EVCO | 21.10.2020 | AZ
| 26
144EJBSI104
EVLJBOX HP Sequencer -
Application manual
Code
Parameter description
Default
Min
Max
U.M.
Menu
Notes
PC10
Kind of regulation condenser valve
0: Minimum ON
1: Enabling step
0
0
1
IS-E
Security
PA01
Probe alarm delay
10
0
240
Sec
IS-S
PA02
Evaporator low temperature alarm
setpoint
-10.0
-15.0
PA04
°C
IS-S
PA03
Evaporator low temperature alarm
differential
5.0
0.1
20.0
°C
IS-S
PA04
Evaporator high temperature alarm
setpoint
60.0
PA02
70.0
°C
IS-S
PA05
Evaporator high temperature alarm
differential
5.0
0.1
20.0
°C
IS-S
PA06
Condenser low temperature alarm
setpoint
-10.0
-15.0
PA08
°C
IS-S
PA07
Condenser low temperature alarm
differential
5.0
0.1
20.0
°C
IS-S
PA08
Condenser high temperature alarm
setpoint
65.0
PA06
70.0
°C
IS-S
PA09
Condenser high temperature alarm
differential
5.0
0.1
20.0
°C
IS-S
PA10
Enable RTC alarm
NO (0)
NO (0)
YES (1)
IS-S
PA11
Type of RTC alarm re-arm:
0: Automatic
1: Manual
0
0
1
IS-S
CAN network
PH09
CAN network local node
1
1
127
IS-CAN
PH10
CAN Baud rate:
1: 20 KB
2: 50 KB
3: 125 KB
4: 500 KB
3
1
4
KB
IS-CAN
MODBUS network
PH12
Baud rate of MODBUS communication:
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 28800
6: 38400
7: 57600
3
0
7
IS-M
PH13
MODBUS parity:
0: None
1: Odd
2: Even
2
0
2
IS-M
PH14
MODBUS stop bit:
0: 1 stop bit
1: 2 stop bit
0
0
1
IS-M
Default
PH15
Reset manufacturer’s default parameters
NO (0)
NO (0)
YES (1)
IS-D
Wait for the NO
(0) value on reset
completion
Other parameters