Sensor measuring modules for MFC
Installation
4.
21
Please note
Keep the dust protection caps and watering caps of the sensors for
subsequent use.
Please note
Cable extension:
The sensor cable may be extended to a maximum length of 50 m.
The originalextension cable part number are listed in the
Instruction Manual „MFC”.
If the pH, Redox or fluoride sensor cables must be extended (max.
50 m), an impedance converter must be attached to the sensor.
The impedance converter converts the very high-resistance
sensor signal into a low-resistance signal. The impedance
converter is supplied by an installed battery. The life of the battery
is approx. 5 years; the impedance converter should be sent to
Evoqua Water Technologies GmbH for battery replacement.
Please note
The respective installation accessories must be used if installing
the pressurized conductivity electrode and membrane sensors.
Connecting the DEPOLOX
®
5 - 3 electrode cell
A Chlorine