE REGULATING VALVE.
There are two points at which chlorine liquid can be brought into the evapora-
tor. The top connection may be used as a convenience from a piping standpoint
when there is only a single evaporator being used. The bottom connection is
required when manifolding several evaporators for high capacity. For single
evaporators, the bottom connection provides an alternate inlet connection.
The bottom connection is also used as a drain when cleaning the evaporator
in place. Ammonia unions are furnished at both liquid inlet points.
!
!
!
Содержание Wallace&Tiernan 50-200 Series
Страница 1: ...Series 50 200 Evaporator For Chlorine BOOK NO WT 050 200 001 UA IM 0814 W3T198237 ...
Страница 2: ...SERIES 50 200 EVAPORATOR FOR CHLORINE BOOK NO WT 050 200 001 UA IM 0814 W3T198237 ...
Страница 15: ...WT 050 200 001 UA IM 0814 50 200 EVAPORATOR FOR CHLORINE 4 EVOQUA W3T98237 ...
Страница 75: ...WT 050 200 001 UA IM 0814 50 200 EVAPORATOR FOR CHLORINE 64 EVOQUA W3T98237 ...
Страница 95: ...CHLORINE HANDLING MANUAL Cl2 BOOK NO WT 025 000 001 UA IM 0614 W3T98244 ...