EVCO S.p.A.
EV3 HP & EVD HP | Installer manual ver. 1.2 | Code 1443DHPE124
page 42 of 52
AFLo
Flow alarm
This alarm is activated when the input configured as a flow switch is active for a period of AL09, with a delay of AL08
from pump switch-on; it is deactivated when the input is inactive for a time amounting to AL10.
It reverts to manual re-arm if the number of alarm events in an hour exceeds AL07.
Main results
-
All functions switched off.
AHtr
High temperature alarm
This alarm is activated when the input water temperature exceeds AL15 for a period longer than AL16. It is deactivated
when the temperature is lower than AL15-AL13.
Main results
-
The compressor is switched off.
EA01
EA02
EA03
EA04
EA05
Probe alarms
The alarm is activated in the following situations:
-
when a probe short circuits or is interrupted
-
if the upper or lower limits set for a probe are exceeded
Main results
-
All functions switched off.