IE-SNC-Tx5xx-03
21
Alarm configuration
Setting of alarms. This submenu contains:
•
setting of upper temperature limit
•
setting of lower temperature limit
•
setting of temperature hysteresis
•
setting of temperature time delay
•
setting of upper limit for humidity
•
setting of lower limit for humidity
•
setting of hysteresis for humidity
•
setting of time delay for humidity
•
setting of upper limit for dew point
•
setting of lower limit for dew point
•
setting of hysteresis for dew point
•
setting of time delay for dew point
Factory defaults – setting from the manufacturer
This selection sets the Setup items to the following values:
•
sets SMTP server address to 0.0.0.0
•
erases addresses of e-mail recipients
•
disables sending of e-mails
•
erases addresses of snmp traps recipients
•
disables sending of traps
•
enables display of www pages
•
set Graphics web
•
sets refresh time of www pages to 60 seconds
•
enables access via modbus
•
sets history logging interval to 60 s
•
setting of alarms: upper temperature limit: 300 °C, lower temperature limit: -200 °C,
temperature hysteresis: 1 °C, time delay for alarm activation after exceeding temperature
limit: 30 s, upper humidity limit: 100 %RH, lower humidity limit: 0 %RH, humidity
hysteresis: 1 %RH, time delay for humidity alarm activation after exceeding limit: 30 s,
upper limit of dew point: 80 °C, lower limit of dew point: -50 °C, hysteresis of dew point:
1 °C, time delay for dew point alarm activation after exceeding limit: 30 s.
•
set sensor name to
TRh-Sensor
or
T-Sensor
Save settings
Saves modifications to the memory and resets the device.
What to do when…
I forgot the IP address of the device
Finding the device IP address
IP address is set to the value 192.168.1.213 by the manufacturer. If you changed it and
forgot the new IP address, run the Tx5xx_setup program and press the “Find…” button. In a new
window all sensors will be show.