EVCO S.p.A.
EVFTFT219 | Installation guide ver. 1.0 | Code 144FTFT219E104
pagina 36 di 50
PARAM.
DEFAULT
MIN.
MAX.
M.U.
FANS
F01
1
0
1
- - - -
evaporator fans
0
= disabled
1
= enabled
refer also to parameter C09
F02
0
0
1
- - - -
condenser fans
0
= disabled
1
= enabled
refer also to parameter C08
F03
5
5
50
°C/°F
(1)
evaporator fans setpoint during normal operation
-
fans are activated if evaporator T°
≤
F03
-
fans are deactivated if evaporator T°
≥
F03+5°C
F04
15
0
50
°C/°F
(1)
condenser fans setpoint
-
fans are activated when compressor is on and if condenser T°
≥
F04+5°C
-
fans are deactivated if evaporator T°
≤
F04 or when
compressor is switched off, with delay time set by parameter
F08
If the condenser probe is faulty or not installed, fans are switched
on/off in parallel with the compressor and depending on F08
F05
0
0
1
- - - -
evaporator fans during defrosting
0
= disabled
1
= enabled
F06
0
0
2
- - - -
condenser fans during defrosting
0
= disabled
1
= enabled
2
= thermoregulated according to the setpoint given by F04
F07
4
-40
50
°C/°F
(1)
evaporator fans activation temperature following the defrosting end or
the device switch-on
F08
0
0
300
s
condenser fan delay
PARAM.
DEFAULT
MIN.
MAX.
M.U.
GENERAL
G01
0
0
900
s
buzzer reactivation after silencing
0
= disabled
PARAM.
DEFAULT
MIN.
MAX.
M.U.
ENERGY SAVING
ES1
24
0
24
h
energy saving start time
24h = disabled