EVCO S.p.A.
EVDRIVE04 | User manual ver. 1.0 | Code 144EPD4I104
Page 51 of 78
0 = barG
1 = barA
P4YM
1676
RW
P4Ym
300.00 barG/barA
1.00
Manufact.
Y max value
P4Ym 1677
RW
-
300.00
P4YM
barG/barA
0.00
Manufact.
Y min value
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Probe settings: offset
OfsTs 1678
RW
-10.0
10.0
K
0.0
User
suction temperature offset
OfsTe 1679
RW
-10.0
10.0
K
0.0
User
suction
pressure
(converted
into
temperature) offset
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Communication settings
Mb0a
1729
RW
1
247
- - - -
1
Manufact.
MODBUS RS-485 port address
Mb0p
1730
RW
0
2
- - - -
2
Manufact.
MODBUS RS-485 port parity
0 = none
1 = odd
2 = even
Mb0b
1731
RW
0
4
- - - -
3
Manufact.
MODBUS RS-485 port baud rate
0 = 1,200
1 = 2,400
2 = 4,800
3 = 9,600
4 = 19,200
Mb0s
1733
RW
0
1
- - - -
0
Manufact.
MODBUS RS-485 port stop bit
0 = 1 bit
1 = 2 bit
CANn
1739
RW
1
127
- - - -
11
Manufact.
CAN node address
CANb
1744
RW
0
4
- - - -
1
User
CAN baud rate
0 = 10K
1 = 20K
2 = 50K
3 = 125K
4 = 500K
CANt
1741
RW
1
60
s
5
User
CAN timeout
Par.
Add. Acc.
Min.
Mas.
Unità
Default
Menu
Simulation
Ps01
1700
RW
0
1
-
0
User
Enable simulation mode
0: normal mode
1: simulation mode
Ps02
1704
RW
0
1
-
0
User
DI 1 Simulation value
Ps03
1705
RW
0
1
-
0
User
DI 2 Simulation value
Ps04
1706
RW
0
1
-
0
User
DI HV Simulation value