EVCO | 21.10.2020 | AZ
| 11
144EJBSI104
EVLJBOX HP Sequencer -
Application manual
Connector 7
Number
Description
USB
USB port to programme the device
Connector 8
Number
Description
AO4
AO4 analogue output (for 0-10 V or PWM signal)
AO3
AO3 analogue output (for 0-10 V or PWM signal)
AO2
AO2 analogue output (for 0-10 V or PWM signal)
AO1
AO1 analogue output (for 0-10 V or PWM signal)
DI4
DI4 digital input
(dry contact and for pulse trains up to 2 KHz)
DI3
DI3 digital input
(dry contact and for pulse trains up to 2 KHz)
IN7
AI7 analogue input
(for PTC, NTC or Pt 1000 probes); can also be
configured for DI11 dry contact digital input
IN6
AI6 analogue input
(for PTC, NTC or Pt 1000 probes); can also be
configured for DI10 dry contact digital input
IN5
AI5 analogue input
(for PTC, NTC or Pt 1000 probes); can also be
configured for DI9 dry contact digital input
IN4
AI4 analogue input
(for PTC, NTC or Pt 1000 probes); can also be
configured for DI8 dry contact digital input
IN3
AI3 analogue input
(for NTC probes, 0-5 V, 0-10 V, 0-20 mA or 4-20 mA
transd.); can also be configured for DI7 dry contact
digital input
IN2
AI2 analogue input
(for NTC probes, 0-5 V, 0-10 V, 0-20 mA or 4-20 mA
transd.); can also be configured for DI6 dry contact
digital input
IN1
AI1 analogue input
(for NTC probes, 0-5 V, 0-10 V, 0-20 mA or 4-20 mA
transd.); can also be configured for DI5 dry contact
digital input
GND
Reference (GND)
12VS
Auxiliary power supply (12 VDC)
5VS
0-5 V ratiometric transducers power supply (5
VDC)