background image

cuiheat.com

126345-01D

5

AIR FOR COMBUSTION AND VENTILATION

 WARNING: This heater shall not be installed in a 

room or space unless the required volume of indoor 

combustion air is provided by the method described 

in the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54,

 

the 

International Fuel Gas Code,

 or applicable local 

codes. Read the following instructions to ensure proper 

fresh air for this and other fuel-burning appliances in 

your home.

Today’s homes are built more energy efficient than ever. New materi-

als, increased insulation and new construction methods help reduce 

heat loss in homes. Homeowners apply weather strip and caulk 

around windows and doors to keep the cold air out and the warm 

air in. During heating months, homeowners want their homes as 

airtight as possible.
While it is good to make your home energy efficient, your home needs 

to breathe. Fresh air must enter your home. All fuel-burning appliances 

need fresh air for proper combustion and ventilation.
Exhaust fans, some fireplaces, clothes dryers and some fuel burning 

appliances draw air from the house to operate. You must provide ad-

equate fresh air for these appliances. This will ensure proper venting 

of vented fuel-burning appliances.

PROVIDING ADEQUATE VENTILATION

The following are excerpts from National Fuel Gas Code, ANSI Z223.1/

NFPA 54, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation 

classifications:
1.  Unusually Tight Construction
2.  Unconfined Space
3.  Confined Space
The information on Pages 5 through 6 will help you classify your 

space and provide adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and windows may provide enough 

fresh air for combustion and ventilation. However, in buildings of 

unusually tight construction, you must provide additional fresh air.

Unusually tight construction is defined as construction where:
a.  walls and ceilings exposed to the outside atmosphere have a 

continuous water vapor retarder with a rating of one perm (6 x 

10

-11

 kg per pa-sec-m

2

) or less with openings gasketed or sealed 

and

b.  weather stripping has been added on openable windows and 

doors and

c.  caulking or sealants are applied to areas such as joints around 

window and door frames, between sole plates and floors, be-

tween wall-ceiling joints, between wall panels, at penetrations 

for plumbing, electrical and gas lines and at other openings.

If your home meets all three criteria above, you must provide 

additional fresh air. See Ventilation Air From Outdoors, page 6. 
If your home does not meet all three criteria above, proceed to 

Determining Fresh-Air Flow For Heater Location.

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1/NFPA54 allows two methods 

for determining whether the space in which the heater is being in-

stalled is confined or unconfined space. The standard method defines 

a confined space as a space whose volume is less than 50 cubic feet 

per 1,000 Btu per hour (4.8 m

3

 per kw) of the aggregate input rating 

of all appliances installed in that space and an unconfined space as 

a space whose volume is not less than 50 cubic feet per 1,000 Btu 

per hour (4.8 m

3

 per kw) of the aggregate input rating of all appli-

ances installed in that space. Rooms communicating directly with the 

space in which the appliances are installed*, through openings not 

furnished with doors, are considered a part of the unconfined space. 

Where the air infiltration rate of a structure is known, the Known Air 

Infiltration Rate Method may be used. Follow The National Fuel Gas 

Code, ANSI Z223.1/NFPA 54 to use this method to determine if the 

space is confined or unconfined.
* Adjoining rooms are communicating only if there are doorless 

passageways or ventilation grills between them.

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space Using 

the Standard Method

Use this work sheet to determine if you have a confined or uncon-

fined space.

Space:

 Includes the room in which you will install heater plus any 

adjoining rooms with doorless passageways or ventilation grills 

between the rooms.
1.  Determine the volume of the space (length x width x height).
  Length x Width x Height =__________cu. ft. (volume of space)
  Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling 

height) = 2560 cu. ft. (volume of space)

  If additional ventilation to adjoining room is supplied with grills 

or openings, add the volume of these rooms to the total volume 

of the space.

2.  Multiply the space volume by 20 to determine the maximum Btu/

Hr the space can support.

