E2648 series Modbus holding registers (part 2)
Register addresses are shown 0-based, Addr in hexadecimal, Reg in decimal format.
Modbus holding register numbers MHR are shown in decimal 1-based format, and may be addressed either from 00001 or 40001 base.

Addr

Reg / MHR

RW

Description

Supported values (dec)

Default

0x00A2

162 / 40163 RW

Zero adjustment for temperature data,
°C × 100

-32000...+32000 (-320,00...+320,00 °C)

0

0x00A5

165 / 40166 RW

Zero adjustment for gas data, ADC

-32000...+32000 ADC units

0

0x00A6

166 / 40167 RW

Slope adjustment for gas data

1...65535

512

0x00A7

167 / 40168 RW

Change rate limit for gas data,

gas unit / s

1...32000, 0 - no limit

0

0x00A8

168 / 40169 RW

Integrating filter time constant, s

1...32000 (seconds), 0 - no filter

0

0x00C9

201 / 40202 RW

Parameter tied to analog output 1

0 – none
1 – temperature
2 – gas concentration
9 – forced Modbus control, value set in MHR / 40204

2

0x00CA

202 / 40203 RW

Parameter tied to analog output 2

0 – none
1 – temperature
2 – gas concentration
9 – forced Modbus control, value set in MHR / 40205

2

0x00CB

203 / 40204 RW

Forced value for analog output 1***

0...1000 (0,0%...100,0% of output scale)

0

0x00CC

204 / 40205 RW

Forced value for analog output 2***

0...1000 (0,0%...100,0% of output scale)

0

0x00D3

211 / 40212 RW

Parameter tied to relay RE1

0 – none
1 – temperature
2 – gas concentration
9 – control by Modbus control, state set in MHR / 40214

2

0x00D4

212 / 40213 RW

Parameter tied to relay RE2

0-none
1 – temperature
2 – gas concentration
9 – control by Modbus control, state set in MHR / 40215

2

0x00D5

213 / 40214 RW

Forced state for relay RE1***

0 – off, 1 – on

0

0x00D6

214/ 40215 RW

Forced state for relay RE2***

0 – off, 1 – on

0

0x00D7

215 / 40216 RW

Switching delay for relay RE1

0...1000 (s)

0

0x00D8

216 / 40217 RW

Switching delay for relay RE2

0...1000 (s)

0

0x00D9

217 / 40218 RW

Minimal on/off time for relay RE1

0...1000 (s)

0

0x00DA

218 / 40219 RW

Minimal on/off time for relay RE2

0...1000 (s)

0

* – The new value is applied after restart.
** – Broadcast slave ID 0 can be used to assign a new ID to device with unknown ID. When addressing by ID 0 the device shall be

the only Modbus instrument in the network. The device will not respond to Master command when addressed by ID 0.

*** – This value is dynamic and not kept in EEPROM after restart

Содержание PluraSens E2648-PID

Страница 1: ...erial and workmanship for a period of one year from the date of original sale During this warranty period Manufacturer will at its option either repair or replace product that proves to be defective T...

Страница 2: ...and or digital interface terminals to the necessary devices according to the relevant connection diagram The screwless quick connect spring terminals on the E2648 series devices are suitable for a wi...

Страница 3: ...may be addressed either from 00001 or 40001 base Addr Reg MHR RW Description Supported values dec Default 0x0001 1 40002 R Hardware version 0x0002 2 40003 R Software version 0x0003 3 40004 R Product s...

Страница 4: ...in MHR 40205 2 0x00CB 203 40204 RW Forced value for analog output 1 0 1000 0 0 100 0 of output scale 0 0x00CC 204 40205 RW Forced value for analog output 2 0 1000 0 0 100 0 of output scale 0 0x00D3 2...

Страница 5: ...0 1 LED is on off in normal condition bit 11 0 1 LED and buzzer syncing off on with RE1 bit 12 0 1 LED and buzzer syncing off on with RE2 user defined 0x0101 257 40258 R Raw gas sensor data ADC data 0...

Страница 6: ...sure to high levels of ethyl acetate results first in irritation of the eyes nose and throat followed by headache nausea vomiting sleepiness and unconsciousness Exposure limits NIOSH TWA 8 hours 1400...

Страница 7: ...Semi Volatile Organic Compound SVOC cannot be measured NA Not available Occasionally you will be measuring a mixture of VOCs If the total concentration is within the linear range of your PID then it i...

Страница 8: ...29 Benzyl acetate C9H10O2 140 11 4 9 0 6 30 Benzyl alcohol C7H8O 100 51 6 8 26 1 6 125 31 Camphor C10H16O 76 22 2 8 76 0 4 32 Carbon dioxide CO2 124 38 9 13 77 NR 0 0 33 Carbon disulfide CS2 75 15 0 1...

Страница 9: ...hyl benzoate C9H10O2 93 89 0 8 9 0 9 68 Ethyl butyrate C6H12O2 105 54 4 9 9 1 4 5 100 69 Ethylamine C2H7N 75 04 7 8 86 1 5 100 70 Ethylbenzene C8H10 100 41 4 8 76 0 56 3 50 71 Ethylcyclohexane C8H16 1...

Страница 10: ...C8H18O 26952 21 6 9 8 1 7 9 170 143 Isopentane C5H12 78 78 4 10 32 4 30 600 144 Isopentanol C5H12O 137 32 6 9 86 2 145 Isopentene C5H10 563 46 2 9 12 0 8 146 Isoprene 2 methyl 1 3 butadiene C5H8 78 79...

Страница 11: ...alic acid C2H2O4 144 62 7 11 2 NR 182 Oxalyl bromide C2Br2O2 15219 34 8 10 49 5 183 Oxydiethanol 2 2 diethylene glycol C4H10O3 111 46 6 10 3 2 20 400 184 Oxygen O2 7782 44 7 12 07 NR 185 Ozone O3 1002...

Страница 12: ...8 9 6 0 7 221 Rose oxide cis Tetrahydro 4 methyl 2 2 methylpropenyl 2H pyran C10H18O 16409 43 1 9 0 8 222 Sec amyl acetate C7H14O2 626 38 0 9 9 5 223 Sevoflurane 1 1 1 3 3 3 hexafluoro 2 fluoromethox...

Страница 13: ...window that presents itself as a blue hue To check for contamination hold the lamp in front of a light source and look across the window surface To avoid contaminating the sensor and affecting accurac...

Отзывы: