background image

Using This Quick Start Manual

Use this Quick Start Manual to set up your Strain Meter and
begin operation. Information is provided on how to:
• Connect ac power

• Set basic options for operation

• Connect the sensor

• Scale the meter.

Features with         are for the “B” version which has three-
color programmable “Big” LED display - All segment
characters shown are for the “B” version.

IMPORTANT:

For complete information on all setup options,

please refer to the Operator’s Manual.

Mount the Unit

1. Cut a panel opening using the

dimensions shown to the right.

2. Position the unit in the opening,

making sure the front bezel is
flush with the panel.

3. Install retaining clips on both

sides of the meter and tighten against the panel.

Wiring

1. Remove the panel at the back of the unit.
2. Locate the TB1 connector.
3. Insert the correct wire in each terminal as shown in the

following figure and tighten the lockdown screws.

4. Tug gently on the wires to verify the connections.

Connect the Sensor

1. Locate the TB2 connector on the rear of the unit.
2. Attach the sensor wires and tighten the lockdown screws.

The diagram below shows the wiring for bridge sensors
with internal excitation. 

NOTE: 

Refer to the Operator’s Manual for setup requirements

for other sensor types. 

Bridge Sensor with Internal Excitation

3. Tug gently on the wires to verify the connections.
4. Replace the panel at the back of the unit.

Using the Configuration Menu

To configure the meter, you use the buttons on the front panel.

To:

Take This Action:

Display the

Press the 

MENU

button. The first function

Configuration Menu on the menu, 

INPT

, displays.

Select a submenu

1. Press 

MENU

until the function you

function

want is shown.

2. Press 

/TARE

.

The information you can change flashes.

Select a value

1. Press 

/NT/GRS

to display the option

for that submenu

you want.

function

2. Press 

MENU

to store it.

STRD

quickly flashes, indicating that

the selection has been stored in memory. 
Then the next menu function displays.

Go back to previous Press 

RESET

once.

menu function
Exit the

Press 

RESET

twice. The unit displays 

Configuration

RST

as it reinitializes. When a numeric

Menu

value displays, the unit is in run mode.
(Optionally, you can press 

MENU

to

move through all the menu functions
until the unit reinitializes.)

NOTE: This Quick Start Manual includes specific configuration
parameters for bridge sensors with an output range of 0–100 mV
and 10 V excitation. Other sensor types may require different
parameters or additional ones. When this is the case, we refer you to
the Operator's Manual for detailed instructions.

2

3

4

Warning: Do not connect AC power to your device until you
have completed all input and output connections. This
device must only be installed by a specially trained
electrician with corresponding qualifications. Failure to
follow all instructions and warnings may result in injury!

DC Powered Unit Connections

AC Powered Unit Connections

When using DC power, do not use internal excitation or
Isolated Analog Output for high color brightness. For
low or medium brightness, internal excitation is limited
to 24 V @ 25 mA; 5 V, 10 V, 12 V @ 35 mA.

To Set the Input Type

1. Press 

MENU

until the unit displays:

2. Press 

/TARE

. The unit displays:

3. For this application you want 

100M

. If 

100M

is not

displayed, press 

/NT/GRS

until it appears. Other choices

are 

50M

10V

5V

and 

0-20

NOTE: Refer to the Operator's Manual for more information

on changing ranges.

4. Press 

MENU

to select the sensor shown. The meter

displays the next menu item. If you changed input type,
the meter displays:

To Set the Decimal Point

1. If it's not already shown, press 

MENU

until the unit displays:

2. Press 

/TARE

. The unit displays:

3. Press 

/NT/GRS

to move the decimal

point to the desired location. The
factory settings is 

FFFF

. The other

choices are 

F.FFF

FF.FF

, and 

FFF.F

.

4. Press 

MENU

to select the decimal point position shown.

The unit displays:

