EVCO S.p.A.
EVDRIVE04 | User manual ver. 1.0 | Code 144EPD4I104
Page 55 of 78
Psp
1799
RO
0.00
100.00
%
- - - -
User
target position
EnaS
1800
RO
0
1
- - - -
- - - -
User
enable valve status
0 = valve not enabled
1 = valve enabled
ResS
1801
RO
0
1
- - - -
- - - -
User
resynchronization request status
0 = no request
1 = request reserved
IhoS
1802
RO
0
1
- - - -
- - - -
User
holding current status
0 = operating phase current
1 = holding phase current
Te
1803
RO
- - - -
- - - -
°C
- - - -
User
Te (evaporation temperature)
Pe
1804
RO
- - - -
- - - -
barG
- - - -
User
Pe (evaporation pressure)
Ts
1805
RO
- - - -
- - - -
°C
- - - -
User
Ts (suction temperature)
SH
1806
RO
- - - -
- - - -
K
- - - -
User
SH
SpSH
1807
RO
- - - -
- - - -
K
- - - -
User
SH setpoint
SetS
1808
RO
1
2
- - - -
- - - -
User
selected SH parameters set
PidP
1809
RO
- - - -
- - - -
%
- - - -
User
PID setpoint position output
ParS
1810
RO
0
2
- - - -
- - - -
User
parameters status
bit0: disable the valve to accept new
parameters
bit1: reset the board to accept new
parameters
SRat
1811
RO
- - - -
- - - -
step/s
- - - -
User
actual value step rate
SetM
1813
RO
- - - -
- - - -
K
- - - -
User
SH setpoint SH with MOP correction
Upr
1814
RO
- - - -
- - - -
- - - -
- - - -
User
used probes
b 0: AI1
b 0: AI2
b 0: AI3
b 0: AI4
TsPr
1815
RO
- - - -
- - - -
- - - -
- - - -
User
Ts prymary probe
0: AI1
0: AI2
0: AI3
0: AI4
PePr
1816
RO
- - - -
- - - -
- - - -
- - - -
User
Pe prymary probe
0: AI1
0: AI2
0: AI3
0: AI4
TsPrB 1817
RO
- - - -
- - - -
- - - -
- - - -
User
Ts backup probe