WT.090.370.000.DE.IM.0715
Operation
Barrier M
5.
**Inputs**
There are five digital inputs:
•
Cabinet temperature
•
Ext. release
•
Desinfection min
•
Lamp 1-6: 111111
•
DIP 0101000000
The current signal state of the digital inputs can be viewed.
Press the acknowledge key to access the digital inputs submenus.
Signal status of the digital input for the cabinet temperature
Legend of the signal status
Signal status of the digital input for the external release
Legend of the signal status
Digital
input
Signal
status
Display
Description
Temp.
cabinet
1
1=ok
Contact closed, temperature
ok
0
0=not ok
Contact open, max. tempe-
rature exceeded
Ext.
release
1
1=on
Contact closed, unit in ope-
ration
0
0=off
Contact open, unit in
standby
Desinf. min
0
0=active
lamps regulate into the opti-
mal power range between
70 and 100 %
1
1=not active
no regulation, the lamps run
at full intensity (100 %)
Lamps 1-6
111111
1
1=on /
0=off
feedback from the EPS that
lamp is on resp. off
0
** Inputs **
Temp. cabinet 1
1=ok
Ext. Release 1
1=on
Содержание WALLACE & TIERNAN Barrier M 1200
Страница 1: ...WALLACE TIERNAN UV DISINFECTION UNIT BARRIER M OPERATING MANUAL...
Страница 2: ...2 WT 090 370 000 DE IM 0715 Barrier M Please note Original manual...
Страница 96: ...96 WT 090 370 000 DE IM 0715 Spare parts maintenance schedule Barrier M 6...
Страница 100: ...100 WT 090 370 000 DE IM 0715 Table of UV alarm levels Barrier M 7...
Страница 102: ...102 WT 090 370 000 DE IM 0715 Certificates declarations and statements Barrier M 8...
Страница 103: ...Barrier M Certificates declarations and statements 8 103 8 2 QPS certificate...
Страница 104: ...104 WT 090 370 000 DE IM 0715 Certificates declarations and statements Barrier M 8...
Страница 105: ...Barrier M Certificates declarations and statements 8 105 8 3 NSF certficate...
Страница 106: ...106 WT 090 370 000 DE IM 0715 Certificates declarations and statements Barrier M 8...
Страница 109: ...Barrier M 109...