66
P21
Minimum time between compressor Off and On
0
99
3
Min
Defrosting
P22
Type of Defrost
0
2
1
-
0 = electric
1 = hot gas
2 = air
P23
Evaporator Temperature for End of Defrost
0
2
8
°C
P24
Maximum Defrost duration
1
99
10
Min
P25
Delay between two Automatic defrosts in Storage
0
99
12
Ore
P26
Delay in defrost activation from the start of Storage
0
99
0
Min
P27
Enable Defrost at Blast chilling/Freezing Cycle start
0
1
0
-
P28
Draining time
0
99
2
Min
P29
Ignore compressor safety times in defrost
0
1
0
-
P30
Delay in compressor activation from defrost request
0
400
30
Sec
P31
Delay in solenoid valve activation from defrost request
0
400
35
Sec
Evaporator fan
P32
Evaporator temperature above which the Fans are locked in Storage
-40
99
10
°C
P33
Hysteresis for restarting Fans
-15
15
1
°C
P34
Enables use of fans in Defrost (for P22 equal to zero and/or one)
0
1
0
-
0 = fans off during defrost
1 = fans active during defrost
P35
Duration of fans lock after draining
0
15
1
Min
P36
Threshold temperature for Fans Lock cell
-40
99
90
°C
P37
Door opening effect on the fans
0
1
1
-
0 = no effect
1 = stop fans
Digital inputs
P38
Door micro input polarity
0
1
0
-
0 = NO; 1 = NC
P39
Door opening signalling delay
0
200
0
Sec
P40
High Pressure Alarm input polarity
0
1
1
-
0 = NO; 1 = NC
P41
High Pressure Alarm Input Delay
0
200
120
Sec
P42
Low Pressure Alarm input polarity
0
1
0
-
0 = NO; 1 = NC
P43
Low Pressure Alarm Input Delay
0
200
0
Sec
P44
Thermal Compressor Alarm input polarity
0
1
1
-
0 = NO; 1 = NC
P45
Thermal Compressor Alarm input Delay
0
200
0
Sec
Sterilization
P46
UV Lamp Start Duration
0
99
20
Min
0 = disabled
Heating the Needle probe (not activated)
P47
Needle probe Heating Activation threshold
-40
99
45
°C
P48
Duration of Needle probe heating
0
99
15
Sec
Door Frames
P49
Cell temperature threshold for Door Frame Activation
-20
20
0
°C
P50
Hysteresis for door frame activation
-10
10
2
°C
Condenser Fans
P51
Condenser fan management mode (only if condenser probe enabled)
0
1
1
-
0 = in parallel with the compressor
1 = always active during the cycles