EVOQUA
W3T98237
WT.050.200.001.UA.IM.0814
50-200 EVAPORATOR FOR CHLORINE
SP-2
VERY IMPORTANT SAFETY PRECAUTIONS (CONT’D)
TO AVOID RUPTURE OF THE SUPPLY CONTAINER, CAUSING POSSIBLE SEVERE PERSONAL INJURY, CLOSE THE
SUPPLY VALVE AND USE THE CHLORINATOR OR GAS DISPOSAL SYSTEM TO COMPLETELY EVACUATE THE EVAPO-
RATOR CYLINDER AND ITS CONNECTING PIPELINES.
ALL TWO-BOLT AMMONIA AND RUPTURE DISC UNIONS ARE ONLY LIGHTLY TIGHTENED FOR SHIPPING. TO AVOID
SEVERE PERSONAL INJURY FROM A CHLORINE LEAK, FIRMLY TIGHTEN ALL UNIONS AFTER PIPING IS INSTALLED.
TO AVOID THE RUPTURE OF THE EVAPORATOR PRESSURE CYLINDER OR ITS CONNECTING PIPELINES, CAUSING
POSSIBLE SEVERE PERSONAL INJURY AND EQUIPMENT DAMAGE, DO NOT ATTEMPT TO DISASSEMBLE OR REPAIR
THE RELIEF VALVE. IF IT MALFUNCTIONS, REPLACE IT.
SECURELY SUPPORT THE EXPANSION TANK (e.g., WITH A BRACKET) TO AVOID DAMAGE THAT COULD RESULT
IN A MAJOR RELEASE OF LIQUID.
USE ONLY WATER TO FILL THE HOT WATER TANK AND HEAT EXCHANGER. DO NOT USE ANY SUBSTITUTE
FLUID. THE BOILING TEMPERATURE OF WATER PROVIDES A LIMIT ON AN ACCIDENTAL OVER-TEMPERATURE
CONDITION, THEREBY LIMITING THE GAS PRESSURE INSIDE THE EVAPORATOR CYLINDER.
THE TOP OF THE TANK WILL BE HOT (180°F). TO AVOID SEVERE PERSONAL INJURY DUE TO HOT SURFACES, DO
NOT REMOVE OR REINSTALL CAPLUG WITH BARE HANDS; USE A GLOVE OR OTHER INSULATING MATERIAL.
WHEN DRAINING HOT WATER OUT OF HEAT EXCHANGER, ALLOW WATER TO COOL BEFORE REMOVING PLUG.
TO AVOID SEVERE PERSONAL INJURY FROM BURNS DUE TO HOT WATER IN SIGHTGLASS TUBE, TURN POWER
OFF AND DRAIN THE TANK ENOUGH SO THAT NO WATER IS VISIBLE IN THE SIGHTGLASS. ALLOW THE SIGHT-
GLASS TO COOL BEFORE HANDLING.
WHEN HANDLING HAZARDOUS MATERIAL, IT IS THE RESPONSIBILITY OF THE EQUIPMENT USER TO OBTAIN AND
OBSERVE ALL SAFETY PRECAUTIONS RECOMMENDED BY THE MATERIAL MANUFACTURER/SUPPLIER.
BOLT THE EVAPORATOR SECURELY TO THE CONCRETE PAD.
LIFT THE EVAPORATOR BY A CRANE HAVING NO LESS THAN A ONE-TON CAPACITY RATING.
TO AVOID SEVERE PERSONAL INJURY FROM ACCIDENTAL EXPOSURE TO HIGH VOLTAGE, THE EVAPORATOR
MUST BE SUITABLY GROUNDED TO EARTH BEFORE START-UP. USE THE GROUNDING CONNECTOR PROVIDED.
LINE VOLTAGE IS PRESENT INSIDE THE CONTROL BOX EVEN WHEN THE PANEL POWER SWITCH IS IN THE OFF
POSITION. TO AVOID POSSIBLE SEVERE PERSONAL INJURY DUE TO ELECTRICAL SHOCK, DISCONNECT THE EX-
TERNAL POWER SUPPLY BEFORE SERVICING.
Содержание Wallace&Tiernan 50-200 Series
Страница 1: ...Series 50 200 Evaporator For Chlorine BOOK NO WT 050 200 001 UA IM 0814 W3T198237 ...
Страница 2: ...SERIES 50 200 EVAPORATOR FOR CHLORINE BOOK NO WT 050 200 001 UA IM 0814 W3T198237 ...
Страница 15: ...WT 050 200 001 UA IM 0814 50 200 EVAPORATOR FOR CHLORINE 4 EVOQUA W3T98237 ...
Страница 75: ...WT 050 200 001 UA IM 0814 50 200 EVAPORATOR FOR CHLORINE 64 EVOQUA W3T98237 ...
Страница 95: ...CHLORINE HANDLING MANUAL Cl2 BOOK NO WT 025 000 001 UA IM 0614 W3T98244 ...