WT.050.200.001.UA.IM.0814
50-200 EVAPORATOR FOR CHLORINE
34
EVOQUA
W3T98237
4.1
General
WARNING: TO AVOID POSSIBLE SEVERE PERSONAL INJURY FROM EXPO-
SURE TO CHLORINE, REVIEW THE CHLORINE HANDLING MANUAL BEFORE
BREAKING ANY CHLORINE CONNECTIONS.
Piping leaks are usually caused by either improperly assembling pipe joints or
reusing gaskets.
WARNING: LINE VOLTAGE IS PRESENT INSIDE THE CONTROL BOX. TO
AVOID POSSIBLE SEVERE PERSONAL INJURY FROM ELECTRICAL SHOCK,
DEAC TIVATE EXTERNAL POWER SOURCE(S) BEFORE OPENING THE
CONTROL BOX.
WARNING: TO REDUCE THE POSSIBILITY OF CHLORINE LEAKAGE, AS-
SEMBLE ALL THREADED JOINTS IN ACCORDANCE WITH THE CHLORINE
HANDLING MANUAL. DO NOT REUSE GASKETS; ALWAYS USE NEW
GASKETS.
WARNING: TO AVOID SEVERE PERSONAL INJURY, WHEN ANY PIPING
CONNECTION IS BROKEN, EVEN FOR A SHORT PERIOD OF TIME, PLUG
THE RESULTANT OPENING IMMEDIATELY TO PREVENT THE ENTRANCE
OF MOISTURE. MOISTURE, INCLUDING ATMOSPHERIC, WHEN COM-
BINED WITH CHLORINE, IS HIGHLY CORROSIVE TO PIPING. WHEN
CHANGING CHLORINE SUPPLY CONTAINERS, PREVENT THE ENTRANCE
OF MOISTURE INTO THE CHLORINE PIPING BY PLUGGING OPEN ENDS
OR USING AUX ILIARY TON CONTAINER VALVES.
4.1.1
Inspection
When performing preventive maintenance or servicing of the evaporator,
perform the following inspection routine:
a. Check for any physical damage to removed parts (chipped, cracked, dam-
aged threads; excessive corrosion). Replace all damaged components.
b. Discard and replace all removed gaskets, seals, and O-rings.
NOTE: Refer to Section 6 for a list of approved Evoqua Water Technologies
spare parts.
4.2
Temperature Control and Indication
The tank water temperature is sensed by an electronic temperature probe im-
mersed in the water bath. The probe is mounted in the probe housing block
located on the top of the hot water tank. The electronic signal from the probe
is processed by the printed circuit board to control the operation of the heat
!
!
!
!
Содержание Wallace&Tiernan 50-200 Series
Страница 1: ...Series 50 200 Evaporator For Chlorine BOOK NO WT 050 200 001 UA IM 0814 W3T198237 ...
Страница 2: ...SERIES 50 200 EVAPORATOR FOR CHLORINE BOOK NO WT 050 200 001 UA IM 0814 W3T198237 ...
Страница 15: ...WT 050 200 001 UA IM 0814 50 200 EVAPORATOR FOR CHLORINE 4 EVOQUA W3T98237 ...
Страница 75: ...WT 050 200 001 UA IM 0814 50 200 EVAPORATOR FOR CHLORINE 64 EVOQUA W3T98237 ...
Страница 95: ...CHLORINE HANDLING MANUAL Cl2 BOOK NO WT 025 000 001 UA IM 0614 W3T98244 ...