50-200 EVAPORATOR FOR CHLORINE
WT.050.200.001.UA.IM.0814
17
EVOQUA
W3T98237
SERIES 50-200 EVAPORATOR - TYPICAL INSTALLATION
50.200.110.010B
ISSUE 3 8-14
WARNING:
TO AVOID PERSONAL INJURY FROM ACCIDENTAL EXPOSURE TO HIgH VOLTAgE, SUITABLY gROUND THE
EVAPORATOR TO EARTH BEFORE START-UP.
THE RELIEF LINE MUST TERMINATE IN AN AREA WHERE gAS FUMES CANNOT CAUSE DAMAgE OR INJURY
TO PERSONNEL. DO NOT TERMINATE THE RELIEF LINE AT A LOCATION ROUTINELY USED BY PERSONNEL
SUCH AS WORK AREAS OR PATHWAYS NOR NEAR WINDOWS OR VENTILATION SYSTEM INTAKES. IF AN
AREA MEETINg THESE REQUIREMENTS IS NOT AVAILABLE, REFER TO THE CHLORINE INSTITUTE, INC.
OR THE COMPRESSED gAS ASSOCIATION, INC. FOR ALTERNATE METHOD OF RELIEF DISPOSAL.
NOTES:
SURFACE TEMPERATURE MAY REACH 212
°
F.
A
ACCESSORY ITEM FURNISHED ONLY IF SPECIFICALLY LISTED IN QUOTATION.
gAS PRESSURE REDUCINg VALVE CAN BE FURNISHED BY EVOQUA WATER TECHNOLOgIES FOR PRESSURE
SUPPLY ARRANgEMENTS.
USE WHEN TWO OR MORE EVAPORATORS ARE MANIFOLDED. FOR ONE EVAPORATOR, CONNECTION MAY BE
AN ALTERNATE TO TOP INLET.
THE SYSTEM MUST BE INSTALLED WITH THE RELIEF VALVE IN A VERTICAL POSITION AND WITH THE CLOSED
END OF THE EXPANSION TANK FACINg UP.
X
ALL PIPINg AND FITTINgS TO BE SUPPLIED BY THE CUSTOMER. USE SCHEDULE 80 SEAMLESS CARBON STEEL
PIPE WITH 3000 LB. FORgED STEEL FITTINgS.
FOR REMOVAL OF CYLINDER, MINIMUM CEILINg HEIgHT MUST BE 10'-0" PLUS LIFTINg gEAR. FOR REMOVAL
OF CABINET, ALLOW 15" MINIMUM SIDE CLEARANCE.
Содержание Wallace&Tiernan 50-200 Series
Страница 1: ...Series 50 200 Evaporator For Chlorine BOOK NO WT 050 200 001 UA IM 0814 W3T198237 ...
Страница 2: ...SERIES 50 200 EVAPORATOR FOR CHLORINE BOOK NO WT 050 200 001 UA IM 0814 W3T198237 ...
Страница 15: ...WT 050 200 001 UA IM 0814 50 200 EVAPORATOR FOR CHLORINE 4 EVOQUA W3T98237 ...
Страница 75: ...WT 050 200 001 UA IM 0814 50 200 EVAPORATOR FOR CHLORINE 64 EVOQUA W3T98237 ...
Страница 95: ...CHLORINE HANDLING MANUAL Cl2 BOOK NO WT 025 000 001 UA IM 0614 W3T98244 ...