MENU 

SUBMENU      

/TARE

DESCRIPTION

INPT

100M

,

±50M

,

!10V

,

!±5V

,

0-20

* Input

DEC.P

FFFF

*,

F.FFF

,

FF.FF

,

FFF.F

Decimal Point

RD.S.O

IN!1

,    

RD!1

,

IN!2

,

RD!2

Scale and Offset

RD.CF

R.1=T

*,

R.1=N

Reading Configuration

R.2=0

R.2=1

R.2=2

R.2=3

R.2=4

*

R.3=F

*,

R.3=U

R.4=P

,

R.4=G

COLR

GRN

,

RED

,   

AMBR

Display Color

S1.CF

S.1=A

*,

S.1=B

Setpoint 1 Configuration

S.2=U

*,

S.2=L

S.3=N

*,

S.3=G  

shown if R.4=G 

S2.CF

S.1=A

*,

S.1=B

Setpoint 2 Configuration

S.2=U

*,

S.2=L

S.3=N

*,

S.3=G  

shown if R.4=G 

S1.DB

0003

*

Setpoint 1, Deadband

S2.DB

0003

*

Setpoint 2, Deadband

OT.CF

O.1=E

*, 

0.1=D

Analog Output

O.2=C

*, 

0.2=V

Configuration

O.3=A

*, 

0.3=P

OT.S.O

RD!1

,

OUT1

,

RD!2

,

OUT2

Output Scale & Offset

LK.CF

RS=E

*,

RS=D

Lockout Configuration

SP=E

*,

SP=D

L3=0

*,

L3=1

BRIT

M.BrT

,

L.BrT

,

H.BrT

Display Brightness

External Fuse Required:

Time-delay, UL 248-14 listed

Time-lag, IEC 127-3 recognized

175 mA (115 Vac line)

125 mA (115 Vac line)

80 mA (230 Vac line)

63 mA (230 Vac line)

Safety Consideration  

This device is marked with the international Caution symbol.

The instrument is a panel mount device protected in
accordance with Class I of EN61010-1 (AC units) and Class III
(DC units). Remember that the unit has no power-on switch.
Building installation should include a switch or circuit-breaker
that must be compliant to IEC 947-1 and 947-3.

SAFETY:

• Do not exceed voltage rating on the label located on the

top of the instrument housing.

• Always disconnect power before changing signal and

power connections.

• Do not use this instrument on a work bench without its

case for safety reasons.

• Do not operate this instrument in flammable or explosive

atmospheres.

• Do not expose this instrument to rain or moisture.

EMC:

• Whenever EMC is an issue, always use shielded cables. 
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wire close to the instrument if

EMC problems persist.

10-32 Vdc, 7.5 W

* Factory Default Settings

DP25-S and DP25B-S

Strain Gage Panel Meter

In order to maintain the same degree of protection as the
AC units, always use a Safety Agency Approval DC source
with the same Overvoltage Category and Pollution Degree.

Servicing North America:

USA:

 

 

         One Omega Drive, P.O. Box 4047

ISO 9001 Certified

 

         Stamford CT 06907-0047

 

 

         TEL: (203) 359-1660 

 

FAX: (203) 359-7700

 

 

         e-mail: [email protected]

Canada:

   

         976 Bergar

 

 

         Laval (Quebec) H7L 5A1

 

 

         TEL: (514) 856-6928 

 

FAX: (514) 856-6886

 

 

         e-mail: [email protected]

For immediate technical or application assistance:

USA and Canada:

           Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA

®

 

 

         Customer Service: 1-800-622-2378 / 1-800-622-BEST

®

 

 

         Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN

®

Mexico and

  

         TEL: (001)800-TC-OMEGA

®

 

FAX: (001) 203-359-7807 

Latin American: 

         

En Español: (001) 203-359-7803 

 

 

         e-mail: [email protected]

Servicing Europe:

Benelux:

  

         Postbus 8034, 1180 LA Amstelveen, The Netherlands

 

 

         TEL: +31 20 3472121 

 

FAX: +31 20 6434643

 

 

         Toll Free in Benelux: 0800 0993344 

 

 

         e-mail: [email protected]

Czech Republic:

 

         Frystatska 184, 733 01 Karviná

 

 

         TEL: +420 59 6311899   

FAX: +420 59 6311114

 

 

         e-mail: [email protected]

France:

   

         11, rue Jacques Cartier, 78280 Guyancourt

 

 

         TEL: +33 1 61 37 29 00  FAX: +33 1 30 57 54 27

 

 

         Toll Free in France: 0800 466 342

 

 

         e-mail: [email protected]

Germany/Austria:

           Daimlerstrasse 26, D-75392 Deckenpfronn, Germany

 

 

         TEL: +49 7056 9398-0   

FAX: +49 7056 9398-29

 

 

         Toll Free in Germany: 0800 639 7678

 

 

         e-mail: [email protected]

United Kingdom:

           One Omega Drive

ISO 9002 Certified

 

         River Bend Technology Centre

 

 

         Northbank, Irlam  Manchester M44 5BD United Kingdom  

 

 

         TEL: +44 161 777 6611  FAX: +44 161 777 6622

 

 

         Toll Free in England: 0800 488 488

 

 

         e-mail: [email protected]

OMEGAnet

®

 On-Line Service

www.omega.com

Internet e-mail

[email protected]

®

®