Instruction Manual for SUPERLINE series battery back-ups
2010/01/13
www.ever.eu
24
8.
After verifying the correctness of connections secure the terminals by replacing
the stoppers. Secure the cables against accidental pulling out by fastening them
with bands to special grips located below the terminals.
9.
Enable the safeguards in the room’s/building’s switching station.
10. Replace the fuse-elements in the respective holders.
11. Close all fuse holders of all connected battery modules.
12. Close the F1 holder on the battery back-up.
13. Wait at least 10 seconds.
14. Close the F2 holder on the battery back–up – accumulators are now
connected.
15. Switch the F3 and F4 circuit breakers to ON.
16. Set up the accumulator parameters of the battery back-up (KONFIGURACJA
4/4).
17. Launch the battery back-up via the user interface (KONTROLA 1/4; UPS).
The displayed data associated with the number of connected accumulators will be
automatically updated once the accumulators are topped up. Until that time the
indications may differ from the actual state.
Disconnecting the modules
1.
Shut down the battery back-up via the user interface (KONTROLA 1/4; UPS).
2.
Switch the F3 and F4 circuit breakers on the battery back-up to OFF.
3.
Disable the safeguards of the basic and BYPASS lines in the room’s/building’s
switching station.
4.
Disable the F1, F2 and F5 safeguards on the battery back-up and the F1 and
F2 safeguards on all battery modules by opening the fuse holders and removing
the fuse-elements.
5.
Remove the connector stoppers.
6.
Disconnect the modules. The connecting cables must be completely
disconnected.
7.
Secure the connectors by replacing the protective stoppers.
8.
Enable the safeguards in the room’s/building’s switching station.
9.
Replace the fuse-elements in the respective holders.
10. Close the fuse holders of all connected battery modules (if any).
11. Close the F1 holder on the battery back-up.
12. Wait at least 10 seconds.
13. Close the F2 holder on the battery back–up – accumulators are now
connected.
14. Switch the F3 and F4 circuit breakers to ON.
15. Set up the accumulator parameters of the battery back-up (KONFIGURACJA
4/4).
WARNING! Never leave leads unconnected! The current flowing in
them may be hazardous to health and possibly lethal!