EVCO S.p.A.
EV3 HP & EVD HP | Installer manual ver. 1.2 | Code 1443DHPE124
page 20 of 52
4.3
Termination of the RS-485 MODBUS line
To reduce reflections on the signal transmitted along the cables connecting the devices to a RS-485 network it is necessary to
terminate the line ONLY at the first and last element in the network.
To terminate the line, it will be sufficient to place EV3 HP micro-switch 1 in position ON. Do not touch micro-switch 2.
When using EVD HP, place micro-switch 1 in position ON.