Instruction Manual for SUPERLINE series battery back-ups
2010/01/13
www.ever.eu
29
The HYBRID (MIXED) mode
In the HYBRID mode the battery back-up provides power to the output from
the basic mains line while supplying the missing power from accumulators.
The BATTERY mode
If the basic mains input line or the BYPASS line in ECO mode fails to meet the
criteria of correct mains parameters, the battery back-up switches to the BATTERY
mode (battery operation). In the BATTERY mode the inverter provides power to the
accumulator output.
The ECO (ECONOMICAL) mode
Mode forced by the user by setting up the control flag (KONTROLA 2/4; ECO).
With the ECO control flag active the NORMAL and HYBRID modes are unavailable.
For the battery back-up to work in ECO mode the criteria of correct mains
parameters must be met for the basic and BYPASS lines. Incorrect parameters of
either line will cause the battery back-up to switch to BATTERY mode. With the ECO
flag set the battery back-up behaves similarly to an OFF-LINE type UPS. In ECO
mode the output is supplied with power from the BYPASS line or from the
accumulators (BATTERY mode). Internal power units are not involved in energy
processing, which increases the battery back-up’s efficiency.
The STOP mode
The battery back-up is switched off (from the user interface); no voltage
meeting the criteria of correct parameters is available on the basic line. It is also the
intermediate state when the battery back-up switches from BYPASS and
EMERGENCY modes.
The CZUWANIE (SLEEP) mode
The battery back-up is switched off (from the user interface); the basic line
meets the criteria of correct mains parameters. Battery preservation mechanisms are
active. When the battery back-up switches from STANDBY to SLEEP mode the
accumulator charge level is checked. If the charge level is below the set threshold
(KONFIGURACJA 3/4; Poj. z STB.), the battery back-up remains in this mode until
the required minimum charge is reached.
The STANDBY mode
The battery back-up may only switch to STANDBY mode from the BATTERY
mode when the accumulators are completely discharged or when forced by the user
(KONTROLA 2/4; UPS->STB). The mode switching is performed after the set time
has elapsed (KONFIGURACJA 2/4; Opoz.STB).
The battery back-up remains in this mode if the basic line voltage fails to meet the
criteria of correct mains parameters while the device is switched on.
Turning the battery back-up off causes it to switch to the STOP or SLEEP mode.
The BYPASS mode
The BYPASS mode is triggered when the battery back-up is overloaded or
when forced by the user (KONTROLA 3/4; UPS->BYPASS).
In such a case the output power is provided by the BYPASS line.