EVCO S.p.A.
EVFTFT219 | Installation guide ver. 1.0 | Code 144FTFT219E104
pagina 35 di 50
C09
1
0
2
- - - -
evaporator fans control
0
= enabled depending on evaporator temperature: the fans are
activated depending on F03 during normal operation and
depending on F07 following a defrosting or a device switch-on
1
= enabled in parallel with the compressor during the normal
operation or depending on F07 following a defrosting or a
device switch-on
2
= the fans are always activated during normal operation and
depend on F07 following a defrosting or a device switch-on
No matter what the value given to parameter C09 is, the ventilation is
stopped under the following circumstances:
-
door opening (see C01); the fans can be reactivated 10
seconds after closing the door or if the door remains open for
more than C03 seconds
-
high condenser T° or dirty condenser alarm (see paragraph
11.1)
C12
-7
-25
20
°C/°F
(1)
door heaters switch-on temperature
-
door heaters output activated if cabinet T°
≤
C12
-
door heaters output deactivated if cabinet T°
≥
C12+2°C
C13
0
0
1
- - - -
product probe
0
= disabled
1
= enabled
PARAM.
DEFAULT
MIN.
MAX.
U.M.
REGULATION
R01
2
0
20
°C/°F
(1)
hysteresis related to the compressor regulation setpoint:
-
Compressor activated if cabinet T°
≥
SR01
-
Compressor deactivated if cabinet T°
≤
Setpoint
R02
1
0
30
min
minimum time span between two successive compressor switch-ons
R03
0
0
300
s
compressor activation delay since the device switch-on
R04
10
0
300
s
minimum time span between compressor switch-on and switch-off
R05
0
0
300
min
compressor ON time allowed when compressor use alarm or cabinet
probe error alarm are in progress
R06
0
0
300
min
compressor OFF time allowed when compressor use alarm or cabinet
probe error alarm are in progress
R07
100
0
100
%
maximum percentage limit allowed for compressor operation
R08
15
-50
50
°C/°F
(1)
maximum value allowed for the setpoint
R09
2
-50
50
°C/°F
(1)
minimum value allowed for the setpoint