   _______ (volume of space) x 20 = (Maximum Btu/Hr the space 

can support)

  Example: 2560 cu. ft. (volume of space) x 20 = 51,200 (maximum 

Btu/Hr the space can support)

3.  Add the Btu/Hr of all fuel burning appliances in the space.
  Vent-free fireplace  ________Btu/Hr
  Gas water heater*  ________Btu/Hr
  Gas furnace 

 ________Btu/Hr

  Vented gas heater  ________Btu/Hr
  Gas fireplace logs  ________Btu/Hr
  Other gas appliances* + ____Btu/Hr
 Total 

= _______Btu/Hr

  * Do not include direct-vent gas appliances. Direct-vent draws 

combustion air from the outdoors and vents to the outdoors.

  Example: 
  Gas water heater      40,000 Btu/Hr
  Vent-free fireplace  +  33,000 Btu/Hr
 Total 

 73,000 Btu/Hr

Содержание EWPO2430NV

Страница 1: ...installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ventilation section on page 5 of this manual WARNING If the information in these instr...

Страница 2: ...this fireplace can cause serious injury or death from burns fire explosion electrical shock and carbon monoxide poisoning DANGER Carbon monoxide poisoning may lead to death Carbon Monoxide Poisoning...

Страница 3: ...for Vented Operation Page 9 This gas log set may not be installed as a vented appliance in a bedroom or bathroom in the Commonwealth of Massachusetts 5 Before installing in a solid fuel burning firep...

Страница 4: ...The flexible gas line connector used shall not exceed 36 inches 92 centimeters in length The individual manual shut off must be a T handle type valve Un vented appliances may NOT be installed in bedr...

Страница 5: ...Air From Outdoors page 6 If your home does not meet all three criteria above proceed to Determining Fresh Air Flow For Heater Location Confined and Unconfined Space The National Fuel Gas Code ANSI Z22...

Страница 6: ...GasCode orapplicablelocalcodes VENTILATION AIR Ventilation Air From Inside Building This fresh air would come from an adjoining unconfined space When ventilating to an adjoining unconfined space you m...

Страница 7: ...ater as your primary heat source WARNING A qualified service person must install heater Follow all local codes NOTICE Stateorlocalcodesmayonlyallowoperation ofthisapplianceinaventedconfiguration Check...

Страница 8: ...ntel shelf See Figure 5 and Figures 6 and 7 Page 9 for minimum clearances IMPORTANT If you cannot meet these minimum clearances you must operate heater with chimney flue damper open Go to Installing D...

Страница 9: ...5 F or higher on the underside of the mantel Determining Minimum Mantel Clearance When Using a Hood If minimum clearances in Figure 6 are not met you must have a hood When using a hood there are still...

Страница 10: ...work properly Installation Items Needed hardware package provided with heater approved flexible gas hose and fittings if allowed by local codes not provided sealant resistant to propane LP gas not pro...

Страница 11: ...T Tap Approved Flexible Gas Hose if allowed by local codes PROPANE LP From External Regulator 11 W C to 14 W C Pressure NATURAL From Gas Meter 5 W C to10 5 W C Pressure Sediment Trap Tee Joint Cap Pip...

Страница 12: ...Check reconnected fittings for leaks Test Pressures Equal To or Less Than 1 2 PSIG 3 5 kPa 1 Close equipment shutoff valve see Figure 14 2 Pressurize supply piping system by either opening propane LP...

Страница 13: ...lace 6 DisconnectjumperwirefromcontrolvalveatTPTHandTHlocations see Figure 18 7 Connect wires to control valve at the TPTH and TH locations as shown in Figure 19 NOTE Make sure excess wire does not in...

Страница 14: ...0 models Place the right top log as shown in Figure 26 Page 15 This log will fit on the matching flat recess on the front middle and rear logs WARNING Failure to position the parts in ac cordance with...

Страница 15: ...Right Top Log for 24 and 30 Log Set Figure 27 Installing Short Cross Log for 30 Models Only Short Cross Log INSTALLATION Continued 7 For 30 models place short cross log as shown in Figure 27 8 Final a...

Страница 16: ...pins on base see Figures 31A and 32 Figure 33 Placing 18 Bottom Front Log Figure 34 Placing 18 Top Right Log Figure 35 Placing 18 Left Top Log Final Assembly for 18 Model Grate Fingers Pin for Top Lef...

Страница 17: ...es in bottom of log must seat over pins on base see Figures 36A and 37 Figure 38 Placing 24 30 Bottom Front Log Figure 39 Placing 24 30 Top Middle Log Figure 40 Placing 24 30 Top Left Log Pins for Top...

Страница 18: ...IONS WARNING Iffireplacehasglassdoors neveroperatethisheater with glass doors closed If you operate heater with doorsclosed heatbuildupinsidefireplacewillcause glass to burst Make sure there are no ob...

Страница 19: ...ed contact a quali fied service person or gas supplier for repairs NOTE If pilot goes out repeat steps 4 through 8 OPERATION Continued Figure 43 Control Knob and Igniter Button Location Shown as Suppl...

Страница 20: ...carpeting pet hair bedding material etc WARNING Failure to keep the primary air opening s oftheburner s cleanmayresultinsooting and property damage BURNER ORIFICE HOLDER AND PILOT AIR INLET HOLE The p...

Страница 21: ...Remove blockage Blocked burner flame holes will create soot Clean the pilot assembly also A yellow tip on the pilot flame indi cates dust and dirt in the pilot assembly There is a small pilot air inl...

Страница 22: ...ocouple connection loose at con trol valve 7 Thermocouple damaged 8 Control valve damaged REMEDY 1 Reconnect Igniter cable 2 Free Igniter cable if pinched by any metal or tubing Keep Igniter cable dry...

Страница 23: ...valve 1 Check burner for dirt and debris If found clean burner see Cleaning and Mainte nance Page 20 2 Problem will stop after a few hours of operation 1 Turn control knob to LO position and let warm...

Страница 24: ...t see Cleaning and Main tenance Page 20 1 Locate and correct all leaks see Checking Gas Connections Page 12 2 Replace control valve 1 Locate and correct all leaks see Checking Gas Connections Page 12...

Страница 25: ...o low If so contact your local propane LP or natural gas supplier TECHNICAL SERVICE You may have further questions about installation operation or troubleshooting If so contact CUI at 1 800 845 5301 W...

Страница 26: ...cuiheat com 126345 01D 26 WIRING DIAGRAM Thermopile Jumper Wire...

Страница 27: ...cuiheat com 126345 01D 27 PARTS BURNER SYSTEMS EWPO2430NV AND EWPO2430PV 3 1 6 2 18 19 8 9 10 11 16 17 15 12 14 13 5 4 7 2...

Страница 28: ...R NG YELLOW FLAME 1 J5538 BURNER LP YELLOW FLAME 1 9 J6424 PILOT ODS COPRECI 243 MV LP 1 J6426 PILOT NG MV COPRECI 1 10 J3635 TUBE PILOT 1 11 J3569 CABLE IGNITER 1 12 J3618 INJECTOR 111 2 82MM 1 J3617...

Страница 29: ...24R J0627 EWPO30R J0632 QTY 1 J6763 Rear Log 1 J6767 Rear Log 1 J6771 Rear Log 1 2 J6764 Middle Log 1 J6768 Middle Log 1 J6772 Middle Log 1 3 J6765 Front Log 1 J6769 Front Log 1 J6773 Front Log 1 4 J6...

Страница 30: ...ar Bottom Log EW 1 F2894 30 Rear Bottom Log EW 1 2 F2884 18 Middle Bottom Log EW 1 F2889 24 Middle Bottom Log EW 1 F2893 30 Middle Bottom Log EW 1 3 F2883 18 Front Bottom Log EW 1 F2888 24 Front Botto...

Страница 31: ...1760 Model GA6080 For Remote Ready and Variable Manually Controlled Models Permanently opens chimney flue damper for vented operation LAVA ROCK Cat No 80L42 formerly F0248 Model FDVS For all models Or...

Страница 32: ...___________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _______...

Страница 33: ...___________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _______...

Страница 34: ...___________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _______...

Страница 35: ...approved by CUI Warranty parts must be obtained through authorized dealers of this product and or CUI who will provide original factory replacement parts Failure to use original factory replacement pa...

Страница 36: ...e SC 29681 CUI reserves the right to make changes at any time without notice in design materials specifications and prices and also to discontinue colors styles and products Consult your local distrib...

Отзывы: